Table 9 - EQ Water Cooled Chiller Electrical Specifications
Model
Voltage
Compressor
Pump
Control Circuit
Unit MCA
2
RLA
1
Power (HP)
FLA
FLA
EQ2W02
208/3/60
9.5
1 (.745 kW)
3.9
0.24
16.8
230/3/60
8.6
3.6
0.22
15.4
460/3/60
4.3
1.8
0.11
8.2
208/3/60
9.5
2 (1.49 kW)
7.5
0.24
20.4
230/3/60
8.6
6.8
0.22
18.6
460/3/60
4.3
3.4
0.11
9.8
208/3/60
9.5
3 (2.24 kW)
10.6
0.24
23.5
230/3/60
8.6
9.6
0.22
21.4
460/3/60
4.3
4.8
0.11
11.2
208/3/60
9.5
2 (1.49 kW)
2-stg
8.8
0.24
21.7
230/3/60
8.6
8
0.22
19.8
460/3/60
4.3
3.7
0.11
10.1
EQ2W03
208/3/60
12.6
1 (.745 kW)
3.9
0.24
20.7
230/3/60
11.4
3.6
0.22
18.9
460/3/60
6.2
1.8
0.11
10.6
208/3/60
12.6
2 (1.49 kW)
7.5
0.24
24.3
230/3/60
11.4
6.8
0.22
22.1
460/3/60
6.2
3.4
0.11
12.2
208/3/60
12.6
3 (2.24 kW)
10.6
0.24
27.4
230/3/60
11.4
9.6
0.22
24.9
460/3/60
6.2
4.8
0.11
13.6
208/3/60
12.6
2 (1.49 kW)
2-stg
8.8
0.24
25.6
230/3/60
11.4
8
0.22
23.3
460/3/60
6.2
3.7
0.11
12.5
Notes:
RLA (Rated Load Amps) based on a percentage of the MMTC (Maximum Must Trip Current) as established by the manufacturer in accordance with UL
Standard 465.
MCA (Minimum Circuit Ampacity) based on 125% of the compressor RLA plus 100% of remaining components FLA in accordance with NEC 440-33. MCA
shown also include 1 amp value for the control circuit.
Voltage Utilization range is: 208 (187 to 229), 230 (207 to 254), and 460 (414 to 506).