Marvair MGA3090-3180 Wall Mount AC I&O Manual 05/2023 Rev.14
1.9 Electrical Operation
The compressor and condenser fan are energized with a contactor controlled by a 24 VAC pilot signal.
Some compressors incorporate an internal PTC crankcase heater that functions as long as primary power
is available. The heater drives liquid refrigerant from the crankcase and prevents loss of lubrication
caused by oil dilution. Power must be applied to the unit for 24 hours before starting the compressor.
The condenser (outside fan) motor is energized by the same contactor.
The indoor evaporator fan motor is controlled by the fan purge on the electronic control board.