SECTION 2 - SPECIFICATIONS 

PERFORMANCE 

 

Accuracy  +/- 5% of reading or 5 CFM, whichever is greater 

Speed of Response  < 1 second control signal response (full stroke cycle time based on actuator type) 

Shut-off Leakage Rate  Standard: < 1.5% FS @ max operating pressure 

“S” Option: 

< 0.5% FS round valves, < 1% FS rectangular valves @ max operating pressure 

Max Operating Pressure 

3”w

c Differential Pressure Across Valve 

Min Operating Pressure  Reference Section 2.1 

Airflow Range  Reference Section 2.1 

Failure Mode  Open, Closed or Last Position (based on actuator type selection) 

ENVIRONMENTAL 

 

Temperature  Airstream: -20 to 165 deg. F for all Standard Valve Models 

                    -20 to 375 deg. F for the High Temp SS Valve Models 
Ambient:   -20 to 125 deg. F 
Storage:     -40 to 165 deg. F 

Humidity  0 to 90% non-condensing 

TRANSMITTER ELECTRICAL 

 

Power Supply  24 VAC +/- 20% 50/60 Hz, 4 VA max (8.5 VA max with remote display) 

  24 VDC +/- 10% 1.5 W max (3.5 W max with remote display) 

Output Signal  Software Configurable; 0-20mA, 4-20mA, 0-10V, 2-10V, 0-5V, or 1-5V 

  12-bit Resolution capable of driving 1K-ohm load 

Configuration Port  USB 2.0, Isolated, C Type Connector, Optional Wireless Configuration using Bluetooth Ver 4.2 

Power Source Switch  Operational Position: Draws power from 24V input terminal block 

Nonoperational Position: Draws power from 5V USB port (Use for configuration only)  

BACnet MS/TP 

(Optional)

  EIA 485 2-wire BACnet MS/TP, Galvanically Isolated 
  Data Rates 9600, 19200, 38400, 76800 and 115200 
  1/8 Unit Load Receiver Input Impedance 
  Network bias and EOL Termination not provided within the Transmitter 

AccuNet 

(Optional)

  2-wire Controller Area Network Bus for summing 2 to 20 Accutrol Device Airflows 
  120-ohm EOL network termination resistors are required 
  Reference Appendix C for details 

Remote Display 

Sold Separately

  LCD, 2 lines x 8 characters with white LED backlight 

 

Includes USB Configuration Port and Factory Cable 

Terminal Plugs  3-position, vertical pluggable, screw on top, wire size 12-30 AWG 

EMC 

Safety 

EN 61326-1:2013, 2014/35/EU (LVD), 2014/30/EU (EMC) 
EN 61010-1:2010 

 

FCC Part 15

 

 

This equipment has been tested and found to comply with the limits for a Class A digital 
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable 
protection against harmful interference when the equipment is operated in a commercial 
environment. This equipment generates, uses, and can radiate radio frequency energy and, if 
not installed and used in accordance with the instruction manual, may cause harmful 
interference to radio communications. Operation of this equipment in a residential area is 
likely to cause harmful interference in which case the user will be required to correct the 

interference at the user’s own expense.  This Class A dig

ital apparatus meets all requirements 

of the Canadian Interference-Causing Equipment Regulations. 

 

Units provided with the optional Bluetooth low energy module contain 
FCC ID: XPYNINAB1  IC: 8595A-NINAB1 
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two 
conditions; 

(1)

 

This device may not cause harmful interference, and 

(2)

 

This device must accept any interference received, including interference that may 
cause undesired operation. 

  KCC South Korea compliance certification number MSIP-CRM-ULX-NINA-B111 

 
 

Australia and New Zealand regulatory compliance.  The NINA-B1 modules are compliant with 
AS/NZS 4268:2012?AMDT 1:2013 standard 

 Radio equipment and systems 

 Short range 

devices 

 Limits and methods of standard measurement made by the Australian 

Communications and Media Authority (ACMA) 

ACTUATOR ELECTRICAL 

 

 

Reference Appendix A 

 

 

Содержание AccuValve AVT6000

Страница 1: ...of this Manual are Subject to Change Without Notification Airflow Control Valve Patented U S 6 991 177 7 543 759 Manufactured by Accutrol Representative AVT6000 MANUAL REV B 2020 05 29 ECN 2627 21 Com...

Страница 2: ...ainst defects or damages arising from improper installation where installation is by persons other than Manufacturer against defects in products or components not manufactured by Manufacturer or again...

Страница 3: ...ii TABLE OF CONTENTS iii SECTION 1 INTRODUCTION 4 SECTION 2 SPECIFICATIONS 6 SECTION 3 PHYSICAL DIMENSIONS WEIGHTS 11 SECTION 4 INSTALLATION 12 SECTION 5 WIRING 15 SECTION 6 ACCUVALVE INSIGHT CONFIGUR...

Страница 4: ...ambers it accelerates and compresses creating an ideal condition for measuring airflow velocity The vortex shedding airflow sensors provide a highly repeatable digital pulse train with a frequency tha...

Страница 5: ...ectangular 48 12 h x 48 w Rectangular ACTUATOR 02 Fail Last Position 2 sec full cycle 0 10v PN 20 0008 03 Fail Last Position 2 sec full cycle 2 10v PN 20 0009 04 Fail Open Closed 2 sec full cycle 0 10...

Страница 6: ...Airflows 120 ohm EOL network termination resistors are required Reference Appendix C for details Remote Display Sold Separately LCD 2 lines x 8 characters with white LED backlight Includes USB Configu...

Страница 7: ...Glv Steel PFA Coated 304SS 304LSS Blades 304LSS 316LSS Glv Steel PFA Coated 304SS 304LSS Shafts 316LSS 316LSS 316LSS PFA Coated 316SS 316LSS Shaft Bearings Teflon Teflon Teflon Teflon Teflon Vortex Se...

Страница 8: ...5 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 25 50 75 100 125 150 175 200 225 250 275 300 325 Valve DP wc Max Airflow CFM 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 100 150 200 250 300 350 400 450...

Страница 9: ...CFM 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 300 600 900 1200 1500 1800 2100 2400 2700 Valve DP wc Max Airflow CFM 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 400 800 1200 1600 2000 24...

Страница 10: ...0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 800 1600 2400 3200 4000 4800 5600 6400 Valve DP wc Max Airflow CFM 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 1000 2000 3000 4000 5000 6000 700...

Страница 11: ...H Stainless Steel Aluminum in mm in mm in mm Lbs kg Lbs kg 06 5 88 149 22 559 10 254 13 5 9 9 4 1 08 7 88 200 24 610 13 330 16 7 3 12 5 4 10 9 88 250 24 610 15 381 20 9 1 14 6 4 12 11 88 300 27 686 1...

Страница 12: ...re Also be sure to select a location that will provide a minimum clearance of 14 356mm unobstructed access to the transmitter actuator and valve access cover 3 Provide an opening in the duct section s...

Страница 13: ...ansmitter actuator and access panel 6 Secure both ends of valve to the duct using draw band clamps 2 Slip the discharge end of the valve into the duct engaging valve into duct 1 at each end 1 Slip the...

Страница 14: ...roperly 2 Lift valve into position to provide unobstructed access to the transmitter actuator and access panel The 36 and 48 wide valves are provided with integral mounting struts to help support the...

Страница 15: ...AccuNet modules installed and the remote monitor connected For more details regarding the AccuNet reference Appendix B 24 vAC 24 vDC or Analog Input BMS Controller Signal Receiving Device Common Powe...

Страница 16: ...Insight Software from https www accutrolllc com Run setup and follow the on screen instructions 6 3 AccuValve Insight Software Product Registration After the software has been installed on your comput...

Страница 17: ...Power Source Switch which should always be in the Operational Position for the transmitter to function normally The Nonoperational Position is provided so the transmitter can be programmed or configu...

Страница 18: ...6000 W with optional wireless Bluetooth module Note Reference Appendix B for Bluetooth Connection Details 6 4 3 Connecting to a remote monitor such as the AFM1 Airflow Monitor Windows 10 Device with B...

Страница 19: ...6 5 1 Configuring USB Driver In some instances the Windows 10 machine being used to run Insight may not be equipped with the appropriate USB driver package needed to connect This is a possible occurre...

Страница 20: ...e It may be necessary to restart your PC after installation of the CP2120x driver for the install to take effect 6 5 2 Accuvalve Insight Dashboard The Insight Dashboard is the primary screen for acces...

Страница 21: ...full scale range of the Analog Output or it can be configured with a full scale range that is independent of the Analog Output To change the full scale range click on the gauge face 6 5 4 AccuNet Tota...

Страница 22: ...nfiguring the Analog Output Example 1 shows the Signal Source set to Valve Airflow which is the most common configuration Example 2 shows the Signal Source set to AccuNet Airflow which is only availab...

Страница 23: ...ion about the device such as MAC Address Serial Number Tag Number and USB Bluetooth com status Each of the menu items are described below 1 5 7 1 File Menu Items System Load From Transmitter Flash Mem...

Страница 24: ...ownload all Generic Config files which save to the desktop Note PC must be connected to a transmitter for this function to operate Print Parameters Report Generates a report showing the present config...

Страница 25: ...ability to filter the airflow volume reading and the analog output Measurement Airflow Measurement Opens the Airflow Measurement Window Configuration Airflow Units Opens the window required for config...

Страница 26: ...ked this will display the communication data on the dashboard task bar 6 5 7 Dashboard Task Bar Provides the USB communication status device serial number device tag and BACnet MAC address at the top...

Страница 27: ...The Accutrol AVT6000Transmitter product family supports a collection of BACnet visible objects which are defined in the following table Point Object Description Present Value Type Units DE Device Inst...

Страница 28: ...ereas Flash memory does RAM memory is used by the transmitter to store and retrieve active values which are not retained when the power to the transmitter is lost Values stored in Flash memory are cop...

Страница 29: ...e 3 8 bolt enough to allow the access door to slide forward CAUTION If the bolt is removed from the captive nut the access cover can spring open possibly causing injury 8 1 2 Using two hands squeeze t...

Страница 30: ...cured to the valve using 4 2 blunt head Phillips head screws To inspect the sensors remove the access cover by removing the screws using a 2 Phillips head screw driver Put the screws aside for reinsta...

Страница 31: ...del Code Actuator Identifier Actuator Description Actuator Part Number A2 AVT6xxx 02 Fail Last Position 0 10v High Speed 20 0008 A3 AVT6xxx 03 Fail Last Position 2 10v High Speed 20 0009 A4 AVT6xxx 04...

Страница 32: ...Installation Operation Manual Model AVT6000 Page A2...

Страница 33: ...Installation Operation Manual Model AVT6000 Page A3...

Страница 34: ...Installation Operation Manual Model AVT6000 Page A4...

Страница 35: ...Installation Operation Manual Model AVT6000 Page A5...

Страница 36: ...tuator PN 20 0057 2 Screws PN 17 0246 8 32 x 5 16 Tools Required 10mm wrench 2 Phillips Head Screw Driver ELECTRICAL Power Supply 24 VAC 20 50 60 Hz or 24 VDC 10 Power Consumption 1 4 W nominal 4 0 W...

Страница 37: ...devices objects in the area and building construction Because the AccuValve is typically installed in locations that have sheet metal duct work metal trusses ceiling grids and concrete with metal mes...

Страница 38: ...t be comprised of AccuValves serving only one lab space Each network shall include no less than two and no more than twenty AccuValves The network shall be wired using Windy City Wire PN 042002 or equ...

Страница 39: ...the wiring diagrams the termination resistors are installed and the analog output on the Totalizer is wired to the room controller The network diagram used for this example is shown in Figure 1 Step...

Страница 40: ...unique network address to this AccuNet Module and AccuValve TAG name will be assigned as the TAG name of this AccuNet Module 3 1d Close the Insight Program Dashboard then disconnect the pc from the A...

Страница 41: ...e network address to this AccuNet Module and AccuValve TAG name will be assigned as the TAG name of this AccuNet Module 3 4d If this device is the Totalizer continue to Step 4b If this device is not t...

Страница 42: ...s not yet been configured the default device address of 127 will be shown The complete device list can only be viewed from the valve assigned as the totalizer valve All other devices will only show th...

Страница 43: ...3 FUME HOOD 2 FUME HOOD 1 FHEV1 AVC6 AV6 AVC6 AVC6 Total Exhaust Air Flow AI AO AI Supply Ctrl Signal Supply Air Flow SAV1 GEV1 FHEV2 FHEV3 AO Gen Exhaust Ctrl Signal Lab Controller T T AV6 SAV TOTALI...

Отзывы: