background image

1

Ethernet Modual

j) Set HTTP port in the eighth setting page, such as 80. Press “V/A” key, 

go to setting state. Users may set parameter in the pointed area, and 

cursor starts at the first digit bit. After setting HTTP port completely, 
press “V/A” key to affirm. Again press “P” key, go to the ninth setting 
page for resetting mode. HTTP port’s default value is 80, and the user 
defined range of port is 6000~9999.  If the set port is not in range, the 

set port will return default value.

Figure 3-12

k) Set resetting mode in the ninth setting page. Select “RESET” to reset 

module.  Select  “NO”  means  not  to  reset  module.  Select  “DEFAULT” 
means load module with default settings and reset module. Press “V/A” 

key, go to setting state, and the pointed area flashes. Press “P” key or “E” 
key to select configuration mode, press “V/A” key to affirm.

Note: When configuring Ethernet module settings completely, users must 
select “RESET” to restart module and new settings will take effect.

Содержание Accuvim II

Страница 1: ......

Страница 2: ......

Страница 3: ...of Accuenergy The information contained in this document is believed to be accurate at the time of publication however Accuenergy assumes no responsibility for any errors which may appear here and res...

Страница 4: ...rous Observe the information after the symbol to avoid possible injury or death Focus symbol avoid inadvertent operations which may lead to abnormal working of instrument even damage to the instrument...

Страница 5: ...RJ45 Interface 8 2 4 Cable 9 2 5 Connection Method 9 Chapter 3 Function Description of Ethernet MODULE 11 3 1 Initializing Ethernet Module 12 3 2 Searching IP Address of Ethernet Module 22 3 3 Descri...

Страница 6: ...s manual carefully before operating and setting the Acuvim II meter to avoid unnecessary trouble Chapter 1 helps you to understand the fundamental concept of Ethernet and application points of Etherne...

Страница 7: ...1 Chapter 1 Introduction Ethernet Introduction Function Description...

Страница 8: ...y standard Ethernet is the most current communication standard in LAN This standard defines the used type of cable and the used method of Signal processing in LAN 1 2 Function Description of Ethernet...

Страница 9: ...Ethernet Modual and the default value of protocol port is 80 and the scope of protocol port is 6000 9999...

Страница 10: ...Ethernet Modual...

Страница 11: ...Chapter 2 Wiring and Connection Appearance and Dimensions Installation Method Definition of RJ45 Interface Cable Connection Method 5...

Страница 12: ...In addition Ethernet module must be the first extended module linked to Acuvim II meter 2 1 Appearance and Dimensions Side View Top View NOTE The environment temperature and humidity should fulfill th...

Страница 13: ...to Acuvim II meter by communication plug It can also be linked to other extended modules like IO modules 1 Insert the installation clips to the counterpart of Acuvim II meter and then press the Ether...

Страница 14: ...RJ45 connector access Ethernet network The mechanical and electrical characteristics of connector are consistent with the requirements of IEC 603 7 Top View Script ID Content 1 TX Tranceive Data 2 TX...

Страница 15: ...rd 2 5 Connection Method 1 Direct Connect Ethernet module use cross line standard 568A to connect to computes Users may refer to the third chapter Function description of Ethernet module for using Eth...

Страница 16: ...10 Ethernet Modual...

Страница 17: ...11 Chapter 3 Function Description Initializing Ethernet Module Searching IP Address of Ethernet Module Description of Modbus TCP protocol Browse Webpage and Set Parameters Mail Function...

Страница 18: ...Module AXM Net default settings are IP Address 192 168 1 254 Subnet Mask 255 255 255 0 Gateway 192 168 1 1 Primary DNS Server 202 106 0 20 If you don t know the settings of module when power on for t...

Страница 19: ...tting mode Device address page is the first page of Setting mode It shows the Modbus address of the device for several seconds and then the screen goes to Access Code page Press V A key go to the para...

Страница 20: ...ion mode in the first setting page AUTO means that users configure module settings with DHCP protocol while MANU means that users configure module settings with manual setting Press V A key go to sett...

Страница 21: ...e Wait until the reset is finished and find the new IP address in the following step Figure 3 5 d Set IP Address in the second setting page such as 192 169 1 100 as shown below Press V A key go to set...

Страница 22: ...such as 255 255 255 0 Press V A key go to setting state Users may set parameter in the pointed area and cursor starts at the first digit bit After setting Subnet Mask completely press V A key to affi...

Страница 23: ...2 169 1 1 Press V A key go to setting state Users may set parameter in the pointed area and cursor starts at the first digit bit After setting Gateway completely press V A key to affirm Again press P...

Страница 24: ...state Users may set parameters in the pointed area and cursor starts at the first digit bit After setting DNS Primary Server completely press V A key to affirm Again press P key go to the sixth setti...

Страница 25: ...ing state Users may set parameter in the pointed area and cursor starts at the first digit bit After setting DNS Secondary Server completely press V A key to affirm Again press P key go to the seventh...

Страница 26: ...ted area and cursor starts at the first digit bit After setting Modbus TCP port completely press V A key to affirm Again press P key go to the eighth setting page for HTTP port Modbus TCP port s defau...

Страница 27: ...ed range of port is 6000 9999 If the set port is not in range the set port will return default value Figure 3 12 k Set resetting mode in the ninth setting page Select RESET to reset module Select NO m...

Страница 28: ...aneously to return menu selecting mode Users can do other operation 3 2 Searching IP Address of Ethernet Module Acuvim II tool software supports search function and Users use it to get IP address and...

Страница 29: ...23 Ethernet Modual Figure 3 14 3 Tool software pop up Search Device s window and window display IP address and MAC address of module Figure 3 15...

Страница 30: ...ng mode of Modbus TCP protocol Figure 3 16 1 Protocol 1 Data Frame Format MBAP Header Function Data 7x8 Bits 8 Bits Nx8 Bits Table 3 1 2 Modbus Application Header MBAP Header Field Modbus application...

Страница 31: ...Data Field The data field is constructed using sets of two hexadecimal digits in the range of 00 to FF hexadecimal The data field of messages sent from a master to slave devices contains additional in...

Страница 32: ...the meaning of each abbreviated word is Transaction identifier hi Transaction Identifier high byte Transaction identifier lo Transaction Identifier low byte Protocol identifier hi Protocol Identifier...

Страница 33: ...er 00H 00H 00H 00H 00H 06H 01H Fun Data start reg hi Data start reg lo Data of regs hi Data of regs lo 01H 00H 00H 00H 02H Table 3 5 Read 2 Relays Status Query Message Response The Acuvim II response...

Страница 34: ...m II and the start address is 0000H The following query is to read the 4 DIs Status of address 1 of Acuvim II Query Transaction identifier hi Transaction identifier lo Protocol identifier hi Protocol...

Страница 35: ...identifier 00H 00H 00H 00H 00H 04H 01H Fun Byte count Data 02H 01H 0FH The content of the data is 7 6 5 4 3 2 1 0 0 0 0 0 1 1 1 1 MSB LSB Table 3 8 Read 4 DIs Response Message 3 Read Data Function Co...

Страница 36: ...03H 0CH 07H D6H 00H 0CH 00H 12H 00H 0EH 00H 0FH 00H 14H Table 3 10 Read Time Response Message 4 Control Relay Function Code 05 Query The message forces a single Relay either on or off Any Relay that...

Страница 37: ...elay Response Message 5 Preset Reset Multi Register Function Code 16 Query Function code 16 allows the user to modify the contents of a Multi Register The example below is a request to an Acuvim II ad...

Страница 38: ...i Registers Response Message Users may refer to the fifth chapter Communication and get the details of Acuvim II When users use Moubus Tcp function you set best the Scan Interval of tool soft under 10...

Страница 39: ...ink to get into webpage Figure 3 17 1 Index Webpage Users put IP address of module in Address of IE Browser and enter Index webpage Index webpage supplies three links to enter Data webpage or Settings...

Страница 40: ...gs Webpage Press Settings link to enter settings webpage Figure 3 20 is flow chart for settings webpage First IE Browser enters Password webpage and it need check module password Initial password is 1...

Страница 41: ...ng Mode Event Mode None Mode Select Content and Press Affirm Button Select Load Default Manner and Press Affirm Button Password Setting Webpage Complete Webpage Set New Password and Press Affirm Butto...

Страница 42: ...Settings webpage It supports two network setting mode Manual or Auto Except network setting mode there are two port settings in Webpage One is HTTP port and the other is Modbus TCP port The default va...

Страница 43: ...37 Ethernet Modual Figure 3 22 Figure 3 23 Configure network settings completely for Manual mode webpage Figure 3 23 Figure 3 24 configure network settings completely for Auto mode webpage...

Страница 44: ...connection for these settings and the module may not send mail The value of Mail Sending Interval is interval time between two mails under Send mail for timing mode the default value is 1 hour the ran...

Страница 45: ...ng mode webpage Send mail for timing mode is a timing manner according to Mail Sending Interval which sends mail content to Mail to mail box Under this mode mail content includes Real Time Metering En...

Страница 46: ...s a manner of event triggered according to event type Alarm type SOE type which sends mail content to Mail to mail box Under this mode mail content includes Alarm Event SOE Event and users may select...

Страница 47: ...ubject and Mail Sending Interval needn t be set repeatedly 4 Webpage Settings Webpage Figure 3 30 Webpage Settings webpage Users set the value of Device s Description according to meter type The defau...

Страница 48: ...42 Ethernet Modual Figure 3 30 Figure 3 31 webpage settings set completely webpage Figure 3 31 5 Load Default Webpage Figure 3 32 Load Default webpage Figure 3 32...

Страница 49: ...Figure 3 33 Load default successful webpage The network settings of module will renewed default value Figure 3 33 6 Password Setting Webpage Figure 3 34 Password Setting webpage Figure 3 34 6 12word...

Страница 50: ...3 36 is flow chart of data webpage There are six kinds of data webpage They are Metering webpage Energy and Harmonics webpage and Max and Min 1 Max and Min 2 webpage Alarm Record webpage and SOE Reco...

Страница 51: ...n parameters such as Volts AN I A and Watt Total Demand Max and Min 2 webpage includes the max and min data of parameters for Acuvim II There are twelve parameters such as Frequency Imbalance V and TH...

Страница 52: ...rval which sends mail content to Mail to mail box The mail content includes Real Time Metering Energy and Harmonics Max and Min Send mail for event mode is a manner of event triggered according to eve...

Страница 53: ...Appendix Appendix A Technical Data and Specifications Appendix B Ordering Information Appendix C Revision History 47...

Страница 54: ...tal IEC 60068 2 30 Safety IEC 61010 1 Communication Port Physical Layer Standard RJ45 socket Protocol Modbus TCP SMTP HTTP Baud Rate 10M 100M auto adapted Suitable Condition Dimensions 90X55 6X22 mm W...

Страница 55: ...49 Ethernet Modual Appendix 2 Ordering Information Type AXM NET...

Страница 56: ...50 Ethernet Modual Appendix C Revision History Revision Date Description 1 0 20070915 1 01 20080718 Note User need to set the parameter of network...

Страница 57: ......

Страница 58: ......

Отзывы: