Page 16 / 22
User Manual ACO5000
Timing for the safe interlock procedure with permanent signals for the START and STOP
SAFE INTERLOCK implemented, start by permanent contact
#
Name
DESCRIPTION
1
24V_OUT
NOT TO BE USED when the SAFE
INTERLOCK is active.
2
ENABLE
Signal is delivered by the PLC only after
reception of the READY signal /
terminals 5-6 DR_R
3
EN_A
Confirmation back to the PLC that the
ENABLE has been activated.
4
EN_A
5
DR_R
READY Relay output
NO potential free contact.
Closed when ready
Failure when open
6
DR_R
7
START
Apply 24 VDC to START the drive.
8
STOP
Signal is delivered by the PLC only after the
reception of the ENABLE confirmation /
terminals 3-4 EN_A. This input has the
function of a START enable.
9
RESET
Apply 24 VDC to reset. DON’T use a jumper.
10 0 V
Electronic ground of the drive
To the machine
controller (PLC)
From the machine
controller (PLC)
From the
machine
controller
(PLC)
+24 VDC
L1, L2, L3
DR_R
EN_A
START
STOP
ENABLE
Safe interlock
required
STATUS
START
START
STOP
POWER UP
POWER DOWN
min. 10 ms
min. 10 ms
open
closed
open
closed
min. 50 ms
SAFE