Levels
Function
UINT32
Set-punkter
Starting level
Start
50
Stop level
Stop
54
Pumpe control
UINT32
UINT32
INT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
Current
Min. current
Latest
operating
time
Latest
capacity
Outlet flow
Inlet flow
Total
quantity
Quantity
today
Quantity
yesterday
Pump
26
44
64
58
78
226
116
144
172
Description
Current from
energy
meter, coil or
CUE
(Amps with 1
decimal)
Low current limit
(Amps with 1
decimal)
“If min. current
is not exceeded,
start failure
occurs after 60
sec”
(Seconds)
Calculated
capacity
(L/s with 2
decimals)
Calculated
flow
(L/s with 2
decimals)
Calculated
flow
(L/s with 2
decimals)
Calculated
quantity
(m³ with 2
decimals)
Calculated
quantity
(m³ with 2
decimals)
Calculated
quantity
(m³ with 2
decimals)
External gauges.
External gauges
UINT32
UINT32
UINT32
Total
Today
Yesterday
Rain gauge
256
258
260
Description
(0,2 mm per pulse with 1 decimal)
(0,2 mm per pulse with 1 decimal)
(0,2 mm per pulse with 1 decimal)
Alarm and Warning.
Pumpword: Register 70
Status
Warning
Alarm
Bit 0: Pump started
√
Bit 1: Pump error - Therma
√
Bit 2: Pump error - Klixon
√
Bit 3: Pump - manual mode
√
Bit 4: Pump error - operation signal not received
√
Bit 5: Internal
Bit 5: Pump warning - Low flow
√
Bit 6: Pump warning - long operation time (Time > total time / (total
starts x 1,5))
Bit 7: Internal
Bit 8: Internal
√
Bit 9: Pump error - High level switch
√
Bit 10: Pump error - High level
√
Bit 11: Pump - started by high level switch
√
Bit 12: Pump - Back stopped
√
Bit 13: Pump error - repeatedly (needs to be reset)
√
Bit 14: Pump - Manual mode
√