Application 

 

The limit value switch 

GWA – 250 

is used for supervising electrical standard signals 0...10V / 0...20mA resp. 

4...20mA or temperature resistors Pt100 regarding transgression resp. underrun of limit values.  

 

The device allows it, additionally to continuous measurements, to set up to two switching limits without the need 
for additional measurement devices. 

 

The version GWA – 250 is suitable for supervision of supply and control voltages, e.g. in the water and waste 
water industry for filling level monitoring and pump control (e.g. 15% pump on, 95% pump off). 

 

The version GWAP – 250, for connection of a temperature resistor Pt100, can be used for supervision of 
process temperatures in all fields of industry. 

 

Alternatively to the on-site operation, where the key coding switches for setting the switching limit are integrated 
in the device, the version S is available, where the key coding switches can be installed separately from the 
device, using them as remote control. These are suitable for the installations into control cubicle doors resp. 
front panels. 
 
 
 
 

Function 

 

Measuring principle 

 

Version GWA – 250 / GWAS – 250 

The connected electrical standard signal 0...10V / 0...20mA resp. 4...20mA is compared by the evaluation circuit 
with the set limit value at the key coding switches in % of the nominal signal range (10V / 20mA / 16mA), with 
reference to the respective signal zero value (0V / 0mA bzw. 4mA). 
Examples: 

 

At standard signal 0...10V the setting 50% equals a signal voltage of 5V 

 

At standard signal 0...20mA the setting 50% equals a signal current of 10mA 

 

At standard signal 4...20mA the setting 50% equals a signal current of 8mA (50% of 16mA) + 4mA = 12mA 

The connected signal device at the input can be powered by the integrated measurand transducer supply. 

 

Version GWAP – 250 / GWAPS – 250 

The voltage drop at the connected temperature sensor Pt100 is compared by the evaluation circuit with the set 
limit value at the key coding switches in % of the set temperature signal range (30K / 50K / 100K / 600K), with 
reference to the set signal zero value (-50°C / 0°C / +50°C). 
Examples: 

 

At zero value –50°C and range 100K the setting 50% equals a temperature of –50°C + 50K = 0°C 

 

At zero value 0°C and range 600K the setting 50% equals a temperature of 0°C + 300K = 300°C 

 

At zero value +50°C and range 30K the setting 50% equals a temperature of +50°C + 15K = 65°C 

The connected Pt100 in 2-wire resp. 3-wire technology is supplied be an internal constant current source and is 
supervised for wire break or short circuit.  

 

Signal evaluation 

 

The transgression resp. underrun of the set limit value causes the switching of the relay resp. the relays 
depending on the configured safety function (minimum resp. maximum safety) resp. operation function (double 
limit value function resp. two-position-control function).  

 

The switching state of the relays is indicated at the front side of the device by two red LED’s. 

 

Switching delay 

 

In some applications it is necessary to compensate heavy signal fluctuations that may be produced by mixing 
machines or at fill-in resp. emptying of containers, to avoid spurious switching actions. 

 

Two switches inside the device allows the configuration of a switching delay of 0,4 s or 4 s, separately for each 
output relay, at activation and deactivation of the respective output relay. 
 

Содержание GWA-250

Страница 1: ...n two separated limit values Two position control function a limit value with hysteresis Configurable switching delay Simple operation per key coding switch for adjusting the limit values from 0 99 of the signal range in steps of 1 Integrated measurand transducer supply Version with remote control available Wide range power supply from 20 to 253V AC and DC L a u t e r b a c h s t r 5 7 8 4 3 0 7 E...

Страница 2: ... display elements 7 Technical data 8 Order code GWA 250 U0 Version input signals 0 10V 0 20mA resp 4 20mA with on site control GWAS 250 U0 Version input signals 0 10V 0 20mA resp 4 20mA with remote control GWAP 250 U0 Version input signal Pt100 from 50 C 650 C with on site control GWAPS 250 U0 Version input signal Pt100 from 50 C 650 C with remote control ...

Страница 3: ...a signal current of 10mA At standard signal 4 20mA the setting 50 equals a signal current of 8mA 50 of 16mA 4mA 12mA The connected signal device at the input can be powered by the integrated measurand transducer supply Version GWAP 250 GWAPS 250 The voltage drop at the connected temperature sensor Pt100 is compared by the evaluation circuit with the set limit value at the key coding switches in of...

Страница 4: ...both output relays A and B the safety function can be set separately This can be carried out by two switches one per relay inside the device Two position control s The activation of the two position control is made by a switch inside the device Two position control with minimum safety Two position control with maximum safety The set limit value A equals the switching value and the limit value B eq...

Страница 5: ...installation on a standard fastening rail acc to DIN EN 60715 TH 35 7 5 resp TH35 15 DIN EN 60715 TH 35 7 5 DIN EN 60715 TH35 15 The device must be installed protected against dust and humidity e g in control stations or in a suitable protection housing with a minimum protection classification IP55 acc to DIN EN 60529 The devices must be installed wheather and stroke protected ideally at places wi...

Страница 6: ...f the inputs at the limit value switch GWA 250 current input maximum 400mA 30V voltage input 50V must not be transgressed The current input is equipped with a self resetting fuse At activation of the fuse the signal current wire must be disconnected for app 5 seconds If more than two limit values to a standard signal V mA should be evaluated at the limit value switch GWA 250 additional devices cou...

Страница 7: ...OFF ON channel B maximum safety switching state S5 switching state S6 safety function ON OFF channel A minimum safety OFF ON channel A maximum safety Switch 3 7 SB1 switching delay switch switching state ON switching state OFF 3 channel B 4 seconds channel B 0 4 seconds 7 channel A 4 seconds channel A 0 4 seconds Switch 4 SB1 operation function switch switching state ON switching state OFF 4 two p...

Страница 8: ...ng range Measurand transmitter supply overload and short circuit protected 3 wire sensor 21 2V at 20mA 20 7V at 27 5mA min 27 5mA max 25V 2 wire sensor 20 0V at 20mA 19 0V at 27 5mA min 27 5mA max 25V Signal input GWAP 250 Temperature resistor Pt100 3 wire 2 wire measuring resistance linear measuring current 2 x 0 515mA 10µA Measuring range Zero value 50 C 0 C 50 C range 30 Kelvin 50 Kelvin 100 Ke...

Отзывы: