WTAU –100 / 120 / 200 / 220 

 

page 7 of 8 

 

Channel 2 

Trimmer for zero and 

end value adjustment 

only at version 

WTAU – 200 

Function indicator 

1 LED for indication of 

ready status 

Channel 1 

Trimmer for zero and 

end value adjustment 

only at version 

WTAU – 100 / 200 

Configuration switch 

inside the housing 

only at versions 

WTAU – 100 / 200 

Operation and display elements

 

 

 

 

 

 

 

 

 

 

 

 

 

Function indicator 

 

  ON   

 green LED    

 ready status, power supply voltage on 

 

Trimmer 

 

For adjustment of zero and end value per channel. Only available at versions WTAU – 100 / 200. 

 

At the Pt100 – isolation amplifier WTAU – 200 – U0 both output signals (output 1 and output 2) are changed uniform by the 

configuration switches and by the trimmer channel 1. 

The output 2 can be additionally separately changed in the zero value by 

 3% and in the end value by 

 6% by the further 

trimmer at the front side (channel 2). 

 

For an accurate results the adjustment zero value – end value must be proceeded repeatedly with connected signal, 

because zero and end value adjustment effects each other. 

 

Configuration switches 

 

The configuration of the input and output signal ranges is made per dip switches inside the housing. 

 

 

Dangerous voltage 

 

Ensure a safe switching off the supply voltage when opening the housing 

 

For configuration release the upper housing part at top and bottom side behind the terminals by using a screwdriver and pull 

it out of the housing. Drop-in pin's avoid a complete pulling out. Following the respective dip switches can be set according to 

the desired functions to ON or OFF. 

 

The switch S3 of switcher block S3 must be set to position ON. The position of all other not described switches are without 

importance. 

 

Input signal range zero value    switcher block SB1 

 

Switch 2 (SB1)     

 zero value 

switch 

switching state ON 

switching state OFF 

zero value 0°C 

zero value –50°C 

 

Input signal range measuring range   switcher block SB2 

 

Switch 1, 2, 3, 4, 5, 6 (SB2)   

 measuring range 

S1 

S2

 

S3

 

S4

 

S5

 

S6

 

measuring range

 

OFF 

OFF 

OFF 

OFF 

OFF 

ON 

50 Kelvin 

OFF 

OFF 

OFF 

OFF 

ON 

OFF 

100 Kelvin 

OFF 

OFF 

OFF 

ON 

OFF 

OFF 

150 Kelvin 

OFF 

OFF 

ON 

OFF 

OFF 

OFF 

200 Kelvin 

OFF 

ON 

OFF 

OFF 

OFF 

OFF 

300 Kelvin 

ON 

OFF 

OFF 

OFF 

OFF 

OFF 

500 Kelvin 

 

 

Output signal range    channel 1  switcher block SB1 

 

Switch 4 (SB1)     

 signal range 

 

switch 

switching state ON 

switching state OFF 

0...10V / 0...20mA 

2...10V / 4...20mA 

 

 

Output signal range    channel 2  switcher block SB3 

 

Switch 4 (SB3)     

 signal range 

 

switch 

switching state ON 

switching state OFF 

0...10V / 0...20mA 

2...10V / 4...20mA 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

     

Содержание WTAU-100

Страница 1: ...ls Direct voltage 0 10V 2 10V simultaneous outputs Direct current 0 20mA 4 20mA simultaneous outputs Signal adjustment of zero value and amplification optional Single or double channel version optiona...

Страница 2: ...no A output 1 code no B 0 C 50 C A 0 10V 1 0 C 100 C B 0 20mA 2 0 C 150 C C 4 20mA 3 0 C 200 C E special range Y 0 C 250 C F 0 C 300 C G 0 C 400 C H 0 C 500 C J 0 C 600 C L output 2 code no C 40 C 60...

Страница 3: ...WTAU 200 U0 adjustable version The connected resistance proportional electrical Pt100 voltage signal is measured by the evaluation circuit linearized adjusted according to the front sided trimmer and...

Страница 4: ...eets the legal requirements of all relevant EC directives Installation notes The device is conceived for vertical installation on a standard fastening rail acc to DIN EN 60715 TH 35 7 5 resp TH 35 15...

Страница 5: ...dard installation cable or multi wire cable for measuring intends with a maximum of 25 per wire can be used Pt100 in 2 or 3 wire measurement can be connected At a 2 wire measurement the terminals 1 an...

Страница 6: ...stage there must be paid attention that mostly the signal circuit must be connected to earth by connection the minus terminal with measuring earth The signal cable should be installed separated from...

Страница 7: ...ide the housing Dangerous voltage Ensure a safe switching off the supply voltage when opening the housing For configuration release the upper housing part at top and bottom side behind the terminals b...

Страница 8: ...25 660K depends on setting configuration switch measuring range Adjustment range zero output 2 3 of respective nominal measuring range Adjustment range range output 2 6 of respective nominal measuring...

Отзывы: