4.3 Read[x03]/Write[x06] Parameter Table 

Read/Write-able Parameters:

 The following parameter’s data can be changed or just be read out 

without change.

 

 

 

Addres

Naming 

Range 

Init Value 

Unit 

x0000 

SV 

LOLT ~HILT 

20.0 

°C/°F 

x0001 

OUTL 

-100.0 ~ 100.0 

0.0 

x0002 

ENAB 

x0000 /    OFF (Turn off output) 

OFF 

Index 
Code 

x0001 /    AT1 (auto-tune at SV) 

x0002 /    AT2 (auto-tune at 90% of SV ) 

x0003 / MPWR (Manual set duty cyl) 

x0004 / SPON (Single Temp point ctrl) 

x0005 / PROG (Run Programmable temp profile) 

x0006 / HOLD (Hold Temp during prog profile run ) 

x0003 

PB1 

0.00 ~ 300.00 

5.0 

x0004 

TI1 

0 ~ 4500 

240 

100mSec 

x0005 

TD1 

0~ 1125 

60 

100mSec 

x0006 

MR1 

0.0 ~ 51.0 

0.0 

x0007 

AR1 

0.0 ~ 100.0 

50.0 

x0008 

ASP1 

LOLT ~HILT 

(region-1 PID range ex. <0~50.0C) 

50.0 

°C/°F 

x0009 

PB2 

0.00 ~ 300.00 

5.0 

x000A 

TI2 

0 ~ 4500 

240 

100m Sec 

x000B 

TD2 

0~ 1125 

60 

100m Sec 

x000C 

MR2 

0.0 ~ 51.0 

0.0 

x000D 

AR2 

0.0 ~ 100.0 

50.0 

x000E 

ASP2 

LOLT ~HILT 

(region-2 PID range ex. <50.1~100.0C) 

100.0 

°C/°F 

x000F 

PB3 

0.00 ~ 300.00 

5.0 

x0010 

TI3 

0 ~ 4500 

240 

100m Sec 

x0011 

TD3 

0~ 1125 

60 

100m Sec 

x0012 

MR3 

0.0 ~ 51.0 

0.0 

x0013 

AR3 

0.0 ~ 100.0 

50.0 

x0014 

ASP3 

LOLT ~HILT 

(region-3 PID range ex. <100.1~150.0C) 

150.0 

°C/°F 

x0015 

PB4 

0.00 ~ 300.00 

5.0 

x0016 

TI4 

0 ~ 4500 

240 

100m Sec 

x0017 

TD4 

0~ 1125 

60 

100m Sec 

x0018 

MR4 

0.0 ~ 51.0 

0.0 

x0019 

AR4 

0.0 ~ 100.0 

50.0 

x001A 

A1SP 

LOLT ~HILT (Alarm 1 set point) 

100.0 

°C/°F 

x001B 

A1HY 

-200.0 ~ 200.0 (value for alarm region or delta-t ) 

0.0 

°C/°F 

x001C 

A1FU 

x0007 /    OFF    ( alarm not activate) 

OFF 

Index 
Code 

x0008 /      HI          (alarm on when >A1SP) 
x0009 /      LO        (alarm on when <A1SP) 
x000A / DIFH    (alarm on when >delta) 
x000B / DIFL    (alarm on when <delta) 
x000C / BDHI    (alarm on when out off region) 
(alarm on when exit region) 
x000D / BDLO (alarm on when PV within region) 

x001D 

A1MD 

x000E / NONE (Alarm run in normal condition) 
(Alarm on normal condition) 

NONE 

Index 
Code 

x000F / STDY    (Ignore first alarm) 
x0010 / LATH    (turn alarm on when latch) 

Содержание ATEC302

Страница 1: ...ATEC302 TE Temperature Controller Reference Manual Rev 1 10 Mar 2018 Accuthermo Technology Corp...

Страница 2: ...Return to Top Level Display 11 ii Go to Menu Mode 11 iii Select Parameters in Menu 11 iv Changing Parameter value 11 3 2 Power UP Display Sequence 12 3 3 Change the SV Set Value Number 12 4 Parameter...

Страница 3: ...rd DIN72x72mm and Din Rail size The input is configurable and allows selection of input between thermocouples RTD and Thermistor The TE Amplifier is capable of running up to 700Watt of power It is a v...

Страница 4: ...uraged to read the following two manuals first TE Temperature Controller System Installation Guild This is the must read document for user to putting the system together It is a step by step guide wit...

Страница 5: ...Accuthermo Technology Corp 5 2 System Overview 2 1 System Configuration Overview...

Страница 6: ...on when controller sent the Enable signal to the amplifier DIR Controller Hot Cold Direction LED indicator for the hot cold direction command signal PWM Pulse Width Modulation Signal LED signal lighte...

Страница 7: ...olate those leads Otherwise possible electric short could happen 2 6 1 Sensor Type Measurement Range There are three types of sensors supported by the TE Panel controllers Thermocouple TC Thermocouple...

Страница 8: ...D sensors If 2 wire is used just short the pin7 pin8 Range 120 0 C 200 0 C Sensor Type Dip Switch Setting SW1 2 SW1 3 SW2 1 SW2 2 OFF OFF ON ON OFF OFF OFF ON ON ON OFF OFF Switch at the inside of the...

Страница 9: ...ut sensor selection Set a higher value to high limit Check connect input sensor selection PV value flashing Input signal below the low limit Incorrect input sensor selection Set al lower value to low...

Страница 10: ...ntacts in system to eliminate high voltage spike sources Separate sensor and controller wiring from dirty power lines Ground heaters Entered data lost Fail to enter data to EEPROM Update EEPROM again...

Страница 11: ...and hold two buttons for 5 seconds the screen will jump to menu mode The RED LED line should show It is the first level menu By pressing button user can select various top menus in sequence using butt...

Страница 12: ...ghlight the digit you want to change ii Use or buttons to change to the value desired iii Press to confirm the value 4 Parameters Description 4 1 Communication Protocol 4 1 1 Communication Method One...

Страница 13: ...r returned an 8 bytes data to its master x01 03 0002 01F7 CCCC Where x01F7 is the temperature measured in Hex format 50 3 where x means hex format C means CRC data 1 2 3 4 5 6 7 8 Represent ID R W Fun...

Страница 14: ...yte 3 4 is the initial parameter address The byte 5 6 is to tell slave how many consecutive data you want The following example only asks for one data The master ask the controller to read current tem...

Страница 15: ...2 and see how they interacting each other Refer to top right pic the protocol page of Accuthermo PC software After read PV and converted to DegC it shown 19 7C and should be the same as value showing...

Страница 16: ...cycle x 0 2 5 _ Autotune 90 SV P I D in analyzing and calculating x 0 3 0 _ Manual Output x 0 4 0 _ General Control single point temperature control Programmable step temperature control multipoint te...

Страница 17: ...history value1 fixed 1 decimal point C F ENG x100E ET2 SV PV history value2 fixed 1 decimal point C F ENG x100F Px Proportional factor x1010 Ix Integral factor Sec x1011 Dx Differential factor Sec x10...

Страница 18: ...Sec x000C MR2 0 0 51 0 0 0 x000D AR2 0 0 100 0 50 0 x000E ASP2 LOLT HILT region 2 PID range ex 50 1 100 0C 100 0 C F x000F PB3 0 00 300 00 5 0 x0010 TI3 0 4500 240 100m Sec x0011 TD3 0 1125 60 100m Se...

Страница 19: ...dition NONE Index Code x000F STDY Ignore first alarm x0010 LATH turn alarm on when latch x0011 STLA Ignore first alarm and turn next alarm on when latch x0025 A2DT 9999 0 delay time to turn alarm on 0...

Страница 20: ...x0038 SP1 LOLT HILT 1 st Set Point Value 20 0 C F x0039 ST1 0 9999 1 st SP Sock Time 60 Sec Min x003A SF1 x002C RT8 after ST time jump to RT8 END Index Code x002D RT7 after ST time jump to RT7 x002E R...

Страница 21: ...mp to RT3 x0032 RT2 after ST time jump to RT2 x0033 RT1 after ST time jump to RT1 x0034 END After prog turn off output x0035 HOLD After prog hold temperature x0036 NEXT After prog goto RT5 x004A LN4 1...

Страница 22: ...fter ST time jump to RT8 x0059 LN7 1 9998 x270E Loop number Infinite loop 9999 x270F 1 count x005A RT8 0 9999 60 Sec Min x005B SP8 LOLT HILT 20 0 C C F x005C ST8 0 9999 60 Sec Min x005D SF8 x002C RT8...

Страница 23: ...n the controller felt there is an error it will return Error Code ID Function x80 00 Error code x00 x00 Function error xx x8x x00 X01 x00 x00 Function error write or read only with x03H or x06H Addres...

Страница 24: ...and then outputting a corrective action that can adjust the process accordingly and rapidly to keep the error minimal Please use the software provided with this system to better understand the relati...

Страница 25: ...2 ST4 R T 1 R T 3 ST1 ST2 RT4 R T 2 ST4 SP1 SP2 SP4 SP1 SP2 SP3 SP4 I f R T3 0 t hen j um p I f ST3 0 t hen j um p SP3 R T 1 ST1 ST2 R T 2 SP1 SP2 i f SF3 EN D t hen O ut l 0 0 R T 1 ST1 ST2 R T 2 SP1...

Страница 26: ...Accuthermo Technology Corp 26 5 4 Alarm Function...

Страница 27: ...ling Rate 10Hz Temperature Control Res 0 1 C 0 1 F Programmable Profile 8 Steps ramp soak time loop in loop complex loop profile Control Software Full function Window Program plot chart log data engin...

Отзывы: