WTAU –100 / 120 / 200 / 220
page 7 of 8
Channel 2
Trimmer for zero and
end value adjustment
only at version
WTAU – 200
Function indicator
1 LED for indication of
ready status
Channel 1
Trimmer for zero and
end value adjustment
only at version
WTAU – 100 / 200
Configuration switch
inside the housing
only at versions
WTAU – 100 / 200
Operation and display elements
Function indicator
ON
green LED
ready status, power supply voltage on
Trimmer
For adjustment of zero and end value per channel. Only available at versions WTAU – 100 / 200.
At the Pt100 – isolation amplifier WTAU – 200 – U0 both output signals (output 1 and output 2) are changed uniform by the
configuration switches and by the trimmer channel 1.
The output 2 can be additionally separately changed in the zero value by
3% and in the end value by
6% by the further
trimmer at the front side (channel 2).
For an accurate results the adjustment zero value – end value must be proceeded repeatedly with connected signal,
because zero and end value adjustment effects each other.
Configuration switches
The configuration of the input and output signal ranges is made per dip switches inside the housing.
Dangerous voltage
Ensure a safe switching off the supply voltage when opening the housing
For configuration release the upper housing part at top and bottom side behind the terminals by using a screwdriver and pull
it out of the housing. Drop-in pin's avoid a complete pulling out. Following the respective dip switches can be set according to
the desired functions to ON or OFF.
The switch S3 of switcher block S3 must be set to position ON. The position of all other not described switches are without
importance.
Input signal range zero value switcher block SB1
Switch 2 (SB1)
zero value
switch
switching state ON
switching state OFF
2
zero value 0°C
zero value –50°C
Input signal range measuring range switcher block SB2
Switch 1, 2, 3, 4, 5, 6 (SB2)
measuring range
S1
S2
S3
S4
S5
S6
measuring range
OFF
OFF
OFF
OFF
OFF
ON
50 Kelvin
OFF
OFF
OFF
OFF
ON
OFF
100 Kelvin
OFF
OFF
OFF
ON
OFF
OFF
150 Kelvin
OFF
OFF
ON
OFF
OFF
OFF
200 Kelvin
OFF
ON
OFF
OFF
OFF
OFF
300 Kelvin
ON
OFF
OFF
OFF
OFF
OFF
500 Kelvin
Output signal range channel 1 switcher block SB1
Switch 4 (SB1)
signal range
switch
switching state ON
switching state OFF
4
0...10V / 0...20mA
2...10V / 4...20mA
Output signal range channel 2 switcher block SB3
Switch 4 (SB3)
signal range
switch
switching state ON
switching state OFF
4
0...10V / 0...20mA
2...10V / 4...20mA