ACL CSC 200 Combustion Safety Control

FEATURES














I

No Programming

CSA approved for Class , Div 2 location

Operational ambient temperature of -40° to +60° Celsius

CSA approved C22.2 No 199-M89. Combustion safety

controls and solid-state Ignitors for Gas & Oil burning
equipment

CSA B149.3 - 10 compliant, meets NFPA standards
Type 4x enclosure, corrosive resistant and weatherproof

100% fail safe design

Safety lockout for high temperature setting
Onboard solenoid driver for power reduction to solenoids and peak-hold solenoids
Two adjustable type K thermocouple inputs for monitoring two

separate temperature points (process temp. & high temp.)

Pilotless burner control selectable. Single and dual stage, Low fire and High fire
Shutdown input (ie. Low level shutdown, pressure shutdown)
2 Selectable thermocouple ranges of -60°C to 1100°C or 0°C to 500°C (-75°F to

2012° F or 32° F to 932° F)

Adjustable dead band from 1, 2, 3 and 5 degrees C or 2, 4, 6 and 10 degrees F

°C

° F

The ACL CSC 200 is designed to be used in conjunction with the ACL combustion
module for a complete safety combustion device. The ACL CSC 200 provides burner
ignition and flame fail, as well as monitoring of two separate thermocouple inputs which
can be utilized for temperature control in process applications such as tanks, line
heaters, re-boilers or any other application where accurate temperature monitoring or
control is required. The system is designed to operate with or without a continuous
pilot.

The two independent temperature set points can be adjusted with the three membrane
push buttons on the face of the controller with LED indication of Temp 1 or Temp 2.
Initial set up for temperature ranges,display and dead band can be obtained through dip
switch selections for various user preferences.

Easy to read four digit seven segment LED display
LED indication of thermocouple 1 or 2 values displayed

or

readout

12/24VDC and solar
Low power consumption (Power save mode operates as low as 1.2 Watts)

On/Off control

“THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I DIVISION 2, GROUPS A,B,C, &D OR NONHAZARDOUS
LOCATIONS ONLY”

“WARNING-EXPLOSION HAZARD- SUBSTITUTION OF COMPONENTS MAY IMPAIR THE SUITABILITY FOR
CLASS I DIVISION 2”

DESCRIPTION

Содержание CSC 200

Страница 1: ...on Safety Control WARNING ACL is not responsible for the misuse or incorrect application of this product This manual must be read in its entirety before installation of this controller Installation must be performed by a qualified technician and must adhere to the standards set by the local regulatory authorities INSTALLATION MANUAL ACL CSC 200 Combustion Safety Control FOR ...

Страница 2: ...4 6 Manufacturing Inc ACL ACL CSC 200 Combustion Safety Control ...

Страница 3: ...d in conjunction with the ACL combustion module for a complete safety combustion device The ACL CSC 200 provides burner ignition and flame fail as well as monitoring of two separate thermocouple inputs which can be utilized for temperature control in process applications such as tanks line heaters re boilers or any other application where accurate temperature monitoring or control is required The ...

Страница 4: ...Whether the I pilotless or intermittent selection or C continuos pilot selection is used the controller will perform as above except the continuous pilot will be initiated by on off as well as temperature demand switch and remain on regardless of temperatures setting The ACL CSC 200 Combustion Safety Control operates in a voltage range between 10 30 Volts DC The terminals are 19 positive 20 negati...

Страница 5: ...ion when cleared latch locks out a restart until a manual reset of the On Off switch is turned off then on or the remote reset switch is opened then closed The alarm status provides for remote indication of whether the CSC 200 is in a normal operating mode or if it is in a shutdown state or turned off either remotely or locally Alarm status terminals 11 and 12 are a dry set of contacts When power ...

Страница 6: ...unnecessary stroking of the main safety shutdown valves to control main gas to the burner for temperature control This output also has the low power feature of the onboard solenoid driver T MAIN INTERMITTENT PILOT Pilotless MAIN OUTPUT CONNECTIONS The ACL CSC 200 controller provides this feature for applications where a continuous pilot may not be desirable The pilot output is only energized when ...

Страница 7: ...ugh the designated dip switch setting or OPEN if the thermocouples are not connected or failed open ACL CSC 200 Combustion Safety Control Power Failure Indication if loss of power to controller occurs Flame Fail Indicates that pilot has gone out and failed to re light Process temperature indication of either TC 1 or TC 2 whichever is selected Indicates switch has been turned off to ignition Remote...

Страница 8: ...utdown clears and controller calls for heat Latches temp 2 and locks controller from restarting when temperature clears below setpoint When set to off controller ignition resumes automatically if temperature falls below setpoint and all shutdowns are clear If power failure to controller occurs the power fail latch setting doesn t allow controller to restart ignition when power returns When set to ...

Страница 9: ...CLCombustion Safety Control IgnitionModule HighVoltage IgnitionWire ToIgnitor Flame RodonBurner P G V TC 1 TC 2 Remotereset S D Jumper whennot used A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 25 26 27 28 P A G V Yellow Red AUX LLSD PSD Shutdowns Proof of closure Main Pilot Pilot solenoid Mainsolenoid Temperaturecontrolled mainsolenoid drycontacts Togroundlug onpilot or burner 22 T Main...

Страница 10: ...and Oil Burning Equipment CSA Standard C22 2 No 213 M1987 Non Incendive Electrical Equipment for Use in Class Division 2 Hazardous Locations UL Standard 50 12th Edition Industrial Control Equipment for Use in Hazardous Classified Locations UL746C 6th Edition Standard for Polymeric Materials Use in Electrical Equipment Evaluations UL 508 17th Edition Industrial Control Equipment ANSI UL 698 13th Ed...

Страница 11: ...___________________________________ _____________________________________________________________________ _____________________________________________________________________ _____________________________________________________________________ _____________________________________________________________________ _____________________________________________________________________ ______________...

Страница 12: ...anship and that any product which is found to be defective in such workmanship or material will be repaired or replaced by Seller for a period of one year from purchase date Warranty of such items do not include shipping installation or set up ACL Manufacturing Inc Shall not be liable for any special indirect consequential or other damages of a like general nature including without limitation loss...

Отзывы: