English
1-13
IMPORTANT:
* These values are for information only, they should be checked and selected to comply with the local and/or
national codes and regulations. They are also subjected to the type of installation and size of conductors
used.
** The appropriate voltage range should be checked with data label on the unit.
Indoor Unit
Terminal Block
Outdoor Unit
Terminal Block
5CEY15E/ER - 5SLY15D/DR
5CEY20/25E/ER - 5SLY20/25C/CR
Power Supply Cable
L
N
SIG
!
!
2
1
SIG
2
1
!
Interconnection
Cable
!
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.
ELECTRICAL WIRING CONNECTION
5CEY28ER - 5SLY28CR
Outdoor Unit
Terminal Block
Indoor Unit
Terminal Block
SIG
!
N
L
SIG
N
L
Interconnection
Cable
!
N
L
Model
Indoor
5CEY15E/ER
5CEY20/25E/ER
5CEY28ER
Outdoor
5SLY15D/DR
5SLY20/25C/CR
5SLY28CR
Voltage range**
Indoor
220V – 240V/1Ph/50Hz +
!
Outdoor
220V – 240V/1Ph/50Hz +
!
Power supply cable size*
mm
2
Number of conductors
1.5
3
2.5
3
2.5
3
Interconnection cable size*
mm
2
Number of conductors
1.5
4
2.5
4
1.5
4
Recommended time delay fuse*
A
15
20
25
!
Power Supply Cable
!
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.
1 EN 5CEY-0709(1).indd 13
1 EN 5CEY-0709(1).indd 13
4/20/11 4:37:10 PM
4/20/11 4:37:10 PM