15

Fig. 3

Connection of the probe double NTC

Brown

Black

Blue

Fig. 4

Measuring of the flame signal

Flame monitoring

The flame detecting device exploits the self rectifying 

property  of  the  flame.  Note  that,  about  safety,  this 

device is more sensitive to the flame during the purging 

ventilation and the ignition steps (negative differential 

switching).

Minimum ionizing current:

 

0.5 μA

System’s temperature probes
- Control probe (SR)

The  control  probe  is  used  for  heat-exchanger 

temperature detection and thus for both fan control and 

safety stop. It is a NTC double sensor type (

standard 

version

) and BRAHMA ST16 sensor is required (see 

picture 3).

Room temperature probe (SA) - optional

The room temperature probe can be used in case the 

remote control panel, equipped with room temperature 

sensor,  is  placed  in  a  separate  room  or  the  room 

temperature shall be related to the outdoor one either. 

See “FUNCTIONS” paragraph for more details.
To this purpose BRAHMA ST07 sensor is required for 

room temperature detecting and BRAHMA SSE for 

outdoor temperature.
Fire damper (STF) - optional By means of this contact 

the status of the eventual fire damper can be detected, 

considering it normally closed. If the contact opens the 

unit’s control interrupts the running cycle and keeps it 

on stand-by. An alarm activates as well and it is shown 

by lighting of the led.
Upon  request,  the  response  of  the  unit  in  case  of 

“contact open” may be changed.

4.4 START-UP INSPECTION

It is strictly recommended to perform the unit inspection 

before the start-up and any time it occurs the unit hasn’t 

been running for a long time or periodic check-up has 

been carried out. Before starting the unit check the 

followings:
- the combustion chamber is free from gas
- if ignition cycle is simulated without gas, check the
  unit lockout occurs after the safety time
- if gas supply is interrupted while the unit is
  running, check the solenoid valve cut-off happens
  within 1 s. After restarting, the unit lockout shall
  occur after a certain number of cycles (see set-up
  parameter)
- operation timing and sequence shall correspond to
  those declared for the type of control unit used
- the flame sensor signal shall be high enough
  (Fig. 4)
- the ignition electrodes shall be properly fixed to
  have clearance equal to 2-4 mm

- the activation of safety devices shall cause the unit
  lockout or the safety stop, in compliance
  with the type of application.

5. CHRONO-THERMOSTAT GA1

5.1 APPLICATION

The  digital  chrono-thermostat  GA1canbeweekly 

Programmed for remote controlling the MEC MIX and 

the room temperature, allowing 3 different temperature 

levels  and  driving  one  or  more  heaters.  It  doesn’t 

require power supply connection nor battery and it 

can control 3 different heaters but they need to be 

equipped with relative interfacing pcb, which shall be 

specified in the order.
To the aim of a flexible management of the facility 

heating,  this  control  panel  allows  of  different 

function modes: manual control; holidays; freezing 

prevention.
The heater control is included in the chrono thermostat 

as well, which manages the power output and the 

automatic alarm resetting.
Here  below  a  detailed  description  of  the  chrono 

thermostat  function  and  the  user  guide  are 

reported.
Picture 5 shows the look of this unit and picture 6 

shows the display of the panel and picture 7 shows 

the performances.
The  use  of  serial  interface  is  possible  by  adding 

BRAHMA 810 unit and dedicated software.

Mirco amper measure

Содержание MEC MIX C

Страница 1: ...1 Wall mounted air heaters with premixed gas burner MEC MIX C condensation and modulation MEC MIX F fixed power TECHNICAL INFORMATION...

Страница 2: ...2...

Страница 3: ...2 WARNING Advises the reader that the next given information is extremely important and must be followed exactly Otherwise proper function of the unit and safety might be jeopardised Paragraphs writt...

Страница 4: ...C MIX C 20 70 20 90 axial 11 3 10 Dimensions MEC MIX F 70 100 axial 11 3 11 Electrical wiring 12 4 CONTROL AND SAFETY 13 4 1 Description 13 4 2 General features 13 4 3 Technical data logical board 13...

Страница 5: ...flow rate the gas supply pressure is within the range shown on the unit s label 2 4 GAS LEAK In case of smell of gas do not operate mobile phone switch or any device that could cause sparking immediat...

Страница 6: ...qualified operator who first shall identify the mode and cause of failure The premix blower is placed in front of the burner and ensure the proper air gas ratio at any condition Iftheairintakeductort...

Страница 7: ...7 3 3 TABLE OF TECHNICAL DATA MEC MIX C CONDENSATION AXIAL 3 4 TABLE OF TECHNICAL DATA MEC MIX F AXIAL...

Страница 8: ...8 3 5 TABLE OF TECHNICAL DATA MEC MIX C CONDENSATION CENTRUFUGE 3 6 TABLE OF TECHNICAL DATA MEC MIX F CENTRUFUGE...

Страница 9: ...nly in the Model MEC MIX C 747 120 3 7 DIMENSIONS Serie MEC MIX C condensation model 20 35 20 45 centrifuge fans Serie MEC MIX F model 35 50 centrifuge fans Values in mm gas connection air inlet exhau...

Страница 10: ...MIX C condensation model 20 35 20 45 axial fans Serie MEC MIX F model 35 50 axial fans The condensate drain is present only in the Model MEC MIX C Values in mm TOP VIEW gas connection exhaust outlet...

Страница 11: ...Dimensions Serie MEC MIX C condensation model 20 70 20 90 centrifuge Serie MEC MIX F model 70 100 centrifuge Values in mm gas connection gas connection air inlet air inlet exhaust outlet exhaust outl...

Страница 12: ...12 3 10 Dimensions Serie MEC MIX C condensation model 20 70 20 90 axial Serie MEC MIX F model 70 100 axial Values in mm gas connection gas connection air inlet air inlet exhaust outlet exhaust outlet...

Страница 13: ...on electrode EF Premix blower EV1 First stage valve EX Cascade unit connection F1 Fuse 1 6 3A F2 Fuse 2 6 3A FAN1 Air motor fan 1 FAN2 Air motor fan 2 GA1 Chrono thermostat ION Detecting electrode M1...

Страница 14: ...ermostatGA1 air delivery temperature and safety control by means of a double NTC ST16 temperature probe air delivery temperature control by means of a double NTC ST08 temperature probe possibility of...

Страница 15: ...out Before starting the unit check the followings the combustion chamber is free from gas if ignition cycle is simulated without gas check the unit lockout occurs after the safety time if gas supply i...

Страница 16: ...esameprocedure for setting T1 Note that anyway T2 shall be higher than T1 Which shall be higher thanT0 otherwise a beep sound advises that the value is not allowed However each temperature shall be wi...

Страница 17: ...parameters Then press PROG to return to the selection of the day of the week By holding pressed the OK button the lighted day programme will be copied to the next day of the week Press AUTO to leave...

Страница 18: ...n via Open Therm it is possible to visualize the value closed to indicator tou By which the set point Tset can be loaded and the outdoor temperature displayed The Tset value is used to calculate the h...

Страница 19: ...bles connection then put the terminal back into the slot The communication protocol allows of 50 m maximum cable length and Ohm resistance of each cable shall not exceed 5 Ohm In case of proximity to...

Страница 20: ...hermostat ENCRONO type GA1 EF Fan motor of the burner FAN Fan motor of treated air ACC1 Auxiliary ignition transformer EV1 First stage valve SR Temperature control sensor STF Fire damper SA Room tempe...

Страница 21: ...WIRING DIAGRAM FOR CASCADES CONNECTIONS OF MULTIPLE DEVICES VIA OPEN THERM Fig 13 NOTE 1 The cascade connection is possible with a chrono thermostat too This configuration is not used in the versions...

Страница 22: ...e MOLEX 2478 J9 Modulator power supply MOD Connector 2 poles type LUMBERG 3114 terminals type LUMBERG 3111 01 L J10 Room temperature SR and air temperature SA probes 9 poles connector type LUMBERG 311...

Страница 23: ...r forming near the window and the cold air entering the room through the door while open Do not install the MEC MIX COND in humid environment like in greenhouse because they aren t protected against h...

Страница 24: ...g 15 A A B A E C D A min 200 cm B min 250 cm max 350 cm C min 40 cm D min 50 cm E min 33 cm A min 200 cm B min 250 cm max 350 cm C min 40 cm D min 50 cm E min 33 cm OBJECT DISTANCES MEC MIX C CENTRIFU...

Страница 25: ...ducts These tabs can be used as reference for air duct and exhaust flue design The following tabs show the maximum ducts length acceptable be advised that bends or any other accessory fixed to the duc...

Страница 26: ...m The maximal length of the piping model 35 type C13 is 20m If the total length exceeds 20 m the way should be modified or using the pipes of bigger diameter 80 mm which can reach 40 m of length The...

Страница 27: ...ve mentioned length shall be considered for straight duct Otherwise the pressure drop shall be calculated INSTALLATION TYPE C13 WALL CROSS COAXIAL DUCT 60 100 Fig 20 MAXIMUM LENGHT ALLOWED m Mod 35 45...

Страница 28: ...Mod 35 45 AIR DUCT 34 34 EXHAUST FLUE 34 34 WARNING the above mentioned length shall be considered for straight duct Otherwise the pressure drop shall be calculated MAXIMUM LENGHT ALLOWED m Mod 35 45...

Страница 29: ...ight duct Otherwise the pressure drop shall be calculated WARNING the above mentioned length shall be considered for straight duct Otherwise the pressure drop shall be calculated WARNING the above men...

Страница 30: ...ation The pipe used shall be suitable for connection to the heater considering that heat chemicals and vibration can stress the pipe Avoid the use of copper or iron if not stainless steel which may ru...

Страница 31: ...used for control panel connection to the unit shall be protected against electromagnetic interference by using shielded cables or fixing the control cables far from power cables 7 2 INSTALLATION OF TH...

Страница 32: ...lied the operator shall first replacethegasnozzlewiththeproperonefollowing the procedure described in chapters 8 2 8 2 HOW TO ADJUST THE GAS VALVE or the combustion s parameters Gas valve function The...

Страница 33: ...set the heater at the maximum heat output 6 checktheCO2valueisstillwithintherequiredrange if not adjust the regulator n 8 which refers to the maximum output 7 repeat from step 3 till the CO2 value is...

Страница 34: ...n accordance to the local regulation about gas fired heating system However it is recommended to perform the unit maintenance and general cleaning of the unit exhaust test heat exchanger and air blowe...

Страница 35: ...35...

Страница 36: ...36 A2B Accorroni E G s r l Via d Ancona 37 60027 Osimo An Tel 071 723991 r a Fax 071 7133153 web site www accorroni it e mail a2b accorroni it...

Отзывы: