Содержание A/ACS2

Страница 1: ...s should be installed on the line side of the power to the electrical equipment The current switches are available in both solid and split core versions which also includes a Patented 35 mm Din Rail mounting foot for easy installation in panel mount applications The adjustable current switches can be used to determine the run time of your equipment as well as basic load trending applications where...

Страница 2: ...s shown in Figure2 Press down firmly on the cover to close the current switch An audible click will be heard as the tab slides over the tongue on the base CAUTION Mating surfaces of the magnetic core are exposed when the sensor is open Electrical contact grease present on the cores to prevent corrosion can capture grit and dirt if care is not exercised Operation can be impaired if anything prevent...

Страница 3: ...ds the use of a two conductor 16 to 22 AWG shielded cable or twisted pair copper wire only for all current switch applications A maximum wire length of less than 30 meters 98 4 feet should be used between the current switch and the Building Management System or controller Note When using a shielded cable be sure to connect only 1 end of the shield to ground at the controller Connecting both ends o...

Страница 4: ...o No Go Current switches are only rated at 0 2A 200 VAC VDC and must use an additional Contactor if controlling motor fans CALIBRATION OF ADJUSTABLETRIP POINT The adjustable current switch has an operating range of 0 250 Amps Do not exceed The current switch has an adjustable trip point range of 0 50 220 Amps 1 50 220 Amps or 0 60 180 Amps depending on the model See Ordering Table on p 5 to determ...

Страница 5: ...ion Screw Terminal Block Not Polarity Sensitive 16 to 22 AWG 1 31 mm2 to 0 33 mm2 Copper Wires only 4 43 to 5 31 in lbs 0 5 to 0 6 Nm 1 2 6 cm between current switch Relays Contactors Transformers SENSOR NON SPECIFIC INFORMATION Monitored Current Type Maximum AC Voltage Operating Frequency Range Core Style Sensor Power Amperage Range Isolation Voltage Trip Point Style Trip Point Contact Type Statu...

Страница 6: ...NOTES Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 6 Version 10 0 I0000788 ...

Страница 7: ...NOTES Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 7 Version 10 0 I0000788 ...

Страница 8: ...nc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 8 Version 10 0 I0000788 ...