MOUNTING
(Continued)
Now fasten and insert (2) screws #8 x 3/4" TEK
(provided and recommended) through the
mounting holes in the flange and tighten until
the unit is held firmly to the duct. Make sure the
foam pad is tight to the duct to eliminate any
possible air leaks. Refer to the
Wiring Instruc-
tions
(p. 2-3) to make necessary connections.
Note:
All enclosures have the foam pad attached.
For the “DO” (no enclosure), the foam pad is
included, but not installed. The foam pad must be
installed prior to mounting.
0.375"
(9.525 mm)
FIGURE 3:
MOUNTING FOR DIFFERENT CONFIGURATIONS
FIGURE 2:
DUCT MOUNTING
-PB
-GD
-BB
-4X
-DO
1.51"
(38.25 mm)
1.59"
(40.39 mm)
1.54"
(39.12 mm)
1.54"
(39.12 mm)
3.01"
(76.51 mm)
3.18"
(80.77 mm)
3.08"
(78.23 mm)
3.08"
(78.23 mm)
1.54"
(39.12 mm)
3.08"
(78.23 mm)
WIRING INSTRUCTIONS
Open the cover of the enclosure. ACI recommends 16 to 26 AWG twisted pair wires or shielded cable for all
sensors. Signal wiring must be run separate from low and high voltage wires (24/120/230VAC). All ACI thermis-
tors and RTD temperature sensors are both non-polarity and non-position sensitive. All thermistor type units
are supplied with (2) flying lead wires, and all RTD’s are supplied with (2) or (3) flying lead wires – see
FIGURE
4
(below). The number of wires needed depends on the application.
THERMISTOR OR
RTD 2WIRE
WIRE NUT
RTD 3WIRE
SAME COLOR WIRES
WIRE NUT
WIRING FROM CONTROLLER
ANALOG INPUT
WIRING FROM CONTROLLER
ANALOG INPUT
3-WIRE RTD WIRING
2-WIRE THERMISTOR or RTD WIRING
FIGURE 4:
TEMPERATURE WIRING