Accuthermo Technology Corp.
18
4.3 Read[x03]/Write[x06] Parameter Table
Read/Write-able Parameters:
The following parameter’s data can be changed or just be read out
without change.
Addres
s
Naming
Range
Init Value
Unit
x0000
SV
LOLT ~HILT
20.0
°C/°F
x0001
OUTL
-100.0 ~ 100.0
0.0
%
x0002
ENAB
x0000 / OFF (Turn off output)
OFF
Index
Code
x0001 / AT1 (auto-tune at SV)
x0002 / AT2 (auto-tune at 90% of SV )
x0003 / MPWR (Manual set duty cyl)
x0004 / SPON (Single Temp point ctrl)
x0005 / PROG (Run Programmable temp profile)
x0006 / HOLD (Hold Temp during prog profile run )
x0003
PB1
0.00 ~ 300.00
5.0
%
x0004
TI1
0 ~ 4500
240
100mSec
x0005
TD1
0~ 1125
60
100mSec
x0006
MR1
0.0 ~ 51.0
0.0
%
x0007
AR1
0.0 ~ 100.0
50.0
%
x0008
ASP1
LOLT ~HILT
(region-1 PID range ex. <0~50.0C)
50.0
°C/°F
x0009
PB2
0.00 ~ 300.00
5.0
%
x000A
TI2
0 ~ 4500
240
100m Sec
x000B
TD2
0~ 1125
60
100m Sec
x000C
MR2
0.0 ~ 51.0
0.0
%
x000D
AR2
0.0 ~ 100.0
50.0
%
x000E
ASP2
LOLT ~HILT
(region-2 PID range ex. <50.1~100.0C)
100.0
°C/°F
x000F
PB3
0.00 ~ 300.00
5.0
%
x0010
TI3
0 ~ 4500
240
100m Sec
x0011
TD3
0~ 1125
60
100m Sec
x0012
MR3
0.0 ~ 51.0
0.0
%
x0013
AR3
0.0 ~ 100.0
50.0
%
x0014
ASP3
LOLT ~HILT
(region-3 PID range ex. <100.1~150.0C)
150.0
°C/°F
x0015
PB4
0.00 ~ 300.00
5.0
%
x0016
TI4
0 ~ 4500
240
100m Sec
x0017
TD4
0~ 1125
60
100m Sec
x0018
MR4
0.0 ~ 51.0
0.0
%
x0019
AR4
0.0 ~ 100.0
50.0
%
x001A
A1SP
LOLT ~HILT (Alarm 1 set point)
100.0
°C/°F
x001B
A1HY
-200.0 ~ 200.0 (value for alarm region or delta-t )
0.0
°C/°F
x001C
A1FU
x0007 / OFF ( alarm not activate)
OFF
Index
Code
x0008 / HI (alarm on when >A1SP)
x0009 / LO (alarm on when <A1SP)
x000A / DIFH (alarm on when >delta)
x000B / DIFL (alarm on when <delta)
x000C / BDHI (alarm on when out off region)
(alarm on when exit region)
x000D / BDLO (alarm on when PV within region)
x001D
A1MD
x000E / NONE (Alarm run in normal condition)
(Alarm on normal condition)
NONE
Index
Code
x000F / STDY (Ignore first alarm)
x0010 / LATH (turn alarm on when latch)