EV/DV300 Series Power Meter
V:2.0 Revised October 2018
43
3. Read Data (function code 03)
Query
This function code is used to read the metering data in meter. Table 4.8 Example of reading
3 metering data U1, U2 and U3. The register address is, U1: 0110H, U2: 011H and U3:
0112H.
Table 4.8 Query of Reading U1, U2 and U3
Addr
Fun
Data
start reg
hi
Data
start reg
lo
Data #of
regs hi
Data #of
regs lo
CRC16
hi
CRC16
lo
11H
03H
01H
10H
00H
03H
07H
62H
Response
The response includes Address of slave device, function code, data register start address,
number of metering data and error check.
Table 4.9 Example of response of reading U1, U2 and U3 (U1=03E8H (100.0V),
U2=03E7H(99.9V), U3=03E9H(100.1V)).
Table 4.9 Response of reading U1, U2 and U3
Addr Fun
Byte
count
Data1
hi
Data1
lo
Data2
hi
Data2
lo
Data3
hi
Data3
lo
CRC16
hi
CRC16
lo
11H 03H
06H
03H
E8H
03H
E7H
03H
E9H
FDH
9CH
4. Control Relay (function code 05)
Query
This message forces single Relay either ON or OFF. The start address of Relay is from 0000H.
(Relay1= 0000H, Relay2=0001H).
The data value FF00H will set the Relay ON and the value 0000H will turn it OFF. All other
values are illegal and will not affect that Relay.
Содержание DV300 Series
Страница 1: ...EV DV300 Series Power Meter Chapter 1 Introduction V 2 0 Revised October 2018 1 Cover page...
Страница 34: ...EV DV300 Series Power Meter Chapter 3 Operation and Setting V 2 0 Revised October 2018 34...
Страница 54: ...EV DV300 Series Power Meter Appendix V 2 0 Revised October 2018 54 Appendix B Ordering Information...
Страница 55: ...EV DV300 Series Power Meter Appendix V 2 0 Revised October 2018 55...