Installation and Operation Instructions 

                                                                                      

WH2630AR/P, WT2630AR/P,   

& BR/P Wireless  

                                                        Humidity and Temperature Wall Sensors                                                   

 

 

AUTOMATION COMPONENTS, INC                                                                                                                                             Version : 4.0 
2305 Pleasant View Road                                                                                                                                                                          I0000685   
Middleton, Wisconsin 53562                                            

Page 1 of 4                                       

www.workaci.com

   (888) 967-5224                                                                                                                                                        

 

 

 

 

 

 
 
 

4.25"

(107.95mm)

2.625"

(66.68mm)

1.26"

(32mm)

1.26"

(32mm)

 

General Description 

The  WH2630  and  WT2630  are  battery  operated  spread  spectrum  wireless  wall  humidity  temperature  sensors 
housed in a rugged enclosure. 

ACI’s mesh network Series 2000 wireless sensors utilize reliable Spread Spectrum Radio technology.  They can 
be  installed  easily  in  minutes  eliminating  hundreds  of  feet  of  wire  and  saving  installation  cost  while  reducing 
installation labor risks. 

The Series 2000 sensor Data-Link LED confirms the data transmission was received by the receiver for fast and 
reliable positioning of the sensor during installation.  

There is no need for special wireless installation equipment 

or tool.

 

Together  with  the  ACI  Series  2000  receivers  and  controllers,  the  ACI  wireless  sensors  can  be  used  with  any 
LON, BacNet, MODbus, or DDC control system or panel. 

The  maximum  radio  transmission  distance  is  dependent  on  the  building  type.    The  maximum  open  air 
transmission  distance  is  one  mile.    In  a  typical  commercial  building  with  steel  I-Beam  construction,  concrete 
floors with reinforcing rod, and metal stud walls, it can be expected that transmissions will penetrate vertically 
through floors and horizontally through 200 to 300 feet of walls, furniture and air. 

 

Содержание WH2630AR/P

Страница 1: ...tallation cost while reducing installation labor risks The Series 2000 sensor Data Link LED confirms the data transmission was received by the receiver for fast and reliable positioning of the sensor during installation There is no need for special wireless installation equipment or tool Together with the ACI Series 2000 receivers and controllers the ACI wireless sensors can be used with any LON B...

Страница 2: ...location to allow exposure to the average zone temperature using two 8 screws Velcro or double sided tape Locate and record the sensor ID numbers located on a label inside the unit prior to mounting Do not mount the sensors on an outside wall on a wall containing water pipes or near air ducts Avoid locations that are exposed to discharge air from registers or radiation from lights appliances or th...

Страница 3: ...midity Accuracy 3 RH Sensor Operating Range 10 to 90 RH Features User Interface External Link Button optional Enclosure Material ABS standard and ruggedized Rating UL 94 HB standard UL 94 5VA ruggedized Environment Operating Temperature 32 to 104F 0 to 40 C standard 32 to 140 F 0 to 60 C ruggedized Operating Humidity 0 to 95 RH non condensing WARRANTY SPECIFICATION The ACI Wireless Series is cover...

Страница 4: ...AUTOMATION COMPONENTS INC Version 4 0 2305 Pleasant View Road I0000685 Middleton Wisconsin 53562 Page 4 of 4 www workaci com 888 967 5224 WH2630ARP WH2630BRP WT2630AR P External Link Button Top View ...

Отзывы: