Fig.6—Typical wiring hookup using L6006 and
L6007 with L8148A.
Check
out
Check to make certain that the Aquastat
®
Controller is
installed and adjusted properly. Put the system into operation
and observe the action of the device through several cycles to
make certain that it provides proper low and/or ligh limit and
circulator control.
L1
(HOT)
L2
1
1
2
2
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
SELECT MODELS HAVE 1/4 IN. TAB TERMINAL FOR W OR B1
TERMINAL.
L6006, L6007
CIRCULATOR AND
LOW LIMIT
CONTROL
L1
L2
3
T
T
R
W
B
B
R
C1
C2
B1
B2
SERIES 80
THERMOSTAT
L8148A
CIRCULATOR
PILOTSTAT
®
LINE VOLTAGE
GAS CONTROL
OIL BURNER RELAY
LINE VOLTAGE
TERMINALS
1
1
2
2
12
M8779
LOW VOLTAGE
LINE VOLTAGE
3
95-5973—3
Adjustment
Set the differential to correspond with the boiler
manufacturer recommendations. To adjust models with
adjustable differential, rotate the wheel on the back of the
snap switch until the desired reading is aligned with the
V
notch in the frame. The wheel provides an adjustment from
5
°
F to 30
°
F (3
°
C to 17
°
C). Replace the cover on the Aquastat
®
Controller.
Adjust control point to correspond with the boiler manu-
facturer recommendations. To adjust, insert a screwdriver in
the slotted screw type head located beneath the window in
the cover. Turn the scale to the desired control point.
Fig. 3—Direct immersion model with bulb
compression fitting partially removed.
M8774
SENSING BULB
BULB COMPRESSION
FITTING
SEALING WASHER
ADAPTER CLAMPS
FIT OVER
GROOVE
SPLIT SLEEVE
ADAPTER
CLAMP
Fig. 4—Mounting L6006C on pipe or tank.
M8771
ENCLOSED
SENSING BULB
PIPE
ADJUSTABLE
PIPE STRAP
AQUASTAT
®
CONTROLLER
CASE
Fig. 5—Typical wiring hookup using the L6006
or L6007 for low limit and circulator control in
oil-fired hydronic system.
L1
(HOT)
L2
1
2
3
1
2
3
PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
R-B OPENS, R-W CLOSES ON TEMPERATURE RISE.
SELECT MODELS HAVE 1/4 IN. TAB TERMINAL FOR
W TERMINAL.
M8778
PROTECTORELAY™
CONTROL
HIGH LIMIT
L6006 OR L6007
CIRCULATOR
AND LOW
LIMIT CONTROL
W
R
B
1
2
4
3
T
T
IGNITION
BURNER
MOTOR
24V
THERMOSTAT
SWITCHING RELAY
CIRCULATOR
LINE VOLTAGE
LOW VOLTAGE