AUTOMATION COMPONENTS, INC                                                                                                                                             Version : 4.0 
2305 Pleasant View Road                                                                                                                                                                          I0000685   
Middleton, Wisconsin 53562                                             

Page 3 of 4                                       

www.workaci.com

  (888) 967-5224                                                                                                                                              

 

 

PRODUCT SPECIFICATIONS

 

Supply 

Voltage 

(1) Li/MnO2 3.0 VDC Battery, 1400 mAH (e.g. Duracell DL123A) 

 

 

 

RF 

Data Protocol 

IEEE 802.15.4-2003/2006 

 

Operating Frequency 

902-928 MHz 

 

Output Power 

+11 dBm 

 

Receiver Sensitivity 

-110 dBm 

 

Open Field Range 

One mile (line of sight) 

 

Data Transmission Interval 

75 seconds (standard), 300 seconds (option) 

 

 

 

Temperature 

 Accuracy 

± 1

°

 

Sensor Operating Range 

32 to 104

°

F (0 to 40°C) 

 

 

 

Humidity 

 Accuracy 

±3% RH 

 

Sensor Operating Range 

10 to 90% RH 

 

 

 

Features 

User Interface 

External Link Button (optional) 

 

 

 

 

 

 

Enclosure 

Material 

ABS (standard and ruggedized) 

 

Rating

 

UL 94 HB (standard), UL 94 5VA (ruggedized) 

 

 

 

Environment 

Operating Temperature 

32 to 104F (0 to 40°C) standard  
32 to 140°F (0 to 60

°

C) ruggedized 

 

Operating Humidity 

0 to 95% RH (non-condensing) 

 

 

 

 
 

WARRANTY SPECIFICATION 

The ACI Wireless Series is covered by ACI’s Two (2) Year Limited Warranty, which is located in the front of 
ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s web site: 

www.workaci.com

. 

 

WEEE Directive 

At the end of their useful life the packaging and product should be disposed of via a suitable recycle 
center. Do not dispose of with household waste. Do not burn. 

 

 

 

 

 

 

 

Содержание WH2630AR/P

Страница 1: ...tallation cost while reducing installation labor risks The Series 2000 sensor Data Link LED confirms the data transmission was received by the receiver for fast and reliable positioning of the sensor during installation There is no need for special wireless installation equipment or tool Together with the ACI Series 2000 receivers and controllers the ACI wireless sensors can be used with any LON B...

Страница 2: ...location to allow exposure to the average zone temperature using two 8 screws Velcro or double sided tape Locate and record the sensor ID numbers located on a label inside the unit prior to mounting Do not mount the sensors on an outside wall on a wall containing water pipes or near air ducts Avoid locations that are exposed to discharge air from registers or radiation from lights appliances or th...

Страница 3: ...midity Accuracy 3 RH Sensor Operating Range 10 to 90 RH Features User Interface External Link Button optional Enclosure Material ABS standard and ruggedized Rating UL 94 HB standard UL 94 5VA ruggedized Environment Operating Temperature 32 to 104F 0 to 40 C standard 32 to 140 F 0 to 60 C ruggedized Operating Humidity 0 to 95 RH non condensing WARRANTY SPECIFICATION The ACI Wireless Series is cover...

Страница 4: ...AUTOMATION COMPONENTS INC Version 4 0 2305 Pleasant View Road I0000685 Middleton Wisconsin 53562 Page 4 of 4 www workaci com 888 967 5224 WH2630ARP WH2630BRP WT2630AR P External Link Button Top View ...

Отзывы: