38
Operating Limits
Air Limits °C
C
Cooling
Heating
Min. Ambient Air, DB/WB
16/-
16/-
Normal Ambient Air, DB/WB
27/19
20/15
Max. Ambient Air, DB/WB
35/-
30/-
Water Limits °C
C
Cooling
Heating
Min. Entering Water
13
10
Normal Entering Water
30
20
Max. Entering Water
40
35
NOTES:
AT STANDARD FLOW RATE.
Environment
This equipment is designed for indoor installation only. Sheltered locations such as attics, garages, etc., generally
should provide sufficient protection against extremes in temperature or humidity, or equipment performance, reliability
and service life span may be affected.
Power Supply
A voltage variation of ±10% of nameplate utilization voltage is acceptable.
Airflow Correction Factors
Rated Airflow Rate Percent
85%
90%
95%
100%
105%
110%
115%
Total Cooling Capacity
0.972
0.982
0.994
1.00
1.007
1.010
1.013
Sensible Heat Capacity
0.926
0.948
0.974
1.00
1.027
1.055
1.066
Latent Heat Capacity
0.975
0.983
0.991
1.00
1.008
1.015
1.018
Cooling Power Input
0.977
0.984
0.993
1.00
1.011
1.018
1.028
Total Heating Capacity
0.967
0.978
0.990
1.00
1.009
1.017
1.024
Heating Power Input
1.009
1.006
1.003
1.00
0.997
0.995
0.993
Содержание AWH028C
Страница 33: ...43 1 20 MODEL AWH028 030C Wiring Diagrams...
Страница 34: ...44 MODEL AWH028 030CR 20...
Страница 35: ...45 MODEL AWH040C 1 20...
Страница 36: ...46 MODEL AWH040CR 20...
Страница 37: ...47 MODEL AWH050 060 065 070C 20...
Страница 38: ...48 MODEL AWH050 060 065 070CR 20...
Страница 39: ...49 MODEL AWH080 100 125 150C 20...
Страница 40: ...50 MODEL AWH080 100 125 150CR 20...
Страница 41: ...51 MODEL AWH180 200 250 300C 02...
Страница 42: ...52 MODEL AWH180 200 250 300CR 02...
Страница 43: ...53 MODEL AWH350C COOLING ONLY AUXILIARY HEATER COOLING ONLY...
Страница 44: ...54 MODEL AWH350CR HEAT PUMP AUXILIARY HEATER...