TROUBLE SHOOTING:
IMPORTANT: BEFORE MAKING ANY OF THE REPAIRS LISTED, MAKE SURE THE WATER 
COOLER IS DISCONNECTED FROM THE ELECTRICAL SUPPLY AND THE WATER SUPPLY 
VALVE IS SHUT OFF.

1. Adjustments:

a. Cartridge – The water flow can be adjusted using a slotted narrow blade screwdriver and

 turning clockwise to increase flow and counterclockwise to decrease flow.

b. Cold Water Thermostat – The water temperature can be adjusted using a slotted

 screwdriver and turning clockwise to make colder and counterclockwise to make warmer.

c. Bubbler Stream – Bubbler can be rotated slightly to direct the stream backwards or

 forwards. Adjust the stream to minimize splashing. Splashing may occur from bubbler
 stream if the unit is not level. Shim lower mounting points, if necessary, to level cooler.

2. Compressor Does Not Run

a. Check the electrical receptacle for power and correct voltage. The incoming voltage must be

 within 10% of the rated voltage on the serial nameplate.

b. The cold thermostat is accessible by removing the bottom access cover. If the cold

 thermostat capillary bulb loses its charge or becomes kinked it will fail in the open position
 causing a disruption of power to the compressor. Unplug the water cooler and using an
 ohm meter check for continuity across the two electrical terminals on the thermostat. Install a     
 new thermostat if there is no continuity.

c. Check for loose wires within the compressor box. The incoming power leads must be

 connected to the overload and relay. 

d. If all components check positive for continuity then test the wiring harness plug for

 continuity to see if there is a broken wire within the wiring harness insulation.

3. Compressor Runs – Water Is Warm

a. The most common cause for a water cooler to run without producing cold water is a

 loss of refrigerant. The water cooler must be taken to a certified refrigerant technician
 for repairs.

b. Make sure the condenser fan motor is operative. The fan blade must turn freely to help

 remove the heat of compression. 

c. An incorrect refrigerant charge, restriction or defective compressor (not pumping) will

 also cause the compressor to run without producing cold water. All these signs indicate
 a problem within the refrigeration system and the water cooler must be checked by an
 authorized service company.

4. Compressor Cycling On Overload Protector 

a. A dirty condenser or a blocked fan will cause a high head pressure and frequent cycling

 of the overload protector. 

b. Check the incoming voltage to make sure it is within 10% of the serial nameplate rating. 
c. A restriction or moisture in the system will also cause intermittent cycling. A certified

 refrigeration mechanic should be contacted in this situation. 

d. Change the overload or relay if defective.

5. Noisy Operation 

a. Check to make sure the fan blade is rotating freely. 
b. Make sure the water cooler is correctly mounted to the wall. Absence of the two lower

 mounting bolts may cause excess noise and vibration. 

c. Check the compressor mounting to make sure the pins and clips are not rattling. If the

 compressor appears to be noisy internally, it must be replaced.

ACORN ENGINEERING FIELD SERVICE

TOLL FREE

 800-743-8259 • 

LOCAL

  626-855-4866 • 

FAX

 626-855-4863

7020-904-001

Page 5 of 11

Date: 03/12/15

Please visit 

 

for most current specifications.

www.acorndrinkingfountains.com

 

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

Содержание A171.8 Series

Страница 1: ...he repair or replacement of the defective materials shall constitute the sole remedy of the Buyer and the sole remedy of Acorn under this warranty Acorn shall not be liable under any circumstances for incidental consequential or direct charges caused by defects in the materials or any delay in the repair or replacement thereof This warranty is in lieu of all other warranties expressed or implied P...

Страница 2: ...l approach installation Adjust vertical dimension as required to comply with federal state and local codes For Child ADA compliant parallel approach decrease spout height to 30 maximum above finished floor Provide clear floor space as required ACORN ENGINEERING FIELD SERVICE TOLL FREE 800 743 8259 LOCAL 626 855 4866 FAX 626 855 4863 7020 904 001 Page 2 of 11 AIR FLOW A 3 8 NCT SUPPLY INLET B WASTE...

Страница 3: ...pler or other components 7 Power supply must be identical in voltage cycle and phase to that specified on the cooler data plate Electrical outlet and furnished power cord with plug must be used to supply power to fixture Do NOT wire compressor directly to the power supply 8 This unit must be grounded per the requirements of applicable electrical codes 9 WARNING Warranty is voided if installation i...

Страница 4: ...p 1 1 4 O D p trap by others waste connection START UP 1 Before connecting power supply and assembling bottom cover to water cooler but after thoroughly flushing the supply line and connecting it to the fixture turn on building water supply and check all connections for leak 2 Air within the water cooler system or the structure supply piping will cause an irregular bubbler outlet stream until purg...

Страница 5: ...inuity to see if there is a broken wire within the wiring harness insulation 3 Compressor Runs Water Is Warm a The most common cause for a water cooler to run without producing cold water is a loss of refrigerant The water cooler must be taken to a certified refrigerant technician for repairs b Make sure the condenser fan motor is operative The fan blade must turn freely to help remove the heat of...

Страница 6: ...om of fixture but do not remove Move complete valve bracket assembly further back from the front push pad and tighten lock in place 8 If Light Within Sensor Does Not Flash When User is Within Range a Verify transformer input and output voltages 120VAC 9VDC output b Replace defective transformer c Transformer polarity crossed Replace transformer sensor may be damaged and also need replacement d Sen...

Страница 7: ...ER MAINTENANCE Note Use the universal maintenance tool to perform the following 1 Strainer plug must be removed before cartridge replacement and strainer maintenance no need to turn the water off at the angle stop Some residual water will drain during plug removal 2 Clean strainer as needed using clean water 3 Cartridge replacement insert diamond end of the universal tool into push button rotate 9...

Страница 8: ...ensure that the water line is depressurized Push collet square towards the push in fitting body and hold While holding the collet in pull on the PE tubing to remove from the push in fitting TO CUT TUBE Cut to fit length of 1 4 PE tubing and remove any burrs or sharp edges Ensure that the outside diameter is free from score marks Tube ends should be square INSERTING THE TUBE 1 Firmly and fully inse...

Страница 9: ...rawing above 27 ACORN ENGINEERING FIELD SERVICE TOLL FREE 800 743 8259 LOCAL 626 855 4866 FAX 626 855 4863 7020 904 001 Page 9 of 11 3 2 1 23 20 4 5 7 8 24 9 10 11 12 22 15 13 17 18 24 21 19 6 14 25 25 25 24 26 16 27 15 15 27 NOTE Flow Restrictor Only Available With Low Flow Bubbler COOLER PARTS BREAKDOWN NOTE See page 11 for fixture drawing corresponding to table of parts below Date 03 12 15 Plea...

Страница 10: ...awing corresponding to table of parts below ACORN ENGINEERING FIELD SERVICE TOLL FREE 800 743 8259 LOCAL 626 855 4866 FAX 626 855 4863 7020 904 001 Page 10 of 11 3 2 1 23 20 4 5 7 8 12 22 15 13 17 18 24 21 19 6 14 25 16 27 NOTE Flow Restrictor Only Available With Low Flow Bubbler 9 30 38 37 36 31 30 34 35 32 28 33 31 29 30 31 Date 03 12 15 Please visit for most current specifications www acorndrin...

Страница 11: ...20 COVER GRANITE 7003 035 299 COVER STAINLESS STEEL 13 7003 201 000 CONDENSER 7012 801 000 COMPRESSOR 7012 030 001 COMPRESSOR 220V 7012 802 000 START RELAY 7012 031 000 START RELAY 220 7012 803 000 START CAPACITOR 7012 032 000 START CAPACITOR 220 17 7003 350 000 FAN BLADE 7003 302 000 FAN MOTOR 7012 062 001 FAN MOTOR 220V 19 7003 120 000 EVAPORATOR ASSEMBLY 20 7003 014 199 HANGER BRACKET 21 1895 1...

Отзывы: