1-5
English
Fig B
10.0mm (0.39")
10.0mm (0.39") Lower
Please ensure that the following steps are taken:
•
Check the gradient for drainage flow as recommended in Figure B.
•
Provide clearance for easy servicing and optimal air flow as shown in Figure C.
•
The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm return air.
•
Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be suitable for piping
and drainage installation. The unit must be a large distance away from the door.
Fig C
Ceiling Type
Floor Standing Type
Min. 10.0mm (0.39")
Max. 250mm (9.84")
Min. 500mm (19.60")
Utensils, Furnitures Or Built-
In Architectural Features
Must Not Protrude More
Than 250.0mm
Min. 1.0m (39.37")
Min. 400.0mm (15.75")
Min. 300.0mm (11.81")
1 IM-CEE-1108(0)-EN AS
5/26/09, 3:14 PM
5
Содержание 5CE 35E
Страница 2: ......
Страница 84: ...6 2 PE PE EH E CTOPO HO OFF H MAH E 1 1...
Страница 85: ...6 3 R410A 1 1975 1 1 2 1 2 1 2 2 3 4 5 6 2...
Страница 87: ...6 5 B 10 0 0 39 10 0 0 39 C 10 0 0 39 250 9 84 500 19 60 250 0 1 0 39 37 400 0 15 75 300 0 11 81...
Страница 88: ...6 6 10 300 300 621 10 10 1 2 3 D E 1 2 3...
Страница 89: ...6 7 1 F 2 G F G 3 H...
Страница 90: ...6 8 I 1 2 3 M4 K J...
Страница 95: ...6 13 C 3 30 76 0 76 II 500 0 76 3 2 4 3 o...
Страница 97: ...6 15 C 46 43 19 14 19 23 C D C B A E C 18 15 C J I G F 10 9 20 27 H 1 40 2 3 1 40 2 2 2...
Страница 98: ...6 16 1 1 E1 2 2 E2 3 3 E3 4 1 E4 5 3 E5 6 2 E6 7 SLM3 8 5 EC AP E7 MS 9 6 E8 3 4 1 3 2 3 4 5 6 7...
Страница 115: ......
Страница 118: ......
Страница 135: ......
Страница 136: ...nI uAJ VO d VO qBHM u u UHOJ W uAJ q u K WK U nI VO d IM CEE 1108 ACSON e r R08019032648...