- 3 -
Active
power/reactive
power/apparent power
■
Four quadrant electric
energy measurement
■
Maximum demand
□
Multiple rate electric
energy measurement
□
Power
quality
monitoring
Total harmonic content
■
subharmonic(2-31 times)
■
Data logging
Incident record
□
Alarm
□
Built-in clock
□
communicatio
n
RS485 interface
■
Optional
function(cho
ose one)
J(2DO)
A1+(B1 or C1)
(4DI+2DO or
4DI+EP)
*
K(4DI)
pulse(2channels)
Note:1、
“■”is standard allocation function,
“□”is matching function,Above instrument stanfard
1 channel RS485 communication;
2、Terminal connection mode corresponding to A1/B1/C1 and so on in selection function;
3、Pulse output and relay output can not be selected at the same time;
4、When you select an event loggong feature,you must configure the DI or DO feature.
4
.
Technical parameter
Technical parameter
Value
Input
Net work
3-phase 3-wire,3-phase 4 wire
Frequency
45~65Hz
Voltage
Rating
:AC 57.7V/100V(100V)、220V/380V(400V)
Overload:1.2-fold rating(continuous);2-fold rating/1second
Consumption:<0.2VA
Current
Rating
: 80A,120A,200A .etc(See specific product
specifications,special parameters can be customized)
Overload:1.2-fold rating(continuous);10-fold rating/1 second
Consumption:
<
0.2VA