background image

26 

WARNING: When you first install and start-up the unit make sure that the unit is working properly in both cooling 

and heating modes. 

8.1

 

POWER-ON OF THE UNIT 

For powering on the appliance, rotate the outer handle of the disconnector to the ON position (indicated with "I"). 

The display on the machine is turned on only if the phase sequence is correct (verification to be done during initial startup). 

Between a shutdown and subsequent power on, wait a minimum time of 1 minute. 

9

 

INDICATIONS FOR THE USER 

It’s important to take note of the identification data of the unit in order to provide them to the Technical Assistance Service in case 

of assistance request. 

The identification plate fixed on the unit shows the technical specifications and the performance of the equipment. 

In case of manumission, removal or deterioration, please ask a duplicate to the Technical Assistance Service. 

The manumission, removal or damaging of the nameplate makes difficult any operation of installation, 

maintenance and spare parts request. 

It is recommended to keep track of assistance operations done on the unit; this will make easy searching any troubleshooting. 

In case breakdown or malfunction situations: 

check the type of alarm to communicate it to the service center;

contact an authorized service center;

if required by the service center, turn off the unit immediately without resetting the alarm;

Ask the use of original spare parts.

10

 

SHUTDOWNS FOR LONG PERIODS

• Turn off the unit by placing the switch of each unit to "OFF" position.

• Close the water valves.

• Place the general differential circuit breaker to "OFF" position.

If the temperature drops below 0°C there is a serious risk of frost: add a mixture of water and glycol in the plant, 

otherwise drain the hydraulic circuits of the plant and of the heat pump. 
WARNING: if the ambient temperature becomes lower than -20°C (value that is permitted only on i-HP LT series), in 

case the unit is turned off and powered down also for short periods, it’s compulsory to drain the plant and the 

hydraulic circuit of the unit by the mixture of water and glycol. Otherwise, the circulator may be irreversibly 

damaged. 

WARNING: with water temperatures below than +5°C, although the transient operation is not guaranteed regarding 

the limits set out in  Paragraph  20.4. Before you turn the unit on after a long off period, make sure that the 

temperature of the mixture of water and glycol is higher than or at least equal to +5°C. 

11

 

MAINTENANCE AND PERIODICAL CONTROLS 

If the temperature drops below 0°C there is serious danger of frost: add a mixture of water and glycol in the plant, 

otherwise drain the hydraulic circuits of the plant and of the heat pump. 
WARNING: if the ambient temperature becomes lower than -20°C (value that is permitted only on i-HP LT series), in 

case the unit is turned off and powered down also for short periods, it’s compulsory to drain the plant and the 

hydraulic circuit of the unit by the mixture of water and glycol. Otherwise, the circulator may be irreversibly 

damaged. 

WARNING: the operation, although it was transient, with water temperatures below +5°C is not guaranteed on the 

basis of the limits set out in Paragraph 20.4. Before you turn the unit on after a long off period, make sure that the 

temperature of the mixture of water and glycol is higher than or at least equal to +5°C. 

WARNING: All the operations described in this chapter HAVE TO BE CARRIED OUT BY TRAINED STAFF ONLY. Before 

any operation or before entering the inner components of the unit, be sure that the power supply is disconnected. 

The compressor’s heads and discharge pipes are usually at high temperature levels. Be very careful when operating 

in their surroundings. Aluminium coil fins are very sharp and can cause serious wounds. Be very careful when 

operating in near them. After maintenance operations, re-install the cover panels, and fix them by means of screws. 
The refrigerant circuits must not be filled with different gas other than that indicated on the nameplate. The use of a 

different refrigerant can cause severe damage to the compressor. 
It’s forbidden to use oils other than those specified in this manual. The use of different oil can cause serious damage 

to the compressor. 
WARNING: MOVING PARTS, RISK OF DEATH. 

Disconnect the power supply and ensure that the fan is stopped before opening the front panel. 

The temperatures of heads and exhaust piping of the compressor are usually high. 

Pay attention to the surfaces of the driver boards heat sinks (see Chapter 

Errore. L'origine riferimento non è stata 

trovata.

), which can become very hot. 

Be careful when working near condensing coils. 

The aluminum fins are very sharp and can cause serious injuries. 

Содержание HPE 35

Страница 1: ...TECHNICAL INFORMATION HPE 25 70 HPE LT 25 50 INVERTER Air water inverter heat pumps with axial fans and steam injection versions HPE 25 70 HPE LT 25 50 INVERTER...

Страница 2: ...m the application of Directive 2014 68 UE Reference to Art I paragraph 2 point f L attrezzatura a pressione rientra nella CAT I L unit quindi esente dall applicazione della normativa PED 2014 68 UE Ri...

Страница 3: ...3 LOCATION AND MINIMUM TECHNICAL CLEARANCES 14 7 4 DIMENSIONS 15 7 5 HYDRAULIC CONNECTIONS 15 7 5 1 Characteristics of water of the plant circuit 16 7 5 2 Hydraulic circuit type 16 7 5 3 Handbook 17...

Страница 4: ...D PRESSURE OF THE UNIT WITH INTEGRATED CIRCULATOR 32 16 CIRCULATOR S CURVES 33 16 1 MODELS HPE 25 35 33 16 2 MODEL HPE 50 50F 33 16 3 MODEL HPE 60 34 16 4 MOD HPE 60 HPE 70 34 16 5 CIRCULATOR CHARACTE...

Страница 5: ...g or transcription errors The customer must keep any updated copy of the manual or parts of it delivered by the manufacturer as an attachment to this manual The company is available to give any detail...

Страница 6: ...ce s health and safety including 89 391 CEE 89 686 CEE 89 655 CEE 2009 104 CE 86 188 CEE and 77 576 CEE directives Every employer shall implement such norms and ensure that workers to respect them It...

Страница 7: ...or each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained respirator The vapors are heavier than air and can cause suffocation by re...

Страница 8: ...diameter is 7 94 mm the thickness of the aluminium fins is 0 12 mm The pipes are mechanically expanded into the aluminium fins in order to improve the heat transfer coefficient The geometry of this he...

Страница 9: ...gy provide maximum efficiency regarding the standard units with scroll compressors The EVI technology consists of injecting the refrigerant vapour at the intermediate stage of the compression process...

Страница 10: ...which identify the sizes versions and factory mounted accessories no 1 fixed digits equal to 0 for now it is not used 0110516 CT1 TA IV CI KA GI FAN SIL TR 00 MC FATHER CODE SIZE VERSION 0110516 CT T...

Страница 11: ...Module not present 1 GI Module present 2 Modbus communication protocol 4 3 Modbus communication protocol and GI module present 0 DC fan 0 Not silenced 1 Silenced 2 Super silenced 0 Coil without treatm...

Страница 12: ...provides thermo acoustic insulators on compressors 2 The super silenced unit with SSL accessory provides thermo acoustic insulators on compressors and a special diffuser installed on the fan which re...

Страница 13: ...this manual can create dangerous situations After receiving the unit immediately check its integrity The unit left the factory in perfect condition any eventual damage has to be questioned to the car...

Страница 14: ...CLEARANCES All i HP models are designed for outdoor installations any cover over the unit or locating near trees even if they partially cover the unit has to be avoided in order to allow the air recir...

Страница 15: ...Make sure that when designing the pipe length and diameter do not exceed the maximum head loss on the plant side please see the technical data available head pressure WARNING An air vent valve should...

Страница 16: ...h lack of washing of the system or lack tampering of the Y filter the company reserves the right not to pass the replacement of the component as a guarantee 7 5 1 Characteristics of water of the plant...

Страница 17: ...ter on the charging topping up pipe must be suitably pre filtered from any impurities and suspended particles Make sure that you have installed a cartridge filter removable WARNING Before beginning th...

Страница 18: ...CIRCULATOR ON BOARD UNIT M AXIAL FAN PV PRESSURE CHECK VALVE CP CAPILLARY SE OUTDOOR AIR TEMPERATURE SENSOR V ON OFF VALVE WITH SOLENOID 7 6 2 Refrigerant circuit of HPE 50 model EEV ELECTRONIC EXPANS...

Страница 19: ...VERTER COMPRESSOR P CIRCULATOR ON BOARD UNIT M AXIAL FAN PV PRESSURE CHECK VALVE 7 6 4 Refrigerant circuit of HPE 50F model EEV ELECTRONIC EXPANSION VALVE NRV NO RETURN VALVE ST COMPRESSOR INLET TEMPE...

Страница 20: ...TEMPERATURE INJP INJECTION PRESSURE TRANSDUCER INJ INJECTION VALVE 7 7 ELECTRICAL CONNECTIONS Check if the power supply circuit meets the unit s electric nominal data tension phases frequency reporte...

Страница 21: ...not ground the unit with pipes or lightning rods A poor grounding of the unit can result in electrocution Warning Electrostatic discharges can damage the electronic components before performing any w...

Страница 22: ...lectric box is opened i HP 0125 i HP 0135 i HP 0250F i HP 0250 On board terminal block and user s terminal block Support boards Transformer Driver board one for each inverter compressor Disconnecting...

Страница 23: ...Ph N PE 400V 50Hz The power cables should be brought inside the electrical panel of the unit and connected to the disconnecting switch inside the electric panel itself in the bottom at the left as sho...

Страница 24: ...tput 230Vac 50Hz 5A resistive 1A inductive 1 2 Secondary circulator GNDR Serial communication Modbus ground reference connection terminal for remote supervision R Serial communication Modbus signal co...

Страница 25: ...l indications on unit labels are respected Check if all power cables are properly connected and all terminals are tightly fixed Check if the electrical connections are performed according to the norms...

Страница 26: ...regarding the limits set out in Paragraph 20 4 Before you turn the unit on after a long off period make sure that the temperature of the mixture of water and glycol is higher than or at least equal t...

Страница 27: ...to direct the water jet perpendicular to the surface of the condenser for not to bend the aluminum fins Avoid hitting the condenser with the water hose It is recommended not to place your thumb on th...

Страница 28: ...ion 12 1 Residual risks In this paragraph we point out the most common situations that could give rise to risks that cannot be eliminated by the manufacturer during the design phase of the project Ris...

Страница 29: ...98 1 97 Load losses user s side heat exchanger 4 kPa 33 46 28 Energetic class Water temp 35 C 55 C Classe A A A A A A Compressor Type Scroll DC Inverter Scroll DC Inverter Scroll DC Inverter Rfrigeran...

Страница 30: ...ger 4 kPa 27 74 25 Energetic class Water temp 35 C 55 C Class A A A A A A Compressor Type Scroll DC Inverter Scroll ON OFF Scroll DC Inverter Scroll DC Inverter Rfrigerant oil type FVC68D FVC68D FVC68...

Страница 31: ...W W 3 98 4 17 3 90 Water flow rate 1 L s 1 00 1 01 1 36 1 37 1 73 1 74 Load losses user s side heat exchanger 1 kPa 32 37 20 Heating Heating capacity 3 kW 24 15 24 02 32 50 32 36 47 78 47 58 Power inp...

Страница 32: ...in apex 1 2 3 and 4 refer to the instantaneous power according to EN 14511 The declared data stated in the apex 6 is determined according to the UNI EN 14825 WARNING The minimum temperature allowed fo...

Страница 33: ...circulator with the possibility of choice between constant P and variable P 16 2 MODEL HPE 50 50F Configuration with integrated circulator control via 0 10 volt analogic signal Configuration with auto...

Страница 34: ...0 23 Because of the circulators have got similar prevalence curves to those integrated please refer to Paragraph 15 for plant designing 17 HEAD LOSS CURVES OF THE HYDRONIC CIRCUIT We obtain the press...

Страница 35: ...1L s we obtaine 1 4kPa valve head loss 30kPa hydronic circuit head loss 34 9 kPa total internal head loss 19 ACCESSORIES TO REDUCE THE NOISE LEVEL 19 1 SL The silenced unit with SL accessory is provid...

Страница 36: ...on systems the proper flow rate for getting the best performance from your unit can be found at maximum speed of the circulator using the pressure gauges for controlling the pressure difference betwee...

Страница 37: ...30 C Water outlet temperature standard injection version Min 25 C Max 58 C 59 C Heat pump mode for sanitary hot water Ambient temperature standard injection version Min 15 25 C Max 50 38 C Ambient te...

Страница 38: ...ater flow rate correction factor PDCF Pressure drops correction factor The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation without gly...

Страница 39: ...A2B ACCORRONI E G VIA ANCONA 37 60027 OSIMO AN www accorroni it a2b accorroni it...

Страница 40: ...tolo puramente indicativo la A2B Accorroni E G S r l si riserva di apportare eventuali modi che senza alcun preavviso web site www accorroni it e mail a2b accorroni it A2B Accorroni E G s r l Via d An...

Отзывы: