PRODUCT SPECIFICATIONS

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 4

Version: 4.0

I0000744

WARRANTY

The A/CO2-DUCT Series is covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of ACI’S 
SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.

24 VAC +/-20%, 50/60 Hz (half-wave rectifier)  |  16.5-40 VDC Max.

3 VA for 24 VAC, 3W for 24 VDC (peak); <0.9W (average)

Single beam infrared sensing technology (NDIR)

Diffusion

0 to 2,000 ppm  

Up to 10,000 ppm (factory set)

+/- 30 ppm and +/- 5% of reading

Output 1:

 0-5 VDC or 0-10 VDC (Default)  |  

Output 2:

 4-20 mA (500 Ohm Load maximum)

Polarity protected

+/-  40 ppm +/- 3% of reading (@ 15-35°C; 20-70% RH and 101.3 kPa)

+ 1.6% reading per kPa (deviation from standard pressure 101.3 kPa)

≤ 2 minutes, diffusion 

< 1 minute (@ full specs < 15 minutes)

Various (see ordering grid)

+/- 1°F (+/- 0.6ºC)

32 to 122ºF (0 to 50ºC)

0 to 95%, non-condensing

Duct Box:

 PC & ABS blend, Flammability Rating UL94V-0

Cover:

 Makrolon® 6555 plastic, Flammability Rating UL94V-0

Pipe: 

PC & ABS blend, Flammability Rating UL94V-0

7,500 sq. ft maximum

4-6 ft

> 15 years (typical)

ABC algorithm (Automatic Baseline Correction)

NON-SPECIFIC INFORMATION

 

Supply Voltage:

Power Consumption:

Sensing Technology:

Sensing Method:

Measurement Range Default:

Extended CO2 Ranges:

Extended Range Accuracy:

CO2 Output Signal:

Fail Safe:

CO2 Accuracy :

Pressure Dependence:

Response Time:

Warm-Up Time:

Temperature Output Range:

Temperature Accuracy:

Operating Temperature Range:

Operating Humidity Range:

Enclosure:

Sensor Coverage Area:

Mounting Height:

Sensor Life :

Calibration 

Note :

 Accuracy is defired after minimum three (3) ABC periods (1 period = 8 days) of continous operations  |  

Note : 

In normal indoor air 

quality (IAQ) applications  |  Corrosive environments are excluded  |  

Note : 

Building CO2 levels must drop to 400 ppm same time during the 

week for ABC to work properly  |  If the building is occupied 24 hours / day, ABC must be turned off

Содержание Carbon Dioxide Duct Series

Страница 1: ...healthier indoor climate MOUNTING INSTRUCTIONS Since there might be a substantial pressure difference in duct mounting applications it is essential to avoid ambient air from suction into the duct mounting box For correct function it is indispensable that the sealing of the box cover the cable entry bushings the cable feed through and the duct entrance are absolutely tight The duct entrance may nee...

Страница 2: ...sted class 2 transformer when powering the unit with 24 VAC Failure to wire the devices with the correct polarity when sharing transformers may result in damage to any device powered by the shared transformer If the 24 VDC or 24VAC power is shared with devices that have coils such as relays solenoids or other inductors each coil must have an MOV DC AC Transorb Transient Voltage Suppressor ACI Part...

Страница 3: ...event any chance of shorting DIP SWITCH CONFIGURATION SW 1 sets the Output Signal SW2 controls the ABC Logic The default setting is 0 10 VDC output switch 1 on and ABC on switch 2 on For 0 5 VDC output set switch 1 to off The 4 20 mA output can be used with switch 1 in the on or off position ABC stands for automatic baseline correction a self calibration function for achieving maintenance free gas...

Страница 4: ...grid 1 F 0 6ºC 32 to 122ºF 0 to 50ºC 0 to 95 non condensing Duct Box PC ABS blend Flammability Rating UL94V 0 Cover Makrolon 6555 plastic Flammability Rating UL94V 0 Pipe PC ABS blend Flammability Rating UL94V 0 7 500 sq ft maximum 4 6 ft 15 years typical ABC algorithm Automatic Baseline Correction NON SPECIFIC INFORMATION Supply Voltage Power Consumption Sensing Technology Sensing Method Measurem...

Отзывы: