Application 

 

The active isolation amplifier of the series 

TVA

 is used, dependent on version, for galvanic isolation of electrical 

standard signals 0..10V / 0..1V / -5..+5V / -0,5..+0,5V / 0..20mA / 4..20mA / -10..+10mA or a pulse frequency 

modulated (PFM) current signal 90...520Hz or for convert it into another standard signal or to adjust the signals 

in the zero value and/or end value resp. amplification. 

 

A galvanic isolation is sometimes the only possibility at error generating ground loops, unwished signal 

overlapping and potential problems. 

Thus, a current flow between more signal current circuits that distort the signal is avoided. 

 

The free configurable resp. fix signal conversion, dependent on version, allows the flexible adaption of different 

systems among each other, e.g. for connection of a 2-wire-measurand transducer with a current signal 4...20mA 

to the input 0...10V of a SPS control. 

 

The adjustable version is suitable, if sections, e.g. 5...14mA of a standard signal 4...20mA at the input should 

amplified to a complete standard signal e.g. 4...20mA or e.g. for zero value adjustment of a fix adjusted 

measurand transducer e.g. because of a position dependent zero value shifting. 

 

At the versions TVA – 200 – U0 / TVA – 220 – U0 in one device there can be two electrical signals simultaneous 

transmitted separately or one electrical standard signal can be doubled into two separated electrical standard 

signals by parallel or series connection. 

 

The signal input for pulse frequency modulated (PFM) current signal 90...520 Hz in combination with 

corresponding measurand transducer resp. signaling transmitter is especially suited for long transmission links 

of several 1000 m. The special type of the signal makes in insensitive against the negative characteristics of 

cables, that occurs only at higher length, like e.g. resistance and inductivity as well as error current through the 

isolation.   

 

Function 

 

Measuring principle 

 

Version TVA – 080 – U0 / TVA – 100 – U0 / TVA – 200 – U0 – adjustable version

 

The connected electrical standard signal 0..10V / 0..1V / -5..+5V / -0,5..+0,5V / 0..20mA / 4..20mA / -10..+10mA 

is measured by the evaluation circuit, adjusted according to the front-sided trimmer and transmitted galvanically 

isolated to the simultaneous output signals 0...10V and 0...20mA or 2...10V and 4...20mA according to the 

settings of the internal configuration switches. 

 

The respective current resp. voltage signals at the output can be used simultaneous. Therefore there are 

simultaneous 2 output signals at the single channel versions TVA – 080 – U0 / TVA – 100 – U0 and 

simultaneous 4 output signals at the double channel version TVA – 200 – U0 are available. 

 

Examples: 

  TVA – 100 – U0  Input signal:  

0...10V is converted to output signal:  

0...10V / 0...20mA 

  TVA – 100 – U0  Input signal:  

5...18mA is converted to output signal:  

2...10V / 4...20mA 

  TVA – 200 – U0  Input signal 1:  

0...10V is converted to output signal 1:  

0...10V / 0...20mA and 

Input signal 2:  

4...18mA is converted to output signal 2:  

2...10V / 4...20mA 

 

Version TVA – 120 – U0 / TVA – 180 – U0 / TVA – 220 – U0 – fix adjusted version

 

The connected electrical standard signal 0..10V / 0..20mA / 4..20mA or the pulse frequency modulated (PFM) 

current signal 90...520Hz (not for the version TVA – 220 – U0) is transmitted by the evaluation circuit 

galvanically isolated to the output signal 0...10V or 0...20mA or 4...20mA. 

 

Examples: 

  TVA – 120 – U0  Input signal:  

0...10V is converted to output signal:  

0...10V 

  TVA – 120 – U0  Input signal:  

90...520Hz is converted to output signal: 

4...20mA 

  TVA – 220 – U0  Input signal 1:  

0...10V is converted to output signal 1:  

0...10V and 

 

 

Input signal 2:  

4...20mA is converted to output signal 2: 

0...20mA

 

 

Measurand transducer supply 

 

Version TVA – 100 – U0 / TVA – 120 – U0 / TVA – 200 – U0 / TVA – 220 – U0 

The integrated measurand transducer supply allows the direct connection and thus the supply of 2-wire and 3-

wire transmitter.  

At the versions TVA – 200 – U0 / TVA – 220 – U0 the measurand transducer supply is two times available, one 

for each channel separately. 

 

Version TVA – 080 – U0 / TVA – 180 – U0 

A measurand transducer supply is not available. 

Содержание TVA-080

Страница 1: ...ls Direct voltage 0 10V 2 10V simultaneous outputs Direct current 0 20mA 4 20mA simultaneous outputs Signal adjustment of zero value and amplification optional Single or double channel version optional Integrated measurand transducer supply optional Space saving safe isolation with 4kV Wide range power supply from 20 to 253V AC and DC L a u t e r b a c h s t r 5 7 8 4 3 0 7 E g g e n f e l d e n G...

Страница 2: ...Output code no B 0 10V 1 0 10V 1 0 20mA 2 0 20mA 2 4 20mA 3 4 20mA 3 90 520Hz PFM P special range Y special range Y TVA 200 U0 Version double channel device adjustable with measurand transducer supply TVA 220 ABCD U0 Version double channel device fix adjusted with measurand transducer supply Input 1 order no A Input 2 order no B Output 1 order no C Output 2 order no D 0 10V 1 0 10V 1 0 10V 1 0 10V...

Страница 3: ...rrent through the isolation Function Measuring principle Version TVA 080 U0 TVA 100 U0 TVA 200 U0 adjustable version The connected electrical standard signal 0 10V 0 1V 5 5V 0 5 0 5V 0 20mA 4 20mA 10 10mA is measured by the evaluation circuit adjusted according to the front sided trimmer and transmitted galvanically isolated to the simultaneous output signals 0 10V and 0 20mA or 2 10V and 4 20mA a...

Страница 4: ...evice meets the legal requirements of all relevant EC directives Installation The device is conceived for vertical installation on a standard fastening rail acc to DIN EN 60715 TH 35 7 5 resp TH 35 15 DIN EN 60715 TH 35 7 5 DIN EN 60715 TH 35 15 The device must be installed protected against dust and humidity e g in control stations or in a suitable protection housing with a minimum protection cla...

Страница 5: ... for measuring intends with a maximum of 25 per wire can be used The use of a shielded signal cable is recommended if strong electromagnetic influences could happens e g due to machines or radio equipment In that case the shielding of the cable should be connected to earth only at the side of signaling transmitter resp measuring transducer The signal cable should be installed separated from power ...

Страница 6: ...nput stage there must be paid attention that mostly the signal circuit must be connected to earth by connection the minus terminal with measuring earth The signal cable should be installed separated from power leading wires For inauguration it is suggested to deactivate all connected control devices to avoid unwanted control reactions Connection of the power supply voltage Due to the integrated wi...

Страница 7: ...ange channel 1 switcher block SB1 Switch 1 2 3 SB1 measuring range switching state S1 switching state S2 switching state S3 measuring range CH 1 OFF ON ON 0 5 0 5V 10 10mA ON OFF OFF 4 20mA OFF OFF ON 0 1V 0 20mA OFF ON OFF 5 5V 10 10mA OFF OFF OFF 0 10V 0 20mA Input signal range channel 2 switcher block SB3 Switch 1 2 3 SB3 measuring range switching state S1 switching state S2 switching state S3 ...

Страница 8: ...put Iout with 20mA TVA 200 220 RL 3333 at 10V RL 6666 at 10V at simultaneous output Iout with 20mA Direct current 0 20mA 4 20mA max 28mA Permitted load direct current TVA 080 100 120 180 RL 880 at 20mA RL 680 at 20mA at simultaneous output Uout with 5mA TVA 200 220 RL 570 at 20mA RL 530 at 20mA at simultaneous output Uout with 1 5mA Adjustment range zero value 25 5 of respective nominal measuring ...

Отзывы: