For applications in which the normal operating current is greater than 150 Amps or for conductor diameters larger than 0.530” 
(1.35 cm) in diameter, an external 5 Amp Current Transformer must be used as shown in 

Figure 4 below

.   

Remember that the secondary of the 5A CT must be shorted together before the power may be turned onto the monitored 
device.

 

 

In

su

la

te

d

Example: For currents up to 600 Amps
                (and not below 70 Amps (A/MCS-A)
                or 95 Amps (A/MSCS-A), where
                Current Transformer (C.T.)
                secondary falls below 1 Amp
                use a 600:5 ratio C.T. as shown:

Nut

Co

nd

uc

to

r

600:5 Ratio 5A C.T.

Wire

 

Figure 4: Current Transformer 

 

 Wiring 

ACI recommends the use of a two conductor 16 to 22 AWG shielded cable or twisted pair 

copper wire only

 for all current switch 

applications.  A maximum wire length of less than 30 meters (98.4 feet) should be used between the A/MCS and A/MSCS current 
switches and the Building Management System or controller.  

Note:

  

When using a shielded cable, be sure to connect only (1) 

end of the shield to ground at the controller.  Connecting both ends of the shield to ground may cause a ground loop.

  When 

removing the shield from the sensor end, make sure to properly trim the shield so as to prevent any chance of shorting. The current 
switch output terminals represent a solid-state switch for controlling both AC and DC loads and is not polarity sensitive.  The 
recommended torque to be used on the terminal block connections is 0.67 Nm or 5.93 in-lbs..  The aperture (hole) size of the 
current switch is 0.53” (1.35 cm) and will accept a 1 AWG maximum wire diameter. 

 Operating Specifications 

 

See 

Figure 5

 and 

Figure 6

 for two different current switch applications using your Building Management System (DDC/PLC 

Controller).  

Figure 5

 is showing the use of the Go/No Go Current Switch as a Digital Input to your DDC Controller, whereas 

Figure 6

 is showing you how to use the Go/No/Go Current Switch in conjunction with your building management system to  

control a fan or pump for example.

   

 

 

Building Management

Digital Input #1

System

(Relay Coil or

120 VAC

Line

Transformer

24 VAC

Contactor)

24 VAC Coil

Relay / Contactor

DI

DO

(Status)

DDC Controller

 

                             Figure 5: Digital Circuit                                                                         Figure 6: Analog Circuit 

 

ACI Model # 

Fixed Trip Point 

Output Switch Rating 

Max. Sensing 

Current Voltage 

Max. Continuous 

Current  

Max. Current for  

6 seconds 

Max. Current for  

1 second 

A/MCS 

0.20 Amps 

0.50 Amp @ 36 VAC/VDC 

600 VAC 

158 Amps 

240 Amps 

600 Amps 

A/MSCS 

0.55 Amps 

0.50 Amp @ 36 VAC/VDC 

600 VAC 

158 Amps 

240 Amps

 

600 Amps 