background image

AUTOMATION COMPONENTS, INC                                                                                                                                                                       Version : 4.0 

2305 Pleasant View Road                                                                                     Page 3 of 4                                                                                    I0000475     
Middleton, Wisconsin 53562 (888) 967-5224 

                                                                                                                                  

www.workaci.com

                                                                                                                                                

 
 
 
 
 

CHECKOUT 

Version identification:

  Most DRN3.1’s are shipped as version #1.  An IC chip on the DRN3.1 is labeled with the 

version program number.  Make sure you have the correct version.  You may have to remove the resistor network 
card to view and compare to table on page 1. 

 

Resistor network: 

 Each DRN3.1 requires a plug-in resistor network card (RN) to operate properly.  This resistance 

card determines the simulated slide wire potentiometer values for the output.  Insert the RN (usually in a separate 
package from DRN3.1) into the DRN3.1.  The HW3 pin on the Resistor Network card should be oriented towards the 
top as shown on Page 1. There are two rows of pins on the RN and two rows of female connections on the DRN3.1.   
The DRN3.1 resistance output simulates a potentiometer.  The Terminal Block located on the far right is the Wiper. 
The Terminal Block located in the middle is the Maximum; the high end of the potentiometer. The Terminal Block 
located on the far left is the Minimum; the low end of the potentiometer. Upon power-up, the wiper will start at the 
Minimum position and will remain there until the first PULSE or FLOATING POINT signal is received.  The ANALOG 
version will begin tracking the input signal instantly after “sampling” the input signal to eliminate error.  The output 
resistance will not change on the PULSE version until the end of the pulse.  To check the resistance output, vary the 
input signal and measure the resistance.  The resistance between terminals Wiper and Minimum will increase as the 
input signal increases and the resistance between Wiper and Maximum will decrease.  If both floating point inputs are 
on for 3 seconds, the DRN3.1 resets to minimum resistance output. 

Setting the jumpers:

  Remove power from the DRN3.1.  Place jumpers S1 through S6 in the appropriate positions.  

All six jumpers must be in proper position for each input type.  Hold the DRN3.1 vertical with the label at top right to 
orient its jumper shunts with the chart.  Version #1 and Version #2 share the same analog inputs.  Ramping time for 
floating point inputs are selectable.  Version #4 accepts a continuous pulse signal command string within a 10 second 
window.  No pulse in this 10 second window produces minimum percent output.  A ten second pulse in this 10 
second window produces 100% output.  Continuous pulse will produce maximum percent output. 
When power is restored, changes will be recognized.  Apply 24 VAC/VDC to “PWR” terminal, confirm power light is 
on and measure voltage to confirm proper voltage. 
When power is applied to terminals “+24V” and “-“, the POWER LED will light and the Fail Safe terminals will be 
disconnected from the output terminals.  Fail-back only occurs when the DRN3.1 has lost power.  When the DRN3.1 
is not powered on terminals “24V” and “-“, the Fail Safe terminals are connected to the Output terminals.  Check for 
continuity. 
The DRN3.1 will automatically fail-back to 0 Ohms.  For a fail-back to some other resistance, a manual potentiometer 
or fixed resistor can be added between Minimum and Wiper only, if out putting a normal acting signal.  If out putting a 
reverse acting signal, please contact ACI for assistance. 

 

TESTING THE INPUT: 

 

Voltage input:

  Connect the “+” or positive wire to “V/I+”.  Connect the common to “24V-“.  Apply a voltage from 

control source.  Measure voltage at “24V-“ and “V/I+” at terminal block. 
If the commanded voltage is not present, remove the “+” or positive wire and measure from “+” wire to   “24V-“.  If no 
voltage is measured check the wiring from controller.  If voltage disappears or is reduced when connected to the 
DRN3.1, confirm input jumper is set to voltage mode and remove signal input wires and power from unit.  Measure 
the resistance from “24V-“ to “V/I+”.  Resistance in the voltage modes will be around 10K.  If input is shorted, contact 
ACI Technical Support.  If not shorted, remove the controller input common and connect 24 VDC/VAC to the DRN3.1.  
Check for ground loop:  Place meter in voltage mode and measure VAC and VDC from analog input common wire to 
power supply common.  If any voltage is measured in DC or AC a ground loop most likely exists.  Check power 
commons and / or ground potentials.   Use a separate 24 volt transformer for the DRN3.1 and let common float. 

 

Current input:  

Confirm the input jumper is in the correct position.  Measured input resistance should be around 250 

Ohms.  Connect “+” or positive to “V/I+” and common or “-“ to “24V-“.  Apply mA signal.  Place meter in voltage and 
measure voltage across “V/I+” and “24V-“ 4 mA is equal to 1 volt and 20 mA is equal to 5 volts.  Use Ohms Law to 
find voltage from current.  (Current x 250 = Volts. Sample: 12 mA or 0.012 x 250 = 3 volts).  If no voltage is present, 
check wiring for open.  Current cannot exist without voltage present from “V/I+” to “24V-“ unless dead shorted. 
 

Pulse Width Modulated (or PWM) input:

  Apply 24 VAC/VDC to the PWR terminals.  Connect your meter to the 

Wiper and Maximum terminals on the output terminal block.  Set meter to resistance range of resistor network.  
Connect a jumper wire from UP to the 24V “+” terminal (this is your jumper wire #1).  Connect another jumper wire 
into the 24V “-“ terminal only (this is your jumper wire #2).  You are now ready to simulate a timed pulse signal.  For 
testing purposes, select 0.1 to 25.5 or 0.1 to 10 seconds on version 2.  Be sure to reset power to allow the DRN3.1 to 
recognize new settings.  Take the free end of jumper wire #2 and connect by holding wire to the COM terminal.  
Reference Figure #2.  Count to 50% of timing range and remove.  Verify the pulse UP LED indication.  Voltage can 
be measured across the input to verify proper voltages.  Read the output.  Has the output changed?  The output 
should be close to 50% of set output.  If no, contact ACI Technical Support.  If yes, unit is functioning properly. 

 

Отзывы: