Standard communication

The  communication  icon  is  steadily  lighted  on  if 

communication  with  the  heater  is  running  properly. 

Normally the requested heat output is displayed as 

% of the nominal output.
Where applicable the number of heaters connected is 

displayed on the top right.

Operation selection : Off - Summer - Winter

Press the [

] button to select the operation mode 

to be run: OFF ( ), SUMMER ( ) or WINTER ( ). 

WINTER activates the heating.
Run and the output is modulated upon the outdoor and 

room temperature (i.e. heating request from the chrono-

thermostat; the outdoor temperature is compared to 

a set-point value).
SUMMER activates only the air blower for ventilation. 

It can be activated manually or
automatically by program; T2 automatic; T0 and T1 

in any other mode of operation and deactivating the 

ventilation.  
The manually activation - by pushing the bottom on 

the chrono thermostat. 
In the first case press the [FAN] button to run the air 

blower and press it again to stop it. 
Press [OFF] to put the heater on stand-by, from any 

function mode.

Outdoor temperature

Press  long  the  [ ]  button  to  enter  the  outdoor 

temperature setting menu.
If one of the appliances switched to Encrono GA1 has 

an outdoor temperature probe (configured to translate 

information via Open Therm) it is possible to visualize 

the value closed to indicator “tou”.
By which the set point “Tset” can be loaded and the 

outdoor temperature displayed. 
The Tset value is used to calculate the heat output 

request and shall be within the range -99 / 100 °C.

Heater lockout and remote reset

In case of heater (or more than one) failure, which 

causes  the  unit  lockout,  different  signals  might  be 

displayed based on the type of protocol/ application 

used:
1.  two  digits  number  that  identifies  the  faulty  unit 

(n. 01 … n.02, ….etc), in case of heaters cascade 

installation 2. “E00” error code, which identifies the 

mode of failure
3. “Err” in case the mode of failure is not available 

(generic error) Table xx shows the list of failure modes 

and codes.
Note that E05 is the sole failure independent from the 

number of units connected, as it refers to the room 

temperature sensor that is fixed inside the control panel 

indipendente of the display shown on the left side of 

the screen, on the right you will see a funter three-digit 

error code, preceded by the letter F, communicated 

directly from the card remote and displayed without 

any processing by the programmable thermostat.
Press [RESET] button to reset the alarm.
However some alarms cannot be reset by the control 

panel; in this case E11 will be displayed for 10 s. For 

some  alarm  the  reset  button  is  deactivated  and  a 

“beep” sound advises that reset by the control panel 

is not allowed.

Fig.8

DIMENSIONS mm

Содержание MEC MIX C

Страница 1: ...1 Wall mounted air heaters with premixed gas burner MEC MIX C condensation and modulation MEC MIX F fixed power TECHNICAL INFORMATION...

Страница 2: ...2...

Страница 3: ...2 WARNING Advises the reader that the next given information is extremely important and must be followed exactly Otherwise proper function of the unit and safety might be jeopardised Paragraphs writt...

Страница 4: ...C MIX C 20 70 20 90 axial 11 3 10 Dimensions MEC MIX F 70 100 axial 11 3 11 Electrical wiring 12 4 CONTROL AND SAFETY 13 4 1 Description 13 4 2 General features 13 4 3 Technical data logical board 13...

Страница 5: ...flow rate the gas supply pressure is within the range shown on the unit s label 2 4 GAS LEAK In case of smell of gas do not operate mobile phone switch or any device that could cause sparking immediat...

Страница 6: ...qualified operator who first shall identify the mode and cause of failure The premix blower is placed in front of the burner and ensure the proper air gas ratio at any condition Iftheairintakeductort...

Страница 7: ...7 3 3 TABLE OF TECHNICAL DATA MEC MIX C CONDENSATION AXIAL 3 4 TABLE OF TECHNICAL DATA MEC MIX F AXIAL...

Страница 8: ...8 3 5 TABLE OF TECHNICAL DATA MEC MIX C CONDENSATION CENTRUFUGE 3 6 TABLE OF TECHNICAL DATA MEC MIX F CENTRUFUGE...

Страница 9: ...nly in the Model MEC MIX C 747 120 3 7 DIMENSIONS Serie MEC MIX C condensation model 20 35 20 45 centrifuge fans Serie MEC MIX F model 35 50 centrifuge fans Values in mm gas connection air inlet exhau...

Страница 10: ...MIX C condensation model 20 35 20 45 axial fans Serie MEC MIX F model 35 50 axial fans The condensate drain is present only in the Model MEC MIX C Values in mm TOP VIEW gas connection exhaust outlet...

Страница 11: ...Dimensions Serie MEC MIX C condensation model 20 70 20 90 centrifuge Serie MEC MIX F model 70 100 centrifuge Values in mm gas connection gas connection air inlet air inlet exhaust outlet exhaust outl...

Страница 12: ...12 3 10 Dimensions Serie MEC MIX C condensation model 20 70 20 90 axial Serie MEC MIX F model 70 100 axial Values in mm gas connection gas connection air inlet air inlet exhaust outlet exhaust outlet...

Страница 13: ...on electrode EF Premix blower EV1 First stage valve EX Cascade unit connection F1 Fuse 1 6 3A F2 Fuse 2 6 3A FAN1 Air motor fan 1 FAN2 Air motor fan 2 GA1 Chrono thermostat ION Detecting electrode M1...

Страница 14: ...ermostatGA1 air delivery temperature and safety control by means of a double NTC ST16 temperature probe air delivery temperature control by means of a double NTC ST08 temperature probe possibility of...

Страница 15: ...out Before starting the unit check the followings the combustion chamber is free from gas if ignition cycle is simulated without gas check the unit lockout occurs after the safety time if gas supply i...

Страница 16: ...esameprocedure for setting T1 Note that anyway T2 shall be higher than T1 Which shall be higher thanT0 otherwise a beep sound advises that the value is not allowed However each temperature shall be wi...

Страница 17: ...parameters Then press PROG to return to the selection of the day of the week By holding pressed the OK button the lighted day programme will be copied to the next day of the week Press AUTO to leave...

Страница 18: ...n via Open Therm it is possible to visualize the value closed to indicator tou By which the set point Tset can be loaded and the outdoor temperature displayed The Tset value is used to calculate the h...

Страница 19: ...bles connection then put the terminal back into the slot The communication protocol allows of 50 m maximum cable length and Ohm resistance of each cable shall not exceed 5 Ohm In case of proximity to...

Страница 20: ...hermostat ENCRONO type GA1 EF Fan motor of the burner FAN Fan motor of treated air ACC1 Auxiliary ignition transformer EV1 First stage valve SR Temperature control sensor STF Fire damper SA Room tempe...

Страница 21: ...WIRING DIAGRAM FOR CASCADES CONNECTIONS OF MULTIPLE DEVICES VIA OPEN THERM Fig 13 NOTE 1 The cascade connection is possible with a chrono thermostat too This configuration is not used in the versions...

Страница 22: ...e MOLEX 2478 J9 Modulator power supply MOD Connector 2 poles type LUMBERG 3114 terminals type LUMBERG 3111 01 L J10 Room temperature SR and air temperature SA probes 9 poles connector type LUMBERG 311...

Страница 23: ...r forming near the window and the cold air entering the room through the door while open Do not install the MEC MIX COND in humid environment like in greenhouse because they aren t protected against h...

Страница 24: ...g 15 A A B A E C D A min 200 cm B min 250 cm max 350 cm C min 40 cm D min 50 cm E min 33 cm A min 200 cm B min 250 cm max 350 cm C min 40 cm D min 50 cm E min 33 cm OBJECT DISTANCES MEC MIX C CENTRIFU...

Страница 25: ...ducts These tabs can be used as reference for air duct and exhaust flue design The following tabs show the maximum ducts length acceptable be advised that bends or any other accessory fixed to the duc...

Страница 26: ...m The maximal length of the piping model 35 type C13 is 20m If the total length exceeds 20 m the way should be modified or using the pipes of bigger diameter 80 mm which can reach 40 m of length The...

Страница 27: ...ve mentioned length shall be considered for straight duct Otherwise the pressure drop shall be calculated INSTALLATION TYPE C13 WALL CROSS COAXIAL DUCT 60 100 Fig 20 MAXIMUM LENGHT ALLOWED m Mod 35 45...

Страница 28: ...Mod 35 45 AIR DUCT 34 34 EXHAUST FLUE 34 34 WARNING the above mentioned length shall be considered for straight duct Otherwise the pressure drop shall be calculated MAXIMUM LENGHT ALLOWED m Mod 35 45...

Страница 29: ...ight duct Otherwise the pressure drop shall be calculated WARNING the above mentioned length shall be considered for straight duct Otherwise the pressure drop shall be calculated WARNING the above men...

Страница 30: ...ation The pipe used shall be suitable for connection to the heater considering that heat chemicals and vibration can stress the pipe Avoid the use of copper or iron if not stainless steel which may ru...

Страница 31: ...used for control panel connection to the unit shall be protected against electromagnetic interference by using shielded cables or fixing the control cables far from power cables 7 2 INSTALLATION OF TH...

Страница 32: ...lied the operator shall first replacethegasnozzlewiththeproperonefollowing the procedure described in chapters 8 2 8 2 HOW TO ADJUST THE GAS VALVE or the combustion s parameters Gas valve function The...

Страница 33: ...set the heater at the maximum heat output 6 checktheCO2valueisstillwithintherequiredrange if not adjust the regulator n 8 which refers to the maximum output 7 repeat from step 3 till the CO2 value is...

Страница 34: ...n accordance to the local regulation about gas fired heating system However it is recommended to perform the unit maintenance and general cleaning of the unit exhaust test heat exchanger and air blowe...

Страница 35: ...35...

Страница 36: ...36 A2B Accorroni E G s r l Via d Ancona 37 60027 Osimo An Tel 071 723991 r a Fax 071 7133153 web site www accorroni it e mail a2b accorroni it...

Отзывы: