PRODUCT SPECIFICATIONS

AC Current

600 VAC 

50/60 kHz

Solid-Core and Split-Core Versions available (See Ordering Grid)

Induced from the Monitored Conductor (Insulated Conductors only)

See Ordering Grid

2200 VAC

Adjustable Trip Point  |  See Ordering Grid  

10% Trip Point, typical

Normally-Open “N/O” 

1A Continuous @ 36 VAC/VDC

< 0.5 Ohms  (tripped)  |  > 1 Meg Ohms  (Open)

A/MCS-A:

 < 90 mS typical  |  

A/MSCS-A:

 < 45 mS typical

Red LED (Current above trip point) | Blue LED (Current below trip point)

0.53” (13.46 mm)

-22 to 140ºF (-30 to 60ºC)

0 to 95%, non-condensing

2 Position Screw Terminal Block (Not Polarity Sensitive)

16 to 22 AWG (1.31 mm2 to 0.33 mm2) Copper Wires only

4.43 to 5.31 in-lbs. (0.5 to 0.6 Nm)

1” (2.6 cm) between current switch (Relays, Contactors, Transformers)

SENSOR NON-SPECIFIC INFORMATION

Monitored Current Type:
Maximum AC Voltage:
Operating Frequency Range:
Core Style:
Sensor Power:
Amperage Range:
Isolation Voltage:
Trip Point Style  |  Trip Point:
Hysteresis:
Contact Type:
Contact Rating:
Contact “On” Resistance  |  “Off” Resistance:
Response Time:
Status LED Indication:
Aperture Size:
Operating Temperature Range:
Operating Humidity Range:
Wiring Connections:
Wire Size:
Terminal Block Torque Rating:
Minimum Mounting Distance¹:

STANDARD ORDERING

Model #
A/MCS-A
A/MSCS-A

Item #

117854

117855

Trip Point Type

Adjustable

Adjustable

N/O

Solid-Core

Split-Core

Amp Range

0.32 to 150A

0.70 to 150A

Amp Range

0.32 to 150A

0.70 to 150A

Contact Rating

1A @ 36 VAC/VDC

1A @ 36 VAC/VDC

Note¹: 

The LED should not be used to determine if current is present. At low currents the LED may not be visible.

Содержание A/MCS-A

Страница 1: ...our equipment where you want to know when your piece of equipment runs and for how long it runs when logging the contact closures on your building management system or PLC MOUNTING INSTRUCTIONS Make sure that all installations are in compliance with all national and local electrical codes Only qualified individuals that are familiar with codes standards and proper safety procedures for high voltag...

Страница 2: ...e sensor end make sure to properly trim the shield so as to prevent any chance of shorting The current switch output terminals represent a solid state switch for controlling both AC and DC loads and is not polarity sensitive The recommended torque to be used on the terminal block connections is 0 67 Nm or 5 93 in lbs The aperture hole size of the current switch is 0 53 1 35 cm and will accept a 1 ...

Страница 3: ...up to 600 Amps and not below 70 Amps A MCS A or 95 Amps A MSCS A where Current Transformer C T secondary falls below 1 Amp use a 600 5 ratio C T as shown in Figure 4 RELAY MOTOR EXHAUST FAN ACI SPLIT CORE SWITCH NEUTRAL 120 VOLT HOT 120 VOLT HOT NEUTRAL 24 VAC HOT NEUTRAL MOTOR RANGE HOOD FAN APPLICATION EXAMPLES See Figure 5 p 3 and Figure 6 p 3 for two different current switch applications Figur...

Страница 4: ...after initial power up this means that you will need to slowly adjust the potentiometer counter clockwise until the Blue LED turns on and then slowly adjust the potentiometer clockwise until the Red LED just turns on and stop immediately The adjustable current switch is now tripped Now verify the output with an Ohmmeter to verify that the contacts of the switch are approximately 0 200 Ohms The adj...

Страница 5: ...mm2 to 0 33 mm2 Copper Wires only 4 43 to 5 31 in lbs 0 5 to 0 6 Nm 1 2 6 cm between current switch Relays Contactors Transformers SENSOR NON SPECIFIC INFORMATION Monitored Current Type Maximum AC Voltage Operating Frequency Range Core Style Sensor Power Amperage Range Isolation Voltage Trip Point Style Trip Point Hysteresis Contact Type Contact Rating Contact On Resistance Off Resistance Response...

Страница 6: ...Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 6 Version 6 0 I0000558 NOTES ...

Страница 7: ...Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 7 Version 6 0 I0000558 NOTES ...

Страница 8: ...nc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 8 Version 6 0 I0000558 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com ...

Отзывы: