35

A5HDC-2009

Troubleshooting

Troubleshooting

Error Code

Heatpump Model (Universal Board)

Operation / Faulty Indication

Room sensor contact loose / short

Indoor coil sensor contact loose

Outdoor coil sensor contact loose

Compressor overload / Indoor coil sensor short / 

Outdoor coil sensor short

Gas leak

N/A

Outdoor defrost (for Heatpump ony)

Error Code at 7 Segment Display

Blink E1

Blink E2

Blink E3
Blink E4
Blink E5

Blink E6

Blink Heat LED 

Fault Condition

1. Fan does not work 3 minutes after

  starting

  Protection against the frequent starting. Wait 3 or 4 minutes.

2. The air conditioning unit does not

  work

  Power failure or need to replace the fuse.

  The power plug is disconnected.

  Possibility of making a programming error in the controller.

  If the fault persist after these verifications, contact your installer.

  The air filter is dirty.

  The doors or windows are open.

  The air entrance and exit are clogged.

  The regulate temperature is not high enough.

4. The remote control light is deficient

  The batteries are discharge.

  The batteries are not correctly inserted.

  The assembly is not good.

5. Air discharge flow has a bad odor

  This odor can be caused by cigarette smoke particles, perfume,

sweat, which stick to the coil.

  Check if there is any moisture on the walls, garment, other.

  Check the drain pan.

6. Condensation on the air grille of

  indoor unit

  This is due to air humidity after a long time of operation.

  The unit has a lower temperature point, increase the point and

operate at high speed.

7. The water flow of air conditioning

  unit

  Check the condensate evacuation.

8. The air conditioning unit are noisy

  “Air flow noise” : refrigerant fluid admission in evaporator.

When any air-conditioner malfunction is noted, immediately switch off the power supply to 

the unit, and contact the local dealer, if necessary. Some simple troubleshooting tips are 

given below :

Fault

Cause

3. The air conditioning unit does not 

  blow sufficiently

Содержание A5HDC20AR

Страница 1: ...Horizontal Ducted Condensing Unit A5HDC 2009 Models A5HDC20AR A5HDC25AR...

Страница 2: ...t Diagram 8 Controller 9 Installation Guideline 11 Sound Data 18 Sound Pressure Level 18 NC Curve 19 Engineering Physical Data 20 General Data 20 Component Data 21 Safety Devices 22 Performance Data 2...

Страница 3: ...ure Indoor Nomenclature A 5 CC 20 C R Brand A Acson Model Name Capacity Index Model Type Refrigerant Omitted if R22 4 R407C 5 R410A CC Ceiling Concealed 20 20 000 Btu h Chassis C C series Omitted if c...

Страница 4: ...nclature A 5 HDC 20 A R Brand A Acson Model Name Capacity Index Model Type Refrigerant Omitted if R22 4 R407C 5 R410A HDC Horizontal Ducted Condensing Unit 20 20 000 Btu h Chassis A A series Omitted i...

Страница 5: ...door Unit A5CC CR Nomenclature L2 SLM 3 Bare Air Filter CE EPS Drain Pan 20CR AFBA X X X X X X 25CR AFAA X X X X X X Handset Heat Pump Classification Refrigerant Control Marking Air Purification Fin O...

Страница 6: ...ct Line Up Outdoor Unit A5HDC AR Cap Tube Hydrophilic Coated Rotary CE 20AR AFBA X X X X 25AR AFAA X X X X Heat Pump Compressor Others Classification A5HDC AR Nomenclature Refrigerant Control Fin Mark...

Страница 7: ...allation cost improved reliability efficiency compared to roof mounted units Flexibility in Installation The supply and return grille can be selected based on end user or professional interior designe...

Страница 8: ...Heatpump Application Information Heating Cooling Outdoor temp CDB Indoor temp CWB 19 35 15 46 24 STD Outdoor temp CWB Indoor temp CDB 9 15 21 6 27 18 STD Caution The use of your air conditioner outsid...

Страница 9: ...8 A5HDC 2009 Application Information Refrigerant Circuit Diagram Model A5CC20CR A5HDC20AR A5CC25CR A5HDC25AR 70034 095378...

Страница 10: ...eed selection Press the button until the desired fan speed is achieved 5 Timer Press the set button to select the switch timer of the air conditioner unit the setting range is between 1 to 10 hours 6...

Страница 11: ...r damage to the compressor Ensure that the unit s panel is closed after service or installation Unsecured panels will cause the unit to operate noisily Sharp edges and coil surfaces are potential loca...

Страница 12: ...Precaution steps as below i Use the hanging bracket supplied with the unit ii Ensure the support is strong enough to withstand the weight of the unit iii Incline the drain pipe as per diagram B Do not...

Страница 13: ...e to insulation failures All wiring must be firmly connected All wiring must not touch the hot refrigerant piping compressor or any moving parts of fan motors Refrigerant Piping Maximum Pipe Length An...

Страница 14: ...5 88 5 8 65 Vacuuming and Charging The precharged outdoor unit does not need any vacuuming or charging However once it is connected theconnecting pipe line and the indoor need to be vacuumed before re...

Страница 15: ...the outdoor unit For the piping length of 5m Additional refrigerant charge after vacuuming is not necessary When the piping length is more than 5m please use the table below unit in gram Model 7m 10m...

Страница 16: ...ere any abnormal vibrations with regard to unit itself or piping d Is there smooth drainage of water Check that 1 Outdoor blower is running with warm air blowing off the discharge grille cooling cycle...

Страница 17: ...l differ depending on whether it is in gaseous or liquid phase Hence when charging R410A ensure that only liquid is being withdrawn from the cylinder or can This is to make certain that only original...

Страница 18: ...and trouble free system operation a During installation or servicing avoid prolong exposure of the internal part of the refrigerant system to moist air Residual POE oil in the piping and components ca...

Страница 19: ...Medium 41 40 36 33 29 28 22 39 32 3 0 Low 36 35 33 31 26 27 21 36 30 A5CC25CR Noise Criteria Overall A dBA 1 1 Octave A Weighted Sound Pressure dBA ref 20 Pa Model Speed A5CC20CR Microphone position 1...

Страница 20: ...60 70 125 250 500 1000 2000 4000 8000 Octave band frequency Hz NC 40 NC 35 NC 30 NC 25 NC 45 NC 50 High fan Low fan Medium fan Sound pressure level dB ref 20 Pa 0 10 20 30 40 50 60 70 125 250 500 100...

Страница 21: ...T DIMENSION HEIGHT 618 24 3 703 27 7 DEPTH WIDTH 1347 53 0 UNIT WEIGHT 22 49 PACKING DIMENSION HEIGHT 1251 49 3 DEPTH 541 21 3 CONDENSATE DRAIN SIZE 19 1 3 4 376 14 8 WIDTH 64 58 34 0 3 0 2 0 1 SOUND...

Страница 22: ...T A5CC20CR OUTDOOR UNIT A5HDC20AR INDOOR FAN TYPE CENTRIFUGAL QUANTITY 2 MATERIAL GALVANIZED STEEL DRIVE DIRECT DIAMETER 160 6 30 LENGTH 202 7 95 INDOOR FAN MOTOR TYPE INDUCTION QUANTITY 1 INDEX OF PR...

Страница 23: ...THERMOSTAT SETTING C F 1 ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE N A N A SAFETY DEVICE HIGH PRESSURE SWITCH TYPE N A N A LOW PRESSURE SWITCH TYPE N A N A PH...

Страница 24: ...ity TC and sensible capacity SC at those temperatures which are not stated out in the table Example Model A5CC20CR A5HDC20AR Indoor Condition 23 C DB 15 C WB Outdoor Condition 37 C DB Solution Overall...

Страница 25: ...r DB C Indoor WB C Outdoor DB C 40 TC kW SC kW 24 15 x2 y2 16 3 066 17 3 137 2 056 1 954 Total capacity TC x2 2 995kW Same as Total capacity at 20 C Indoor DB 15 C Indoor WB 40 C Outdoor WB Sensible c...

Страница 26: ...ndition 40 C DB Indoor DB C Indoor WB C Outdoor DB C 40 TC kW 20 15 2 995 23 15 x4 y4 24 15 2 995 1 195 2 158 Total capacity TC x4 2 995kW Same as Total capacity at 20 C Indoor DB 15 C Indoor WB 40 C...

Страница 27: ...tdoor Condition 37 C DB Indoor DB C Indoor WB C Outdoor DB C 35 37 40 TC kW SC kW TC kW TC kW SC kW SC kW 23 15 3 295 2 233 x y 2 995 1 917 Total capacity TC Interpolation Method 40 C 35 C 2 995kW 3 2...

Страница 28: ...227 5 720 2 942 5 305 2 599 24 7 188 3 746 6 845 3 424 6 503 3 102 6 161 2 780 5 819 2 458 5 408 2 072 20 6 843 5 699 6 488 5 522 6 133 5 345 5 778 5 169 5 423 4 992 4 997 4 780 21 6 929 5 361 6 577...

Страница 29: ...62 7 542 3 749 7 071 3 335 6 600 2 921 6 035 2 425 24 8 741 4 299 8 243 3 846 7 745 3 393 7 247 2 940 6 749 2 488 6 151 1 944 20 7 716 6 066 7 325 5 769 6 934 5 473 6 543 5 177 6 153 4 880 5 684 4 525...

Страница 30: ...009 Outline and Dimension Outline and Dimension Indoor Unit Model A5CC20 25CR A B C D E F G H A5CC20CR 1041 225 1002 962 261 411 351 1065 A5CC25CR 1176 225 1137 1097 261 411 351 1200 Note Dimension in...

Страница 31: ...30 A5HDC 2009 Outline and Dimension Outdoor Unit Model A5HDC20 25AR Note Dimension in mm...

Страница 32: ...CAPACITOR F RATED INPUT POWER COOLING W RATED INPUT POWER HEATING W RATED RUNNING CURRENT COOLING A RATED RUNNING CURRENT HEATING A LOCKED ROTOR AMP A MODEL INDOOR UNIT A5CC20CR OUTDOOR UNIT A5HDC20A...

Страница 33: ...32 A5HDC 2009 Wiring Diagram Wiring Diagram Heat Pump Indoor Unit Outdoor Unit Model A5CC20CR Model A5HDC20AR A5CC25CR A5HDC25AR 70034 095382...

Страница 34: ...filter well and dry before placing it back on to the unit 3 Do not use gasoline volatile substances or chemicals to clean the filter 1 Clean any dirt or dust on the grille or panel by wiping it with...

Страница 35: ...ten all wiring connections and panels Check for refrigerant leakage Most of the parts are accessible by removal of bottom side panel Caution Do not charge OXYGEN ACETYLENE OR OTHER FLAMMABLE and poiso...

Страница 36: ...are open The air entrance and exit are clogged The regulate temperature is not high enough 4 The remote control light is deficient The batteries are discharge The batteries are not correctly inserted...

Страница 37: ...defective 2 Reversing valve leaking 1 Undercharged with refrigerant 2 Refrigerant leakage 3 Air filter clogged dirty indoor unit 4 Indoor fan locked seized 5 Defective defrost control outdoor coil fr...

Страница 38: ...actor Change The Contactor Get The Right Voltage Get The Right Voltage Get The Right Voltage Tighten The Connections Repair or Replace The Components Repait The Power Line Repair Or Replace The Switch...

Страница 39: ...ections See High Discharge Pressure or High Suction Pressure Tighten The Connections See High Discharge Pressure or Low Suction Pressure Add Refrigerant Repair Leakage If Detected See High Discharge P...

Страница 40: ...y Strainer Whistling High Suction Pressure Low Suction Pressure Noisy Operation High Suction Pressure Excessive Fresh Air Intake Evaporator Air Inlet Temperature Insufficient Duct Insulation Defective...

Страница 41: ...50039005356 2 Fan Deck B Assy Wheel Housing Right R50039005355 A5CC20CR R50014035082 C Fan Motor A5CC25CR R50014032629 A5CC20C R03039004898 3 Assy Coil A5CC25CR R03039004899 A5CC20CR R50024079268 D Ai...

Страница 42: ...cription No Description 1 Assy Front Panel 12 Assy 4 Way Valve 2 Assy Drain Pan 13 Tube Comp Suct To Acc Out 3 Assy Base Panel 14 Blower 4 Assy Coil 15 Fan Motor 5 Compressor Jacket 16 Bracket Fan Mot...

Страница 43: ...cription No Description 1 Assy Front Panel 12 Assy 4 Way Valve 2 Assy Drain Pan 13 Tube Comp Suct To Acc Out 3 Assy Base Panel 14 Blower 4 Assy Coil 15 Fan Motor 5 Compressor Jacket 16 Bracket Fan Mot...

Страница 44: ...press we are constantly striving for improvement and therefore reserve the rights to alter model specifications and equipment without prior notice Details of specifications and equipment are also sub...

Отзывы: