![AccuEnergy AcuDC 200 Series Скачать руководство пользователя страница 38](http://html1.mh-extra.com/html/accuenergy/acudc-200-series/acudc-200-series_user-manual_3772079038.webp)
28
AcuDC 200 Series
Voltage Output Current Output
Fig 2.20 Analog Output
Output Capability:
4~20mA, Max Load Resistance 500 Ohm; 0~5 V, Max Output Current 20mA.
2.3.4 Communication
AcuDC 200 series uses RS485 serial communication and the Modbus-RTU protocol.
The terminals of communication are A, B, and S (20, 21, 22). A is differential ,
B is differential signal - and S is connected to shield of twisted pair cable. Up to 32
R
VCC
Vout
AcuDC 200
+
-
Load
R2
VCC
Vout
AcuDC 200
+
-
Load
R1
www.
GlobalTestSupply
.com
Find Quality Products Online at: