T-ABVA Manual |Rev.C, JULY 2017                                                                                                Page 7 

Pre-Calibration 

 

Mute Button

 

The Mute Button has three functions, which are selected based on the time duration the button is held. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Calibration Button

 

To prevent accidental contact, the Calibration Button is located below the hole in the front lower right 
corner of the ABVA.  In order to press the Calibration Button, simply straighten the end of a small paper 
clip and insert straight into the hole. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Calibration Modes 

The ABVA has two different modes for calibrating the alarm set point.  Mode 1 calibrates the alarm set 
point to the velocity at which the fume hood is presently operating and Mode 2 calibrates the alarm set 
point to 20% less than the operating velocity.  

NOTE: Mode 2 was added in April 2008.  Units sold 

prior to April 2008 include Mode 1 only.  (

Serial #’s > 1500 have MODE 1 & 2) 

 
Mode 1 should be used if the desired alarm set point can be achieved by either modulating the exhaust 
flow or by positioning the fume hood sash.  Mode 2 should be used if the desired alarm set point can not 
be achieved and is 20% less than operating velocity.  Two examples are provided below for selecting 
which Mode is suited best for your application.  

Example 1: 

Desired Alarm Set Point:  80 FPM 
Fume Hood Type:  Constant Exhaust Volume 
Face Velocity Range:  When Sash is 100% Open the Face Velocity is measured at 80 FP. 
Calibration Mode:  Select Mode 1; because the desired alarm set point can be achieved by opening the sash 100%. 

Example 2: 

Desired Alarm Set Point:  80 FPM 
Fume Hood Type:  Variable Exhaust Volume 
Face Velocity Range:  Face Velocity is controlled to 100 FPM, regardless of sash position. 
Calibration Mode:  Select Mode 2; because the desired alarm set point is 20% less than the operating velocity. 

 

Calibration Button 

 
Pressing and releasing; 

toggles calibration modes. 

 
Pressing and holding for 5 seconds

; initiates alarm calibration. 

 
Pressing and holding for 10 seconds;

 zeros the sensor. 

Note: The sensor should not need to be re-zeroed unless directed to do 
so by the factory.  Re-zero should only be performed with the airflow 
sensor blocked. 

 

 

 

Mute Button 

 
Pressing and releasing once; 

during alarm condition will silence the 

horn.  Pressing again reactivates the alarm horn. 

 
Pressing and holding for 3 seconds

; provides visual indication of the 

present calibration mode.  One LED ON = Mode 1, Two LEDs ON = 
Mode 2. 

 
Pressing and holding for 15 seconds;

 disables the horn with no re-

beep.  The horn will remain off until Mute is held again for 15 seconds.

 

 

 

 

Содержание T-ABVA

Страница 1: ...i Installation Operation Maintenance Manual Apex Basic Velocity Alarm Model T ABVA Manual 0133MAN00018 Accutrol LLC 21 Commerce Dr Danbury CT 06810 Tel 203 445 9991 www accutrolllc com ...

Страница 2: ...ginal warranty period has expired Unless specifically authorized by Accutrol LLC in writing no warranty is made with respect to and no liability is assumed in connection with any goods which are incorporated into other products or equipment by the Buyer The foregoing is in lieu of all other warranties and is subject to the conditions and limitations stated herein No other expressed or implied warr...

Страница 3: ...f Contents WARRANTY II TABLE OF CONTENTS III INTRODUCTION 1 GENERAL DESCRIPTION 2 SPECIFICATIONS 3 MODEL CODE DESCRIPTION 4 GETTING STARTED UNPACKING 4 INSTALLATION 5 PRE CALIBRATION 7 CALIBRATION 8 MAINTENANCE 9 ...

Страница 4: ...T ABVA Manual Rev C JULY 2017 Page iv This Page Intentionally Blank ...

Страница 5: ...tory fume hoods The following items are identified by ASHRAE as being important factors contributing to the safe operation of laboratory fume hoods 1 Cross drafts Air currents may by creating turbulent air pockets draw contaminants from the hood Such cross drafts could be caused by air supply diffusers or grilles open windows or doors or rapid movements of people in front of the hood 2 Work proced...

Страница 6: ...FF until the Mute Button is pressed again or the alarm condition clears 5 Calibration Button The calibration button is recessed to prevent accidental triggering To press the calibration button use the end of a paper clip Pressing the Calibration Button momentarily will toggle the alarm calibration mode Pressing and holding the Calibration Button for 5 seconds will initiate the Alarm Calibration Pr...

Страница 7: ... Mute is activated Re Beep Mode single fast tone every 5 minutes when horn muted and alarm not cleared ALARM DELAY 7 seconds to reduce false alarms ALARM RELAY OUTPUT I O Terminal Positions 3 4 and 5 Type SPDT relay Specifications 1A 30 VDC 0 5A 125 VAC resistive load Operation NORMAL Power ON ALARM Fault or Power Loss Relay Contact Term 3 4 OPEN CLOSED Relay Contact Term 5 4 CLOSED OPEN REMOTE MU...

Страница 8: ... wide FH2P Dual Hood Probe Kit for fume hoods 8 feet wide and greater BS1P Probe Kit for BSC Duct Optional Items Sold Separately 1025CAB00066 6 Foot Extension Cable for Power Supply T ABVA SMKIT Side Mount Kit Getting Started Unpacking Before proceeding unpack box and verify all components arrived safely through shipping Item Qty Description 1 1 Velocity Alarm Main Unit 2 1 Wall Pluggable Power Mo...

Страница 9: ...y a Using the hardware and instruction sheet provided with the side mount kit Accutrol LLC PN T ABVA SMKIT install the bracket to the side panel of the device being monitored b Install the plastic electrical box provided to the side mount bracket using the hardware provided c Install the ABVA to the plastic electrical box however do not secure until Steps 3 through 7 have been completed With the f...

Страница 10: ...he back side of the ABVA Step 8 Secure the ABVA Secure the ABVA to the mounting surface using the appropriate two screws provided Drilled Hole Inside of Fume Hood Step 3 Locate the Hood Probe Due to the wide variety of fume hoods and configurations available there is no single hood probe location that will work for all fume hoods Contact the fume hood manufacturer to obtain the optimum side wall p...

Страница 11: ...which Mode is suited best for your application Example 1 Desired Alarm Set Point 80 FPM Fume Hood Type Constant Exhaust Volume Face Velocity Range When Sash is 100 Open the Face Velocity is measured at 80 FP Calibration Mode Select Mode 1 because the desired alarm set point can be achieved by opening the sash 100 Example 2 Desired Alarm Set Point 80 FPM Fume Hood Type Variable Exhaust Volume Face ...

Страница 12: ...h to provide the desired velocity for the alarm set point c Using a calibrated velocity meter measure the average airflow velocity using appropriate ANSI ASHRAE method If the measured velocity is within the desired alarm set point then proceed to Step d If not then adjust exhaust flow or fume hood sash and repeat Step c until the desired velocity is achieved d To calibrate the alarm set point pres...

Страница 13: ...ll now hear a series of short fast beeps while the microprocessor is acquiring data from the sensor After about 5 seconds the buzzer will provide one longer beep to signify calibration set point has been stored e Verify the alarm set point is calibrated properly by modulating the exhaust volume or moving the fume hood sash to achieve the desired alarm set point After calibration is verified you ma...

Страница 14: ...T ABVA Manual Rev C JULY 2017 Page 10 Notes ...

Страница 15: ...Revision History ECN New Rev New File Name 2260 C T ABVA Rev C February 2017 TOC Updated company physical address to the front and back cover pages ...

Страница 16: ...Proudly made in the USA 21 Commerce Dr Danbury CT 06810 Tel 203 445 9991 www accutrolllc com ...

Отзывы: