Network Connector:

  9-pin D-Sub connector (female) with metal housing 

and 4-40 jack screw support. 

 

D-Sub Pin  Signal 

Description 

SHLD 

Shield (Connect to Earth Ground) 

NC 

No Connection 

Data A (TxD/RxD+) 

RTS 

Request To Send 

GND 

RS485 Logic Ground 

+5V 

+5V 

NC 

No Connection 

Data B (TxD/RxD-) 

NC 

No Connection 

 
Operating Temperature:  

 -25

C to +70

C (-13

F to +158

F). 

Storage Temperature:  

-40

C to +85

C (-40

F to +185

F). 

Relative Humidity:

  5 to 95%, non-condensing. 

Power Requirements:

  11-36V DC SELV (Safety Extra Low Voltage).  

Observe proper polarity.  Current draw may decrease up to 10% as the 
baud rate is increased to 12MB (data below is at 9600 baud). 

 

Supply  

961PB-2006 or 962PB-2006 Current Draw (9600bps) 

12V 

172mA Typical / 195mA Maximum 

15V 

133mA Typical / 146mA Maximum 

24V 

83mA Typical / 91mA Maximum 

36V 

61mA Typical / 67mA Maximum 

 
CAUTION:  

Risk of Electric  Shock 

– More than one disconnect switch may 

be required to de-energize equipment before servicing.

 

 
Power Supply Effect:   

Volts:  

Less than 

0.001% of output span change per volt for rated 

power supply variations. 

60/120 Hz Ripple:

  Less than 0.01% of output span per volt peak-to-

peak of power supply ripple.

 

Isolation: 

 Input channels (as a group), power, and network circuits are 

isolated from each other for common-mode voltages up to 250VAC, or 
354V DC off DC power ground, on a continuous basis (will withstand 
1500VAC dielectric strength test for one minute without breakdown).  
Complies with test requirements of ANSI/ISA-82.01-1988 for voltage 
rating specified. 

Installation Category:

  Designed to operate in an Installation in a Pollution 

Degree 2 environment with an installation category (over-voltage 
category) II rating. 

Electromagnetic Interference Immunity (EMI):

  Measurement shift is less 

than 

0.25% of input span for interference from switching solenoids, 

commutator motors, and drill motors. 

Electromagnetic Compatibility (EMC) - 
Minimum Immunity Per European Norm EN50082-1: 

Electrostatic Discharge (ESD) Immunity:  

4KV direct contact and 8KV 

air-discharge to the enclosure port per EN61000-4-2. 

Radiated Field Immunity (RFI):

  10V/M, 80 to 1000MHz AM and 

900MHz keyed carrier, per EN61000-4-3 and ENV50204. 

Electrical Fast Transient Immunity (EFT):

  2KV to power, and 1KV to 

signal I/O per EN61000-4-4. 

Enclosure and Physical 

Environmental 

CAUTION:

  Do not exceed 

36VDC peak, to avoid damage 
to the module. 
 

External Fuse:

  Select a high 

surge tolerant fuse rated for 
1A or less to protect unit.

 

Note that input channels are 
not isolated channel-to-
channel, except for small 
common-mode variations less 
than ±4V peak. 

 
These limits represent the 
minimum requirements of the 
standard, but product has 
typically been tested to comply 
with higher standards in some 
cases. 

Содержание 961PB-2006

Страница 1: ...rent Inputs Model 962PB 2006 Six Differential Voltage Inputs USER S MANUAL ACROMAG INCORPORATED Tel 248 624 1541 30765 South Wixom Road Fax 248 624 9234 Wixom MI 48393 2417 U S A Copyright 2002 Acroma...

Страница 2: ...Troubleshooting Tools 9 Using Connectors To Troubleshoot 10 Diagnostics Function 10 Diagnostics Table 10 CALIBRATION 11 TECHNICAL REFERENCE KEY FEATURES 13 HOW IT WORKS 14 SPECIFICATIONS 15 Model Num...

Страница 3: ...MINAL BLOCKS PROFIBUS CONNECTOR DB9 FEMALE PROF IBUS Acromag RUN PWR LED GREEN SLAVE ADDRESS HEX TB3 DP SLAVE ADDRESS SWITCHES REMOVABLE INPUTS 0 1 IN4 44 41 33 PWR NETWORK 13 IN0 16 IN1 21 5V 24 IN2...

Страница 4: ...dress 126 cannot be used in data exchange mode and is reserved for commissioning purpose only You must use the Set Slave Address command to change the internal EEPROM address following power up in ord...

Страница 5: ...the length indicated below for your transmission rate For baud rates not shown the lower length of the closest range end points apply i e 100M at 3Mbps Bus Segment Length Limit Per Baud Rate For Type...

Страница 6: ...AND END OF A NETWORK OR NETWORK SEGMENT SEGMENT 1 UP TO 1200 METERS UP TO 32 NODES PER SEGMENT END OF SEGMENT TERMINATION ON PROFIBUS MASTER A HOST PC WITH PROFIBUS CARD INSTALLED AND RUNNING APPLICAT...

Страница 7: ...IN1 TB1 DIFFERENTIAL CURRENTMONITORING INP Temperature Pressure Level Flow Speed 961PB DCS PLC NOTE 961PB INPUTS ARE NOT ISOLATED CHANNEL TO CHANNEL EXCEPT FOR COMMON MODE VOLTAGES LESS THAN 5V AS SUC...

Страница 8: ...oes not include an earth ground screw it may be necessary to strip the cable insulation near the field device and clamp the cable shield to a local grounding bar or surface as shown Connect Earth Grou...

Страница 9: ...nd Held ProfiBus Network Maintenance Tools Manufacturer Part Number Special Features Siemens BT 200 Primarily a Cable Tester Comsoft NetTest II Set 4000 7 06C J Includes DP Mono Master Functionality I...

Страница 10: ...ort this command and can read the diagnostic information from the Profibus device SYMPTOM POSSIBLE CAUSE POSSIBLE FIX Yellow BUS LED does not light Initialization Problem LED ON if module in data exch...

Страница 11: ...one for normal operation and another for accomplishing calibration The normal data exchange definition supports 6 input words 12 input bytes representing your measured values A second calibration def...

Страница 12: ...3 6 for the other channels of the same range 8 With user parameter bytes 0 1 select the next range to be calibrated Note 961PB The 4 20mA range is calibrated when the 0 20mA range is calibrated and i...

Страница 13: ...model number Range Variability The first 3 channels must share the same range but this can be different than the range of the last 3 channels Optional AC Current Input 961PB Only An optional AC curre...

Страница 14: ...4 9 current sink resistors across the inputs Voltage input models use 10 1 precision resistor voltage dividers at the input A multiplexer is used to connect each input voltage to an A D converter sepa...

Страница 15: ...figurable for 0 to 20mA 4 20mA 0 11 17mA and 0 1mA DC nominal input ranges A precision 24 9 current sink resistor converts the input current to a voltage that is processed by the A D converter An opti...

Страница 16: ...s except 0 1mA This includes the effects of repeatability terminal point conformity and linearization but does not include sensor error Measurement Temperature Drift Better than 50ppm C 0 005 C Analog...

Страница 17: ...0 01 of output span per volt peak to peak of power supply ripple Isolation Input channels as a group power and network circuits are isolated from each other for common mode voltages up to 250VAC or 3...

Страница 18: ...ty for Class I Division 2 WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has been switched off or the area is known to be non hazardous Interface Standard 3 wire RS 485 multi drop h...

Страница 19: ...the Set Slave Address command before completing initialization and assuming the data exchange mode IMPORTANT Address Setting The internal EEPROM address setting and external switch setting is 126 from...

Страница 20: ...ive low inputs a value of 1 means the input is ON active low near 0V while a value of 0 specifies the input is OFF or in its high state usually 0V This model includes three user parameterization bytes...

Страница 21: ...ory The following table shows the revision history for this document Release Date Version EGR DOC Description of Revision 03 APR 03 A BC KLK Initial release 28 OCT 03 B BC KLK UL updates per ECN 03J02...

Отзывы: