Ethernet Modual
1) Read Status Relay (Function Code 01)
Function Code 01
This function code is used to read relay status in Acuvim II.
1=On
0=Off
There are 8 Relays in Acuvim II, and the start address is 0000H.
The following query is to read 2 Relays Status of Acuvim II Address 1.
Query
Transaction
identifier hi
Transaction
identifier lo
Protocol
identifier hi
Protocol
identifier lo
Length hi Length lo
Unit
identifier
00H
00H
00H
00H
00H
06H
01H
Fun
Data start reg hi
Data start reg lo
Data #of regs hi
Data #of regs lo
01H
00H
00H
00H
02H
Table 3-5 Read 2 Relays Status Query Message
Response
The Acuvim II response includes MBAP Header, function code, quantity
of data byte, the data. An example response to read the status of Relay
1 and Relay 2 is shown as Table 3-6. The status of Relay 1 and Relay 2 is
responding to the last 2 bit of the data.
Relay 1: bit0
Relay 2: bit1
Transaction
identifier hi
Transaction
identifier lo
Protocol
identifier hi
Protocol
identifier lo
Length hi Length lo
Unit
identifier
00H
00H
00H
00H
00H
04H
01H
Содержание Accuvim II