AUTOMATION COMPONENTS, INC Version : 4.0
2305 Pleasant View Road I0000685
Middleton, Wisconsin 53562
Page 3 of 4
PRODUCT SPECIFICATIONS
Supply
Voltage
(1) Li/MnO2 3.0 VDC Battery, 1400 mAH (e.g. Duracell DL123A)
RF
Data Protocol
IEEE 802.15.4-2003/2006
Operating Frequency
902-928 MHz
Output Power
+11 dBm
Receiver Sensitivity
-110 dBm
Open Field Range
One mile (line of sight)
Data Transmission Interval
75 seconds (standard), 300 seconds (option)
Temperature
Accuracy
± 1
°
F
Sensor Operating Range
32 to 104
°
F (0 to 40°C)
Humidity
Accuracy
±3% RH
Sensor Operating Range
10 to 90% RH
Features
User Interface
External Link Button (optional)
Enclosure
Material
ABS (standard and ruggedized)
Rating
UL 94 HB (standard), UL 94 5VA (ruggedized)
Environment
Operating Temperature
32 to 104F (0 to 40°C) standard
32 to 140°F (0 to 60
°
C) ruggedized
Operating Humidity
0 to 95% RH (non-condensing)
WARRANTY SPECIFICATION
The ACI Wireless Series is covered by ACI’s Two (2) Year Limited Warranty, which is located in the front of
ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s web site:
WEEE Directive
At the end of their useful life the packaging and product should be disposed of via a suitable recycle
center. Do not dispose of with household waste. Do not burn.