If recalibration of any input is required, all applicable ranges should be done.
The following table gives the calibration values for these models. These
represent the input signals required to calibrate the range endpoints.
Your success in recalibrating the input will strongly depend upon the
accuracy and precision of your signal source.
Input Calibration Values For Supported Input Ranges
Available
INPUT CALIBRATION POINTS
Input
Ranges
LOW CALIBRATION
POINT (Cal Lo)
HIGH CALIBRATION
POINT (Cal Hi)
Type J TC
0.0
(0.000mV)
700.0
(39.130mV)
Type K TC
0.0
(0.000mV)
1300.0
(52.398mV)
Type T TC
0.0
(0.000mV)
390.0
(20.252mV)
Type R TC
0.0
(0.000mV)
1700.0
(20.215mV)
Type S TC
0.0
(0.000mV)
1700.0
(17.942mV)
Type E TC
0.0
(0.000mV)
950.0
(72.593mV)
Type B TC
260
(0.317mV)
1700
(12.426mV)
Type N TC
0.0
(0.000mV)
1200.0
(43.836mV)
100 mVDC
-100.000 mVDC
100.000 mVDC
±1.00 VDC
-1.00V DC
+1.00V DC
IMPORTANT:
Be sure to turn CJC off prior to calibrating any TC or voltage
ranges. For best results, be sure to use a precision millivoltage source
capable of reproducing the nominal thermoelectric endpoint signals at least
as accurate as the module itself (better than ±0.1% of span). In addition,
always allow the module to warm up several minutes prior to calibration.
WEB BROWSER
Calibration Page