14
Rate, start time, start minute
respectively
3 flats, 4 valleys
Start: 0-23
Start Score: 1-59
1059H
The second set of timetables,
Each period occupies three bytes,
Rate, start time, start minute
respectively
R/W
Same as the first set of
timetables
106EH
The third set of timetables,
Each period occupies three bytes,
Rate, start time, start minute
respectively
R/W
Same as the first set of
timetables
1083H
The fourth set of timetables,
Each period occupies three bytes,
Rate, start time, start minute
respectively
R/W
Same as the first set of
timetables
1098H
Voltage ratio
4
R/W
plastic
109AH
Current transformation ratio
4
R/W
plastic
109CH-109FH
reserved
2000H
Voltage
4
R
Integer
Keep 1 decimal place, the
unit is V
If the value is U= 2200 , PT
= 1 ;
U=U* P T= 2200 * 0.1 * 1 =
220.0 V
2001H-200BH
reserved
200CH
current
4
R
Integer, unit A
2 decimal places
If the value is I= 200 ,
CT=10;
I=I*CT= 2 00*0.01*10 =
20A
200DH-2013H
reserved
2014H
Active power
4
R
Integer signed
Unit kW
3 decimal places
If the value is 11720, P
T=10, CT=10;
Then value = value * P
T*CT=
11720*0.001*10*10=1172 .
0kW
2016H-201BH
reserved
201CH
reactive power
4
R
Integer signed