Technical data 

 

Auxiliary power supply

 

 

 

Permitted supply voltage: 

20 V to 253 V AC / DC  48...62  Hz, reverse polarity protected 

 

Power consumption: 

 3 VA / 1,5 W (TVA – 080 / 180) resp. 

 5 VA / 3 W (TVA –100 / 120) resp.  

 

 7 VA / 5 W (TVA – 200 / 220) 

 

Overvoltage category: 

II 

acc. to DIN EN 61010-1 

 

Protection classification: 

II  

double or reinforced insulation 

 

Isolation voltage: 

4kV~ 

auxiliary power to signal inputs to signal outputs 

 

Galvanic isolation: 

All supply, input and output channels among each other as well as both input and  

 

output channels from each other are safe galvanically isolated. 

 

 

Signal input (1x resp. 2x available, depends on version)

 

 

Direct voltage:              0…10 V / 0...1 V / -5...+5 V / -0,5...+0,5 V / max. 50V / input resistance 1,1M

 

 

Direct current:               0…20mA / 4…20mA / -10...+10mA / max. 400mA at 30V  

self-resetting fuse / input resistance 25

 + 0,2V 

 

PFM modulated current signal: 

90...520 Hz, overlapping current pulse 5mA

10%, T

Pulse

=110µs

20% 

 

Measurand transducer supply: 

overload and short circuit protected 

  TVA – 100 / 120 

3- wire-sensor:

 

 18,7V at 20mA 

 18,3V at 27,5mA  min. 27,5mA / max. 25V 

 

 

2- wire-sensor: 

 18,3V at 20mA 

 17,9V at 27,5mA  min. 27,5mA / max. 25V

 

  TVA – 200 / 220 

3- wire-sensor:

 

 17,6V at 20mA 

 17,5V at 22,5mA  min. 22,5mA / max. 25V 

 

 

2- wire-sensor: 

 17,3V at 20mA 

 17,1V at 22,5mA  min. 22,5mA / max. 25V

 

 

Signal output (1x resp. 2x available, depends on version)

 

 

Direct voltage:              0…10 V / 2...10 V, max. 17V, overload and short circuit protected 

 

Permitted load direct voltage:   

 

TVA – 080 / 100 / 120 / 180

   R

L

 

 1250

 at 10V / R

L

 

 2000

 at 10V (at simultaneous output I

out

 with 20mA) 

 

TVA – 200 / 220         

R

L

 

 3333

 at 10V / R

L

 

 6666

 at 10V (at simultaneous output I

out

 with 20mA) 

 

Direct current:               0…20mA / 4…20mA, max. 28mA 

 

Permitted load direct current:   

 

TVA – 080 / 100 / 120 / 180  

R

L

 

 880

 at 20mA / R

L

 

 680

 at 20mA (at simultaneous output U

out

 with 5mA) 

 

TVA – 200 / 220         

R

L

 

 570

 at 20mA / R

L

 

 530

 at 20mA (at simultaneous output U

out

 with 1,5mA) 

 

Adjustment range zero value:      –25...+5%     of respective nominal measuring range 

 

Adjustment range end value:      –5...+45%     of respective nominal measuring range

 

 

Transmission frequency:        

 500 Hz 

 

Limit value deviation:          

 0,2%       of factory calibrated measuring range (delivery setting) 

 

Range changing deviation:       

 2%        of respective nominal measuring range

 

 

Characteristic deviation:        

 0,05%      of respective nominal measuring range 

 

Temperature deviation:         

 0,05% / 10 K  of respective nominal measuring range 

 

Long term deviation: 

 

 

 

0,1%  

  of respective nominal measuring range / year   

 

Influence output load:   

 

 0,05% 

  of respective nominal measuring range

 

 

Materials 

 

Connection housing: 

PA – polyamide 

 

Terminal housing: 

PA – polyamide 

 

Sticker: 

PE – polyester 

 

Connection terminals 

 

Number: 

3 resp. 4 terminal blocks with each 4 terminals, everlasting screws 

 

Connection cross-section: 

maximum 1 x 2,5 mm or 2 x 1,5 mm 

 

Housing style 

 

Housing: 

Series installation housing, 22,5mm wide

 

 

Weight: 

100 g

 

 

Environmental conditions 

 

Environmental temperature: 

Single installation  – 40°C...+70°C    versions TVA – 080 / 100 / 120 / 180 

 

 

 

  – 40°C...+60°C    versions TVA – 200 / 220 

 

Series installation  – 40°C...+60°C    versions TVA – 080 / 100 / 120 / 180 

 

 

 

  – 40°C...+50°C    versions TVA – 200 / 220 

 

Climatic classification: 

3K3 resp. 3M2    DIN EN 60721-3-3

 

 

Protection classification: 

IP20 

 

  DIN EN 60529 

 

EM – compatibility: 

emission    

  DIN EN 61326-1 

operation device class B 

 

immunity   

  DIN EN 61326-1 

 industrial range 

 

Содержание TVA-080

Страница 1: ...ls Direct voltage 0 10V 2 10V simultaneous outputs Direct current 0 20mA 4 20mA simultaneous outputs Signal adjustment of zero value and amplification optional Single or double channel version optional Integrated measurand transducer supply optional Space saving safe isolation with 4kV Wide range power supply from 20 to 253V AC and DC L a u t e r b a c h s t r 5 7 8 4 3 0 7 E g g e n f e l d e n G...

Страница 2: ...Output code no B 0 10V 1 0 10V 1 0 20mA 2 0 20mA 2 4 20mA 3 4 20mA 3 90 520Hz PFM P special range Y special range Y TVA 200 U0 Version double channel device adjustable with measurand transducer supply TVA 220 ABCD U0 Version double channel device fix adjusted with measurand transducer supply Input 1 order no A Input 2 order no B Output 1 order no C Output 2 order no D 0 10V 1 0 10V 1 0 10V 1 0 10V...

Страница 3: ...rrent through the isolation Function Measuring principle Version TVA 080 U0 TVA 100 U0 TVA 200 U0 adjustable version The connected electrical standard signal 0 10V 0 1V 5 5V 0 5 0 5V 0 20mA 4 20mA 10 10mA is measured by the evaluation circuit adjusted according to the front sided trimmer and transmitted galvanically isolated to the simultaneous output signals 0 10V and 0 20mA or 2 10V and 4 20mA a...

Страница 4: ...evice meets the legal requirements of all relevant EC directives Installation The device is conceived for vertical installation on a standard fastening rail acc to DIN EN 60715 TH 35 7 5 resp TH 35 15 DIN EN 60715 TH 35 7 5 DIN EN 60715 TH 35 15 The device must be installed protected against dust and humidity e g in control stations or in a suitable protection housing with a minimum protection cla...

Страница 5: ... for measuring intends with a maximum of 25 per wire can be used The use of a shielded signal cable is recommended if strong electromagnetic influences could happens e g due to machines or radio equipment In that case the shielding of the cable should be connected to earth only at the side of signaling transmitter resp measuring transducer The signal cable should be installed separated from power ...

Страница 6: ...nput stage there must be paid attention that mostly the signal circuit must be connected to earth by connection the minus terminal with measuring earth The signal cable should be installed separated from power leading wires For inauguration it is suggested to deactivate all connected control devices to avoid unwanted control reactions Connection of the power supply voltage Due to the integrated wi...

Страница 7: ...ange channel 1 switcher block SB1 Switch 1 2 3 SB1 measuring range switching state S1 switching state S2 switching state S3 measuring range CH 1 OFF ON ON 0 5 0 5V 10 10mA ON OFF OFF 4 20mA OFF OFF ON 0 1V 0 20mA OFF ON OFF 5 5V 10 10mA OFF OFF OFF 0 10V 0 20mA Input signal range channel 2 switcher block SB3 Switch 1 2 3 SB3 measuring range switching state S1 switching state S2 switching state S3 ...

Страница 8: ...put Iout with 20mA TVA 200 220 RL 3333 at 10V RL 6666 at 10V at simultaneous output Iout with 20mA Direct current 0 20mA 4 20mA max 28mA Permitted load direct current TVA 080 100 120 180 RL 880 at 20mA RL 680 at 20mA at simultaneous output Uout with 5mA TVA 200 220 RL 570 at 20mA RL 530 at 20mA at simultaneous output Uout with 1 5mA Adjustment range zero value 25 5 of respective nominal measuring ...

Отзывы: