Application 

 

The active isolation amplifier of the series 

WTAU

 is used to linearize Pt100 temperature signals, to convert it 

into one resp. two galvanic isolated electrical standard signals or to adjust the signals in the zero value and/or 

end value resp. amplification. 

 

A galvanic isolation is sometimes the only possibility at error generating ground loops, unwished signal 

overlapping and potential problems. 

Thus, a current flow between more signal current circuits that distort the signal is avoided. 

 

The free configurable resp. fix signal conversion, dependent on version, allows the flexible adaption of the Pt100 

temperature signal to different systems, e.g. to the standard signal input of a SPS control. 

 

The adjustable version is suitable, if sections, e.g. +10°C...+40°C of a standard temperature signal 0°C...+50°C 

should be amplified to a complete standard signal e.g. 4...20mA or for zero value adjustment e.g. because of 

temperature losses caused by heat transfer. 

 

At the versions WTAU – 200 – U0 / WTAU – 220 – U0 the Pt100 temperature signal is converted in parallel into 

two electrical standard signal. Thus the Pt100 temperature signal can be doubled, to use it in two separated 

evaluation circuits. 

 

 

 

Function 

 

Measuring principle 

 

Version WTAU – 100 – U0 / WTAU – 200 – U0 – adjustable version

 

The connected resistance proportional electrical Pt100 voltage signal is measured by the evaluation circuit, 

linearized, adjusted according to the front-sided trimmer and transmitted galvanically isolated to the 

simultaneous output signals 0...10V and 0...20mA or 2...10V and 4...20mA according to the settings of the 

internal configuration switches. 

 

The respective current resp. voltage signals at the output can be used simultaneous. Therefore there are 

simultaneous 2 output signals at the single channel versions WTAU – 100 – U0 and simultaneous 4 output 

signals at the double channel version WTAU – 200 – U0 are available. 

 

Examples: 

  WTAU – 100 – U0  Input signal 0°C..+100°C is converted to  

output signal  

0...10V / 0...20mA 

 

  WTAU – 100 – U0  Input signal 0°C..+50°C is converted to  

output signal  

2...10V / 4...20mA 

 

  WTAU – 200 – U0  Input signal 0°C..+50°C is converted to  

output signal 1  

0...10V / 0...20mA 

   

output signal 2  

2...10V / 4...20mA 

 

Version WTAU – 120 – U0 / WTAU – 220 – U0 – fix adjusted version

 

The connected resistance proportional electrical Pt100 voltage signal is measured by the evaluation circuit, 

linearized and transmitted galvanically isolated to the to the output signal 0...10V or 0...20mA or 4...20mA. 

At the version WTAU – 220 – U0 the Pt100 input signal is transmitted simultaneously to the both output 

channels. 

 

Examples: 

  WTAU – 120 – U0  Input signal 0°C..+100°C is converted to  

output signal  

0...10V 

 

  WTAU – 220 – U0  Input signal 0°C..+50°C is converted to  

output signal 1  

0...10V 

 

 

 

output signal 2 

0...20mA

 

 

 

Содержание WTAU-100

Страница 1: ...ls Direct voltage 0 10V 2 10V simultaneous outputs Direct current 0 20mA 4 20mA simultaneous outputs Signal adjustment of zero value and amplification optional Single or double channel version optiona...

Страница 2: ...no A output 1 code no B 0 C 50 C A 0 10V 1 0 C 100 C B 0 20mA 2 0 C 150 C C 4 20mA 3 0 C 200 C E special range Y 0 C 250 C F 0 C 300 C G 0 C 400 C H 0 C 500 C J 0 C 600 C L output 2 code no C 40 C 60...

Страница 3: ...WTAU 200 U0 adjustable version The connected resistance proportional electrical Pt100 voltage signal is measured by the evaluation circuit linearized adjusted according to the front sided trimmer and...

Страница 4: ...eets the legal requirements of all relevant EC directives Installation notes The device is conceived for vertical installation on a standard fastening rail acc to DIN EN 60715 TH 35 7 5 resp TH 35 15...

Страница 5: ...dard installation cable or multi wire cable for measuring intends with a maximum of 25 per wire can be used Pt100 in 2 or 3 wire measurement can be connected At a 2 wire measurement the terminals 1 an...

Страница 6: ...stage there must be paid attention that mostly the signal circuit must be connected to earth by connection the minus terminal with measuring earth The signal cable should be installed separated from...

Страница 7: ...ide the housing Dangerous voltage Ensure a safe switching off the supply voltage when opening the housing For configuration release the upper housing part at top and bottom side behind the terminals b...

Страница 8: ...25 660K depends on setting configuration switch measuring range Adjustment range zero output 2 3 of respective nominal measuring range Adjustment range range output 2 6 of respective nominal measuring...

Отзывы: