3  Installation

The correct function of the device within the specific technical data can only be guaranteed, if 

the permitted process and environmental temperatures (see chapter „Technical data“) will not be 

exceeded.

3.1 Installation place

The installation of the device at locations where high pressure blows can occur should be avoided.
At a pressure measurement in gases, the device should be installed above the tapping point, so that 

the condensate can flow into the process.
At a pressure measurement in steams, the device should be installed after a siphon and a shut-off 

device below the tapping point. 

The siphon reduces the temperature to almost ambient temperature. 

Fill the siphon with fluid before commissioning.
At a pressure measurement in liquids, the device should be installed after a shut-off device below or 

at the same level as the tapping point.

At a filling level measurement in liquids, the device should be installed below the lowest measuring 

point. Do not mount the device in the fill flow, in the suction area of a pump, in the tank outlet or at 

a point in the container which could be affected by pressure pulses from an agitator. Calibration and 

functional test can be carried out more easily if you mount the device after a shut-off device.
The installation position can have an influence on the measuring result of the kind of a zero value shift 

because of the deadweight of the measuring diaphragm. The correction of this deviation at the device 

is not possible.

3.2 Process and environmental temperature

The installation of the device should be made if possible at temperature calmed places to get a reliable 

measuring result. 

Strong temperature steps, e.g. at filling of a hot liquid into a cold system, can produce a short-time 

higher measuring signal deviation.
At high process temperatures a heat transfer to the terminal enclosure can be reduced by isolation of 

the medium carrying part of the plant.

At underrun of the dew point, e.g. cold process medium at high environmental temperature, there 

is the possibility of condensate formation within the pressure measuring sensor, which can lead to 

increased measurement deviations resp. malfunctions.

These deviations are fully reversible by drying the condensate.

The use of a device with a strain gauge pressure measuring sensor is recommended.

3.3 Installation notes

Drive the system pressure free prior installation resp. deinstallation of the sensor.

The protective cap, which is attached at the diaphragm, must only be removed immediately before the 

installation.

The diaphragm must not be point loaded, because this can lead to diaphragm damage.
The installation of the device into a closed off completely with process liquid filled connection can lead 

to destruction of the measuring diaphragm. The reduction of the volume of the liquid at screw-in leads 

to a very high pressure boosting, which can exceed the permitted maximum value by a multiple. Thus, 

before installation, the connection must be sufficiently emptied.
The screw-in of the thread process connection by using the terminal enclosure, the connection plug 

resp. the connection cable is not permitted.

The tightening of the thread process connection may only be done at the hexagon by a suitable 

spanner and with the maximum permitted torque strength (see chapter „Technical data“).

Содержание Precont CT

Страница 1: ...in features Wide range of applications Finely graded measuring ranges from 100 mbar up to 16 bar Wide process temperature range 40 C to 125 C Wide variety of process connections High protection class...

Страница 2: ...al manual and the relevant standards and rules This expert must have read and understood this technical manual and especially the safety notes The device may only be used within the permitted operatio...

Страница 3: ...ssure from 0 8 bar to 1 1 bar If the device is operated beyond these atmospheric conditions the EU type examination certificate can be used as a guide Additional tests for the special application cond...

Страница 4: ...and environmental temperature The installation of the device should be made if possible at temperature calmed places to get a reliable measuring result Strong temperature steps e g at filling of a hot...

Страница 5: ...M12 drill hole besides the plug Plug EN 175 301 803 C plug socket Plug EN 175 301 803 A plug socket Cable capillary inside the cable At the version with cable the environmental air pressure is lead t...

Страница 6: ...lation place of the device 4 3 Supply voltage The voltage applied to the terminal contacts may not exceed the maximum permitted supply voltage see chapter Technical data to avoid damage of the electro...

Страница 7: ...1 Electronic output 2 wire current 4 20mA Plug M12 Conductor color standard connection cable M12 A coded BN brown BU blue Plug EN 175 301 803 Cable Conductor color cable RD red BK black GNYE greenyel...

Страница 8: ...CS CONTROL SYSTEMGmbHlLauterbachstr 57lD 84307Eggenfeldenlwww acs controlsystem delinfo acs controlsystem de 8 Plug EN 175 301 803 Cable Conductor color cable RD red BK black WH white GNYE greenyellow...

Страница 9: ...rmation s must be enclosed An exact description of the application The chemical and physical characteristics of the product A short description of the occurred error 6 4 Return Before returning the de...

Страница 10: ......

Отзывы: