Installation & Operation Manual
- Model AVT6000
Contents of this Manual are Subject to Change Without Notification
Page 6
SECTION 2 - SPECIFICATIONS
PERFORMANCE
Accuracy +/- 5% of reading or 5 CFM, whichever is greater
Speed of Response < 1 second control signal response (full stroke cycle time based on actuator type)
Shut-off Leakage Rate Standard: < 1.5% FS @ max operating pressure
“S” Option:
< 0.5% FS round valves, < 1% FS rectangular valves @ max operating pressure
Max Operating Pressure
3”w
c Differential Pressure Across Valve
Min Operating Pressure Reference Section 2.1
Airflow Range Reference Section 2.1
Failure Mode Open, Closed or Last Position (based on actuator type selection)
ENVIRONMENTAL
Temperature Airstream: -20 to 165 deg. F for all Standard Valve Models
-20 to 375 deg. F for the High Temp SS Valve Models
Ambient: -20 to 125 deg. F
Storage: -40 to 165 deg. F
Humidity 0 to 90% non-condensing
TRANSMITTER ELECTRICAL
Power Supply 24 VAC +/- 20% 50/60 Hz, 4 VA max (8.5 VA max with remote display)
24 VDC +/- 10% 1.5 W max (3.5 W max with remote display)
Output Signal Software Configurable; 0-20mA, 4-20mA, 0-10V, 2-10V, 0-5V, or 1-5V
12-bit Resolution capable of driving 1K-ohm load
Configuration Port USB 2.0, Isolated, C Type Connector, Optional Wireless Configuration using Bluetooth Ver 4.2
Power Source Switch Operational Position: Draws power from 24V input terminal block
Nonoperational Position: Draws power from 5V USB port (Use for configuration only)
BACnet MS/TP
(Optional)
EIA 485 2-wire BACnet MS/TP, Galvanically Isolated
Data Rates 9600, 19200, 38400, 76800 and 115200
1/8 Unit Load Receiver Input Impedance
Network bias and EOL Termination not provided within the Transmitter
AccuNet
(Optional)
2-wire Controller Area Network Bus for summing 2 to 20 Accutrol Device Airflows
120-ohm EOL network termination resistors are required
Reference Appendix C for details
Remote Display
Sold Separately
LCD, 2 lines x 8 characters with white LED backlight
Includes USB Configuration Port and Factory Cable
Terminal Plugs 3-position, vertical pluggable, screw on top, wire size 12-30 AWG
EMC
Safety
EN 61326-1:2013, 2014/35/EU (LVD), 2014/30/EU (EMC)
EN 61010-1:2010
FCC Part 15
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be required to correct the
interference at the user’s own expense. This Class A dig
ital apparatus meets all requirements
of the Canadian Interference-Causing Equipment Regulations.
Units provided with the optional Bluetooth low energy module contain
FCC ID: XPYNINAB1 IC: 8595A-NINAB1
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two
conditions;
(1)
This device may not cause harmful interference, and
(2)
This device must accept any interference received, including interference that may
cause undesired operation.
KCC South Korea compliance certification number MSIP-CRM-ULX-NINA-B111
Australia and New Zealand regulatory compliance. The NINA-B1 modules are compliant with
AS/NZS 4268:2012?AMDT 1:2013 standard
–
Radio equipment and systems
–
Short range
devices
–
Limits and methods of standard measurement made by the Australian
Communications and Media Authority (ACMA)
ACTUATOR ELECTRICAL
Reference Appendix A