Acromag 961PB-2006 Скачать руководство пользователя страница 16

BusWorks® 

961/962PB Module User’s Manual            ProfiBus Differential I/V Input 

__________________________________________________________________ 

 

_______________________________________________________________________________________ 
Acromag, Inc.   Tel:248-624-1541  Fax:248-624-9234   Email:

[email protected]

  http://www.acromag.com 

16 

 

 

Input Burden

:  A function of the wire gauge resistance used for primary 

turns (the current carrying wire being monitored). 

AC Current Sensor to Transmitter Wiring Distance

:  400 feet 

maximum for 18 gauge wire.  Other wire gauges can be used as long 
as the resistance of both wires is less than 5

.

 

Input Overload

:  The AC current sensor will withstand overload 

conditions as follows: 

 

20 times full scale for 0.01 seconds. 

 

10 times full scale for 0.1 seconds. 

 

5 times full scale for 1.0 second.

 

DC Voltage (962PB Only):

  A 10:1 input divider is installed at the input 

(utilizing divider resistor values of 100K and 10.5K).  User-configurable 
for the nominal bipolar DC voltage ranges of 

10V, 

5V, 

2.5V, 

1.25V, 

625mV, 

313mV, 

156mV, and 

78mV DC. 

Input Impedance:

  110.5K

Voltage Input Reference Test Conditions:

  -10 to 10V DC input; 

ambient temperature = 25

C; 24VDC supply. 

Input Overvoltage Protection:

  Bipolar Transient Voltage Suppressers 

(TVS), 18V clamp level typical. 

 

Accuracy:

  Better than 

0.05% of span, typical for nominal input ranges 

(except 0-1mA).  This includes the effects of repeatability, terminal point 
conformity, and linearization, but does not include sensor error. 

Measurement Temperature Drift:

  Better than 

50ppm/

C (±0.005%/

C). 

Analog to Digital Converter (A/D): 

 A

 

16-bit 

-

 converter.

 

Resolution:

  0.005% or 1 part in 20000 (961PB), 0.0025% or 1 part in 

40000 (962PB, full bipolar range). 

Input Conversion Rate:

 80ms per channel, or 480ms for six input channels. 

Input Filter: 

 Normal mode filtering, plus digital filtering optimized and fixed 

per input range within the 

-

 ADC. 

Input Filter Bandwidth:

  -3dB at 3Hz, typical. 

Noise Rejection (Normal Mode): 

 40dB @ 60Hz, typical  with 100

 input 

unbalance. 

Noise Rejection (Common Mode):

  140dB @ 60Hz, typical with 100

 input 

unbalance. 

 
ProfiBus Trade Organization (PTO):  

Certified.

 

Safety Approvals:

  CE marked (EMC Directive 89/336/EEC);  UL Listed 

(UL508, UL1604);  cUL Listed (Canada Standard C22.2, No. 142-
M1987 & 213-M1987);  Hazardous Locations: Class 1; Division 2; 
Groups A, B, C, and D. 

 
Dimensions:

  1.05 inches wide, 4.68 inches tall, 4.35 inches deep.  Refer to 

the dimensions drawing at the front of this manual. 

DIN Rail Mount:

  

Type EN50022; “T” rail (35mm). 

I/O Connectors:

  Removable plug-in type terminal blocks rated for 

15A/300V; AWG #12-24 stranded or solid copper wire. 

Case Material:

  Self-extinguishing NYLON type 6.6 polyamide thermoplastic 

UL94 V-2, color beige; general purpose NEMA Type 1 enclosure. 

Printed Circuit Boards:

  Military grade FR-4 epoxy glass. 

Shipping Weight: 

1 pound (0.45 Kg) packed. 

Analog Inputs 

General Specifications 

Agency Approvals 

Enclosure and Physical 

Содержание 961PB-2006

Страница 1: ...rent Inputs Model 962PB 2006 Six Differential Voltage Inputs USER S MANUAL ACROMAG INCORPORATED Tel 248 624 1541 30765 South Wixom Road Fax 248 624 9234 Wixom MI 48393 2417 U S A Copyright 2002 Acroma...

Страница 2: ...Troubleshooting Tools 9 Using Connectors To Troubleshoot 10 Diagnostics Function 10 Diagnostics Table 10 CALIBRATION 11 TECHNICAL REFERENCE KEY FEATURES 13 HOW IT WORKS 14 SPECIFICATIONS 15 Model Num...

Страница 3: ...MINAL BLOCKS PROFIBUS CONNECTOR DB9 FEMALE PROF IBUS Acromag RUN PWR LED GREEN SLAVE ADDRESS HEX TB3 DP SLAVE ADDRESS SWITCHES REMOVABLE INPUTS 0 1 IN4 44 41 33 PWR NETWORK 13 IN0 16 IN1 21 5V 24 IN2...

Страница 4: ...dress 126 cannot be used in data exchange mode and is reserved for commissioning purpose only You must use the Set Slave Address command to change the internal EEPROM address following power up in ord...

Страница 5: ...the length indicated below for your transmission rate For baud rates not shown the lower length of the closest range end points apply i e 100M at 3Mbps Bus Segment Length Limit Per Baud Rate For Type...

Страница 6: ...AND END OF A NETWORK OR NETWORK SEGMENT SEGMENT 1 UP TO 1200 METERS UP TO 32 NODES PER SEGMENT END OF SEGMENT TERMINATION ON PROFIBUS MASTER A HOST PC WITH PROFIBUS CARD INSTALLED AND RUNNING APPLICAT...

Страница 7: ...IN1 TB1 DIFFERENTIAL CURRENTMONITORING INP Temperature Pressure Level Flow Speed 961PB DCS PLC NOTE 961PB INPUTS ARE NOT ISOLATED CHANNEL TO CHANNEL EXCEPT FOR COMMON MODE VOLTAGES LESS THAN 5V AS SUC...

Страница 8: ...oes not include an earth ground screw it may be necessary to strip the cable insulation near the field device and clamp the cable shield to a local grounding bar or surface as shown Connect Earth Grou...

Страница 9: ...nd Held ProfiBus Network Maintenance Tools Manufacturer Part Number Special Features Siemens BT 200 Primarily a Cable Tester Comsoft NetTest II Set 4000 7 06C J Includes DP Mono Master Functionality I...

Страница 10: ...ort this command and can read the diagnostic information from the Profibus device SYMPTOM POSSIBLE CAUSE POSSIBLE FIX Yellow BUS LED does not light Initialization Problem LED ON if module in data exch...

Страница 11: ...one for normal operation and another for accomplishing calibration The normal data exchange definition supports 6 input words 12 input bytes representing your measured values A second calibration def...

Страница 12: ...3 6 for the other channels of the same range 8 With user parameter bytes 0 1 select the next range to be calibrated Note 961PB The 4 20mA range is calibrated when the 0 20mA range is calibrated and i...

Страница 13: ...model number Range Variability The first 3 channels must share the same range but this can be different than the range of the last 3 channels Optional AC Current Input 961PB Only An optional AC curre...

Страница 14: ...4 9 current sink resistors across the inputs Voltage input models use 10 1 precision resistor voltage dividers at the input A multiplexer is used to connect each input voltage to an A D converter sepa...

Страница 15: ...figurable for 0 to 20mA 4 20mA 0 11 17mA and 0 1mA DC nominal input ranges A precision 24 9 current sink resistor converts the input current to a voltage that is processed by the A D converter An opti...

Страница 16: ...s except 0 1mA This includes the effects of repeatability terminal point conformity and linearization but does not include sensor error Measurement Temperature Drift Better than 50ppm C 0 005 C Analog...

Страница 17: ...0 01 of output span per volt peak to peak of power supply ripple Isolation Input channels as a group power and network circuits are isolated from each other for common mode voltages up to 250VAC or 3...

Страница 18: ...ty for Class I Division 2 WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has been switched off or the area is known to be non hazardous Interface Standard 3 wire RS 485 multi drop h...

Страница 19: ...the Set Slave Address command before completing initialization and assuming the data exchange mode IMPORTANT Address Setting The internal EEPROM address setting and external switch setting is 126 from...

Страница 20: ...ive low inputs a value of 1 means the input is ON active low near 0V while a value of 0 specifies the input is OFF or in its high state usually 0V This model includes three user parameterization bytes...

Страница 21: ...ory The following table shows the revision history for this document Release Date Version EGR DOC Description of Revision 03 APR 03 A BC KLK Initial release 28 OCT 03 B BC KLK UL updates per ECN 03J02...

Отзывы: