background image

6

Содержание SC-09WGLD-HP230

Страница 1: ......

Страница 2: ...6 ...

Страница 3: ......

Страница 4: ......

Страница 5: ......

Страница 6: ......

Страница 7: ... Not all items included with equipment purchase ...

Страница 8: ......

Страница 9: ...ions to ensure proper airflow 5 Wall or roof is strong enough to withstand the full weight and vibration of the outdoor unit for wall or roof installation only 6 Outdoor unit is out of reach of children and does not obstruct walkways 7 Outdoor unit is not exposed toexcessive dust or strong wind 8 Condensate water can drain freely during heating 9 Maintenance and repairs can be easily performed on ...

Страница 10: ...bracket for centering the indoor unit on the wall 5 Mounting bracket must be installed horizontally and level right to left NOTE Condensate drain pan has built in pitch for proper drainage 6 Secure mounting bracket to wall with a minimum of five screws evenly spaced to properly support indoor unit weight NOTE It is recommended to install screw anchors for sheet rock concrete block brick and such t...

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ... piping and tighten flare nut using a standard wrench and a torque wrench as shown in the indoor piping section 5 Carefully tighten flare nuts to correct torque level referring to theTorqueTable below Service Valve Cover 4 Properly align piping and tighten flare nut using a standard wrench and a torque wrench as shown in figure to the below Carefully tighten flare nuts to correct torque level refe...

Страница 17: ...mp The drain hose must slope downward with no kinks raises or fluctuations PIPING INSTALLATION Drain hose Outlet pipe Drain Rubber Plug Right Left 1 Connect the field supplied drain hose to the outlet pipe of indoor wall unit A field supplied transition or adapter may be required 2 Apply pipe insulation to the entire drain line and joints to prevent sweating 3 The through wall hole for the drain h...

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ...uation duration depends on the vacuum pump size and unit s capacity generally 20 minutes for the 9 000 BtuH units to 1 hour for a larger 36 000 BtuH unit 6 Close the manifold valves and shut off the pump a If vacuum holds below 700 microns for 15 minutes the system can be considered dry and leak free Go to step 5 b If vacuum increases to 800 microns or greater this is an indication of moisture in ...

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ...em load is too high 3 Indoor coil is blocked or dirty 1 Communication cable is mis wired between indoor and outdoor units 2 Indoor or Outdoor control board malfunction 1 Incorrect refrigerant charge level 2 Refrigerant metering device malfunction 3 Compressor malfunction Control board malfunction 1 No jumper cap inserted on the control board 2 Incorrect or damaged jumper cap on control board 3 Ind...

Страница 27: ......

Страница 28: ......

Страница 29: ...y air filters will affect the performance and the longevity of your unit It is recommended that air filters be cleaned every three 3 months To access and clean the filter CARE AND CLEANING 1 Open Front Panel Firmly grasp both sides of the front panel and pull upward to about 60 degree angle NOTE do not force panel open 2 Remove Filter Remove the filter as indicated in the figure at right 3 Clean F...

Страница 30: ...Resolution Process In order for any warranty situation to be resolved the following process must be followed 1 AN EPA certified contractor must diagnose the equipment and provide a diagnosing procedure part number or part description that is needed and the model and serial number s of the system in question ACiQ may also request an original installation invoice at its discretion This information w...

Страница 31: ...as service and maintenance records of all equipment on the warrantied system including but not limited to proof of a minimum of a once a year maintenance plan 10 Warranties will only be applicable to products installed at their original installation location and reinstalled equipment will not be covered by any warranty at the discretion of ACiQ 11 Defective parts must be returned to ACiQ through a...

Страница 32: ...loor New York NY 10019 www adr org JAMS 1920 Main Street Ste 300 Irvine CA 92614 www jamsadr com or subject to our approval any other arbitration organization These organizations rules can be obtained by contacting the organization or visiting its website If the chosen arbitration organization s rules conflict with this Arbitration Clause the provisions of this Arbitration Clause control The award...

Отзывы: