ACS GWA-250 Скачать руководство пользователя страница 8

 

 

GWA – 250

page 8 of 8

 

 

Technical data 

 

Auxiliary power supply

 

 

 

Permitted supply voltage: 

20 V to 253 V AC / DC  48...62  Hz, reverse polarity protected 

 

Power consumption: 

 2,5 VA / 1,75 W 

 

Overvoltage category: 

II 

acc. to DIN EN 61010-1 

 

Protection classification: 

II  

double or reinforced insulation 

 

Isolation voltage: 

4kV~ 

Auxiliary power to relay outputs to signal inputs 

 

Galvanic isolation: 

All supply, input and output channels among each other as well as both relay outputs 

 

from each other are safe galvanically isolated.  

 

Relay outputs

 

 

Function: 2x 

potential-free changeover contact 

 

Switching power of the contacts: 

 

U~  

maximum 253 V AC 

I~   

maximum 6 A AC (maximum switch-on current 10A) 

P~   

maximum 1500 VA at ohmic load / 300 VA at cos 

 0,7 

 

at U- 

maximum I- 

maximum P- 

30 V 

6 A 

180 W 

110 V 

0,3 A 

33 W 

220 V 

0,12 A 

26,4 W 

 

Minimum switching load:  

 50mW (0,5 V / 1 mA)

 

 

Switching cycles: 

 100.000 switching cycles at maximum contact load 

 

Delay time: 

 0,4s 

±

 0,1s resp. 

 4s 

±

 1s 

 

Switching hysteresis 

0,5% 

±

 0,2% / at two-position-control 

s: limit value A – limit value B 

 

Signal input GWA – 250

 

 

Direct voltage: 

 

 

 

 

 

 

0…10 V / maximum 50V / input resistance 100k

 

 

Direct 

current: 

       0…20mA 

4…20mA 

maximum 400mA at 30V – self resetting fuse 

           Input 

resistance 

50

 + 0,2V 

 

Measuring 

deviation: 

     

 0,4%    

of nominal measuring range 

 

Temperature 

deviation: 

    

 0,2% / 10 K of nominal measuring range 

 

Measurand transmitter supply: 

overload and short circuit protected 

 

 

3-wire-sensor:

 

 21,2V at 20mA 

 20,7V at 27,5mA  min. 27,5mA / max. 25V

2-wire-sensor: 

 20,0V at 20mA 

 19,0V at 27,5mA  min. 27,5mA / max. 25V

 

Signal input GWAP – 250

 

 

Temperature resistor Pt100:  

 

 

3-wire- / 2-wire-measuring, resistance linear, measuring current 2 x 0,515mA 

±

 10µA 

 

Measuring range:  

 

 

 

 

 

Zero value: –50°C, 0°C +50°C / range: 30 Kelvin, 50 Kelvin, 100 Kelvin, 600 Kelvin 

 

Measuring 

deviation: 

     

 0,4% (at zero value –50 / +50°C end value error 

 2%) of nominal meas. range 

 

Temperature 

deviation: 

    

 0,2% / 10 K of nominal measuring range 

 

Wire 

resistance: 

 

      

 40 

 per wire 

 

Error supervising: 

  

 

 

 

At wire break / short circuit of one or multiple Pt100 connection wires the output 

 

  

 

 

 

relays are switched off (at safety function minimum safety). At short circuit resp.  

 

  

 

 

 

wire link between terminals 1 and 2 the device operates in 2-wire-measuring

 

 

Materials 

 

Connection housing: 

PA – polyamide 

 

Terminal housing: 

PA – polyamide 

 

Sticker: 

PE – polyester 

 

Connection terminals 

 

Number: 

3 resp. 4 terminal blocks with each 4 terminals, everlasting screws 

 

Connection cross-section: 

maximum 1 x 2,5 mm or 2 x 1,5 mm 

 

Housing style 

 

Housing: 

Series installation housing, 22,5mm wide

 

 

Weight: 100 

g

 

 

Environmental conditions 

 

Environmental temperature: 

Single installation  – 40°C...+85°C 

 

Series installation  – 40°C...+70°C 

 

Climatic classification: 

3K3 resp. 3M2   

DIN EN 60721-3-3

 

 

Protection classification: 

IP20 

 

 

DIN EN 60529 

 

EM – compatibility: 

emission    

 

DIN EN 61326-1 

operation device class B 

 

immunity   

 

DIN EN 61326-1 

 industrial range 

Содержание GWA-250

Страница 1: ...n two separated limit values Two position control function a limit value with hysteresis Configurable switching delay Simple operation per key coding switch for adjusting the limit values from 0 99 of the signal range in steps of 1 Integrated measurand transducer supply Version with remote control available Wide range power supply from 20 to 253V AC and DC L a u t e r b a c h s t r 5 7 8 4 3 0 7 E...

Страница 2: ... display elements 7 Technical data 8 Order code GWA 250 U0 Version input signals 0 10V 0 20mA resp 4 20mA with on site control GWAS 250 U0 Version input signals 0 10V 0 20mA resp 4 20mA with remote control GWAP 250 U0 Version input signal Pt100 from 50 C 650 C with on site control GWAPS 250 U0 Version input signal Pt100 from 50 C 650 C with remote control ...

Страница 3: ...a signal current of 10mA At standard signal 4 20mA the setting 50 equals a signal current of 8mA 50 of 16mA 4mA 12mA The connected signal device at the input can be powered by the integrated measurand transducer supply Version GWAP 250 GWAPS 250 The voltage drop at the connected temperature sensor Pt100 is compared by the evaluation circuit with the set limit value at the key coding switches in of...

Страница 4: ...both output relays A and B the safety function can be set separately This can be carried out by two switches one per relay inside the device Two position control s The activation of the two position control is made by a switch inside the device Two position control with minimum safety Two position control with maximum safety The set limit value A equals the switching value and the limit value B eq...

Страница 5: ...installation on a standard fastening rail acc to DIN EN 60715 TH 35 7 5 resp TH35 15 DIN EN 60715 TH 35 7 5 DIN EN 60715 TH35 15 The device must be installed protected against dust and humidity e g in control stations or in a suitable protection housing with a minimum protection classification IP55 acc to DIN EN 60529 The devices must be installed wheather and stroke protected ideally at places wi...

Страница 6: ...f the inputs at the limit value switch GWA 250 current input maximum 400mA 30V voltage input 50V must not be transgressed The current input is equipped with a self resetting fuse At activation of the fuse the signal current wire must be disconnected for app 5 seconds If more than two limit values to a standard signal V mA should be evaluated at the limit value switch GWA 250 additional devices cou...

Страница 7: ...OFF ON channel B maximum safety switching state S5 switching state S6 safety function ON OFF channel A minimum safety OFF ON channel A maximum safety Switch 3 7 SB1 switching delay switch switching state ON switching state OFF 3 channel B 4 seconds channel B 0 4 seconds 7 channel A 4 seconds channel A 0 4 seconds Switch 4 SB1 operation function switch switching state ON switching state OFF 4 two p...

Страница 8: ...ng range Measurand transmitter supply overload and short circuit protected 3 wire sensor 21 2V at 20mA 20 7V at 27 5mA min 27 5mA max 25V 2 wire sensor 20 0V at 20mA 19 0V at 27 5mA min 27 5mA max 25V Signal input GWAP 250 Temperature resistor Pt100 3 wire 2 wire measuring resistance linear measuring current 2 x 0 515mA 10µA Measuring range Zero value 50 C 0 C 50 C range 30 Kelvin 50 Kelvin 100 Ke...

Отзывы: