![AccuEnergy AcuDC 200 Series Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/accuenergy/acudc-200-series/acudc-200-series_user-manual_3772079034.webp)
24
AcuDC 200 Series
Fig 2.19 Relay Output
The two relays in AcuDC 200 Series can be used to control field switches or other
devices. The maximum mechanical response time for the relay is 3ms. Three output
modes are available: latching, momentary and alarming. For latching mode, two
output status are available: "ON" and "OFF". For momentary mode, output of the
relay changes from "OFF" to "ON" for a time interval of "Ton" then goes back to
"OFF". "Ton" can be set from 30~5000ms. Output mode and pulse width can only
be set through communication. The alarming mode will be discussed in detail in the
following chapter under the "alarming" section. The wire of relay output should be
chosen between AWG22 (0.5mm
2
)~AWG16 (1.5mm
2
)
27
28
AcuDC 200
R11
R12
wires of mediate relay
mediate relay
auxiliary power
+
_
www.
GlobalTestSupply
.com