FIGURE 1: 

ENCLOSURE

DIMENSIONS

VOC-ROOM                                                                                                                   

Installation & Operation Instructions

Phone:

 1-888-967-5224

Website:

 workaci.com

GENERAL INFORMATION

VOCs are emitted as gases from certain solids or 
liquids, such as building materials and furnishings, 
office equipment, cleaners and disinfectants, etc. 
These types of contaminants directly affect indoor air 
quality and occupant comfort. Measuring and 
communicating VOC levels back to the BAS will help 
users adjust ventilation to maintain proper IAQ 
levels. These units utilize a high-performance metal 
oxide sensor and will output TVOC levels in a range 
from 0-1000 ppb. All units come equipped with both 
analog and RS485 Modbus RTU outputs easily 
interface into existing BAS systems. 

IMPORTANT PRECAUTIONS

Read the following instructions carefully before 

using the indoor air quality sensor described in 

this document to avoid erroneous readings and 

to prevent the device from permanent damage.

•  The sensor must not be exposed to high 

concentrations of organic solvents, 

ammonia, silicone vapour or cigarette-smoke 

in order to avoid poisoning the sensitive 

layer.

MOUNTING INSTRUCTIONS

For optimal temperature readings, follow these 

tips:  

Do not install on external walls. 

Avoid air registers, diffusers, vents, and windows 

Avoid confined areas such as shelves, closed cabinets, 

closets, and behind curtains.

Eliminate and seal all wall and conduit penetrations. 

Air migration from wall cavities may alter 
temperature readings. 

Do not install near heat sources. eg: lamps, radiators, 

direct sunlight, copiers, chimney walls, walls 
concealing hot-water pipes

FIGURE 2: 

OPENING COVER

Separate the cover from the base by inserting a 
flat head screwdriver into the top slot marked 
“OPEN”. Pry the cover forward. 

Attach the base directly to the wall or to a 
standard 2” x 4” junction box using (2) #6-32 x 1” 
screws. 

3.268"

(82.00 mm)

1.205"

(30.60 mm)

4.79"

(121.55 mm)

.984"

(25.00 mm)

Version: 2.0

I0000939

Содержание VOC-ROOM

Страница 1: ...using the indoor air quality sensor described in this document to avoid erroneous readings and to prevent the device from permanent damage The sensor must not be exposed to high concentrations of org...

Страница 2: ...transformer IF THE 24 VDC OR 24VAC POWER IS SHARED WITH DEVICES THAT HAVE COILS SUCH AS RELAYS SOLENOIDS OR OTHER INDUCTORS EACH COIL MUST HAVE AN MOV DC AC TRANSORB TRANSIENT VOLTAGE SUPPRESSOR ACI...

Страница 3: ...evice in a chain have a termination resistor This is controlled using the J8 switch as shown in FIGURE 7 When the jumper is set to ON Enabled a 120 Ohm resistance is added in parallel to the data line...

Страница 4: ...r and the devices giving the information are Modbus Slaves The Modbus sensors are slave devices and the number of Data Bits needs to be the same as in the Master device configuration ACI s Modbus RTU...

Страница 5: ...d Function register Control setting point 1 Control setting point 2 Control setting point 3 Return difference Range for LED color to change Baud rate Parity Remarks Product code equivalent CO2 value U...

Страница 6: ...4 20mA Default 0 10VDC 4 20 mA 500 Ohms maximum 0 10VDC 2K Ohms Minimum N O rated 3A 30VDC 3A 250VAC 230ppb 5 seconds 15 minutes Modbus RTU EIA RS 485 1 247 4800 or 9600 None Even Odd 1 8 ScrewTermin...

Страница 7: ...Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 7 Version 2 0 I0000939...

Страница 8: ...c 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 8 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci c...

Отзывы: