- 20 -
secondary side coefficient
16-17
Primary side and secondary
side coefficient of current
R
Float mould
2
18-19
Power,primary and secondary
side coefficients
R
Float mould
2
21-23
Multi-rate time period 1
R/W
Information about multi-rate:8 time period
、
4
rates; Each period of time occupies 3
bytes:the first byte is for hour
、
the second is
for minute
、
the third is for rate;
four rates: 0-tip, 1-peak,2-Flat, 3-valley.
3
24-26
Multi-rate time period 2
R/W
3
27-29
Multi-rate time period 3
R/W
3
30-32
Multi-rate time period 4
R/W
3
33-35
Multi-rate time period 5
R/W
3
36-38
Multi-rate time period 6
R/W
3
39-41
Multi-rate time period 7
R/W
3
42-44
Multi-rate time period 8
R/W
3
53
First channel Switching input
RO
Switching as 1,non-switching as 0.
1
54
Second
channel
Switching
input
RO
1
55
Third channel Switching input
RO
1
56
Fourth channel Switching input
RO
1
57
Fifth channel Switching input
RO
1
58
Sixth channel Switching input
RO
1
59
Seventh channel Switching
input
RO
1
60
Eighth channel Switching input
RO
1
61
First channel Switching output
R/W
Writing 1,Output relay contact is closed,
Writing 0,Output relay contact is opening.
1
62
Second
channel
Switching
output
R/W
Writing 1,Output relay contact is closed,
Writing 0,Output relay contact is opening.
1
63
Third channel Switching output
R/W
Writing 1,Output relay contact is closed,
Writing 0,Output relay contact is opening.
1
64
Fourth
channel
Switching
output
R/W
Writing 1,Output relay contact is closed,
Writing 0,Output relay contact is opening.
1
128
Year
R/W
Time://BCD code format.
Setting time requires the use of the 10H
command to set all the time
1
129
Month
R/W
1
130
Day
R/W
1
131
Hour
R/W
1
132
Minute
R/W
1