8. APPENDIX
37
General
Unit
Default
Min
Max
Resolution
Model
Flag
4
0
2
1
0=Chiller
(Boiler)
1=Heat pump,
2=Chiller/ Boiler,
3=Heat pump/ Boiler, 4=Boiler
5=Heat pump+Boiller
Number of compressor
Flag
1
1
4
1
1=1 compressor,
2=2 compressor,
3=3 compressor,
4=4 compressor
On/Off input
Flag
0 (disable)
0
1
1
0=disable, 1=enable
Coo/ Heat input
Flag
0 (disable)
0
1
1
0=disable, 1=enable
External alarm input
Flag
0 (disable)
0
1
1
0=disable, 1=enable
Water system for chiller network
Flag
0 (disable)
0
1
1
0=independent, 1=modular
G7
Unit number
Flag
0
0
50
1
G5
G6
G1
G2
G3
G4
REGULATOR
Unit
Default
Min
Max
Resolution
R1
Cooling set-point
°C (F)
12 (53.6)
7(44.6)
20(68)
0.1
R2
Cooling differential
°C (F)
1.5* (2.7)
0.4 (0.7)
10 (18)
0.1
R3
Heating set-point
°C (F)
40 (104)
30(86)
50(122)
0.1
R4
Heating differential
°C (F)
1.5* (2.7)
0.4 (0.7)
10 (18)
0.1
R5
Minimum Cooling set-point
°C (F)
7 (44.6)
-20 (-4)
20(68)
1
R6
Maximum Cooling set-point
°C (F)
20 (68)
7(44.6)
40 (104)
1
R7
Minimum Heating set-point
°C (F)
30 (86)
-20 (-4)
50(122)
1
R8
Maximum Heating set-point
°C (F)
50 (122)
30(86)
90 (194)
1
R9
Auxiliary heater set-point(threshold below
°C (F)
5 (9)
0 (0)
40 (72)
0.1
below heating set-point)
R10
Auxiliary heater differential
°C (F)
2 (3.6)
0.4 (0.7)
10 (18)
0.1
R11
Auto boiler set-point(threshold below
°C (F)
5 (9)
0 (0)
40 (72)
0.1
Heating set-point)
R12
Auto boiler differential
°C (F)
2 (3.6)
0.4 (0.7)
10 (18)
0.1
R13
Auto boiler start time threshold
min
30
0
199
1
COMPRESSOR
Unit
Default
Min
Max
Resolution
C1
Compressor minimum run time
sec
120
0
1990
10
C2
Compressor minimum stop time
sec
180
0
1990
10
C3
Time interval between two starts
sec
450
0
1990
10
C4
Start delay between two compressors
sec
15
0
199
1
C5
Pump on
ĺ
compressor on delay
sec
180
0
1990
10
C6
Comp off
ĺ
pump off delay
sec
60
0
199
10
C7
Discharge cut-off-set-point
°C (F)
120(248)
0 (32)
150 (302)
1
CONDENSER DEFROST
Unit
Default
Min
Max
Resolution
D1
Start defrost temperature
°C (F)
0 (32)
-20 (-4)
14(57)
1
D2
End defrost temperature
°C (F)
14 (57)
0(32)
40 (104)
1
D3
Maximum duration of defrost cycle
min
10
1
40
1
D4
Defrost interval time
min
45
0
199
1
D5
Delay before defrosting
sec
0
0
1990
10
D6
Delay after defrosting
sec
120
0
1990
10
Содержание A5ACV 100 CR
Страница 43: ...INSTALLATION A5ACV 30 55 75CR 41 ...
Страница 44: ...A5ACV 30CR A5ACV 55CR 75CR 42 ...
Страница 78: ...10 WIRING DIAGRAMS PA R T NO 50 13 9 026086 MODEL A5ACV 30CR 76 ...
Страница 79: ...77 MODEL A5ACV 55CR ...
Страница 80: ...MODEL A5ACV 75CR PA R T NO 50 13 4 083602 78 ...
Страница 81: ...MODEL A5ACV 100 135CR 79 ...