6.2.7 Advance Parameter Settings
The Chiller Panel provide user a lot of advance parameter settings for the Chiller. The parameters are
divided into 7 groups. There all are stored in
[Set Parameter]
menu and it is password-protected layer
in the panel.
*
CAUTION : INPROPER SETTINGS WILL CAUSE PERMANENT DAMAGE TO THE CHILLER !!!
7 groups of Advance Parameter:
1) General
2) Regulator
27
<ENTER>
<ENTER>
Summary Pages
Main Menu
Settings Menu
<ESC>
<ESC>
<ENTER> <ESC>
Key in Password
Set Parameter
R1 Cool SP
: 12.0°C
R2 Cool Diff
: 3.0°C
R3 Heat SP
: 40.0°C
R4 Heat Diff
: 3.0°C
R5 Min Cool SP : -20°C
R6 Max Cool SP : 40°C
R7 Min Heat SP : -20°C
R8 Max Heat SP : 90°C
R9 Ax Heat SP : 5.0°C
R10 Ax Heat Diff : 2.0°C
R11 Au Bo SP : 5.0°C
R12 Au Bo Diff : 2.0°C
R13 Au Bo Start : 30m
G1 Mode
: Chiller
G2 No. Comp
: 1 Comp
G3 On/Off in
: Disable
G4 Cool/Heat in : Disable
G5 Ext Alarm in : Disable
G6 Water sys
: Isolated
G7 Unit No
: 0