section 18-1J2 of the Canadian Electrical Code for installations within
Canada and in accordance with the authority having jurisdiction.
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, and D, or non-hazardous locations only.
WARNING
– EXPLOSION HAZARD –
Substitution of any components may
impair suitability for Class I, Division 2.
WARNING
– EXPLOSION HAZARD –
Do not disconnect equipment unless
power has been switched off or the area is known to be non-hazardous.
Connector:
Shielded RJ-45 socket, 8-pin, 10BaseT/100BaseTX.
Wiring:
Wired MDI. Unit does NOT support auto-crossover.
Protocol:
Modbus TCP/IP w/Web Browser Configuration.
IP Address:
Default static IP address is 128.1.1.100.
Port:
Up to 10 sockets supported, uses port 502 (reserved for Modbus).
Transient Protection:
Transient Voltage Suppressors (TVS) are applied
differentially at the transmit and receive channels. Additionally, the
metal shield is coupled to the earth ground terminal via an isolation
capacitor and TVS.
Data Rate:
Auto-sensed, 10Mbps or 100Mbps.
Duplex:
Auto-negotiated, Full or Half Duplex.
Compliance:
IEEE 802.3, 802.3u, 802.3x.
Modbus TCP/IP Protocol Support:
Uses built-in web pages for
configuration and control over ethernet via a standard web browser. Up
to 10 sockets may be selected. The module uses the standard Modbus
TCP/IP port number 502.
Rx/Tx Memory:
8K bytes of SRAM for receive/transmit buffers (FIFO).
Communication Distance:
The distance between two devices on an
Ethernet network is generally limited to 100 meters using recommended
copper cable. Distances may be extended using hubs, switches, or
fiber optic transmission. However, the total round trip delay time must
not exceed 512 bit times for collision detection to work properly with
CSMA/CD (half-duplex).
Port Status Indicators:
Green LED indicates link status (ON if auto-
negotiation has successfully established a connection), yellow LED
indicates activity (ethernet connection is busy/traffic is present).
Address:
The module IP address can be preset by the user (static) and
loaded from internal non-volatile memory, or it can be automatically
acquired at startup via a network server using a BOOTP (Bootstrap
Protocol), or DHCP (Dynamic Host Configuration Protocol). The unit
also includes a default mode toggle switch to cause the module to
assume a “known” fixed static IP address of 128.1.1.100 for
troubleshooting purposes.
LED Indicators:
RUN (Green) -
Constant ON if power is on and unit is OK. Continuous
flashing ON/OFF indicates unit is in “wink” ID mode.
ST (Yellow)
–
Blinks ON/OFF in default communication mode. Stays ON
if any input signal is out of range. Note that over-range indication may
mask default mode indication. Thus, open channels should be
terminated, since break detection (open channel) can cause over-
range indication.
LINK (Green)
–
Indicates Ethernet
link
status (ON if auto-negotiation has
successfully established a connection).
Ethernet Interface
Refer to Acromag Application
Note 8500-734 for instructions
on how to change the IP
address of your PC network
interface card in order to talk
to an Acromag module.
Controls & Indicators