1.9 TECHNICAL DATA TABLE
100
200
300
400
600
800
max.
2.830
4.130
5.640
7.050
9.770
12.330
med.
2.530
3.680
5.140
6.290
8.860
11.230
min.
2.220
3.210
4.670
5.230
7.480
10.580
Max water capacity
243
355
485
606
825
1.060
Max charge loss water 70 °C
1,50
3,00
7,30
11,45
23,50
33,00
max.
1.620
2.200
3.370
4.050
5.900
6.060
med.
1.450
1.830
3.070
3.640
5.270
5.610
min.
1.270
1.680
2.790
3.240
4.620
5.090
Max charge loss water 50 °C (E )
kPa
max.
1,03
2,27
6,45
8,90
22,25
26,50
max.
1.860
2.420
3.380
4.100
5.930
6.530
med.
1.710
2.240
3.160
3.800
5.510
6.270
min.
1.540
2.060
2.970
3.490
4.630
6.070
1 row battery water capacity
160
208
291
352
516
559
Max charge loss water 1 row battery
4,50
7,60
16,00
26,50
46,00
51,00
max.
1.150
1.630
2.730
3.110
4.660
5.140
med.
1.030
1.380
2.410
2.880
4.230
4.740
min.
880
1.270
2.190
2.630
3.870
4.360
max.
930
1.320
2.220
2.550
3.640
4.150
med.
830
1.110
1.940
2.180
3.220
3.670
min.
700
995
1.720
1.970
2.850
3.340
Max cooling water capacity
192
275
460
552
790
868
Max charge loss cooling water (E)
1,22
2,70
7,65
10,55
26,45
31,00
max.
210
340
450
560
760
1.000
med.
180
280
400
485
630
890
min.
150
240
340
434
540
780
Number of fans
max.
30,6
39,5
40,7
42,3
44,7
50,0
med.
27,7
34,9
37,4
39,4
41,8
48,1
min.
22,9
31,9
34,2
36,7
37,1
45,5
max.
39,1
48,0
49,2
50,8
53,2
58,5
med.
36,2
43,4
45,9
47,9
50,3
56,6
min.
31,4
40,4
42,7
45,2
45,6
54,0
230 V / 1 / 50 Hz
Max motor potential (E )
34
45
58
77
104
123
Max current absorption
0,15
0,20
0,25
0,34
0,46
0,59
W eight
17,0
19,0
22,0
24,6
28,8
30,2
(E ) = E urovent certified. Data refer to the following working conditions:
S ummer cooling: outside air temperature: 27 °C b .s., 19 °C b .u.
W ater temperature: intak e 7 °C, outgoing 12 °C at max speed
W inter heating: outside air temperature: 20 °C
W ater temperature: intak e 70 °C,
∆
T 10 °C at max speed
(with intak e water at 50 °C the same water capacity as for cooling at max speed)
Unit of mes.
Heat potential
(incom ing w ater 70°C)
W
l/h
kPa
Heat potential (E)
(incom ing w ater 50°C)
W
Heat potential for
supplementary 1 row battery
W
l/h
kPa
Total cooling potential (E)
W
Air capacity (E)
m
3
/h
Sensitive cooling potential
W
l/h
kPa
2
Noise levels
dB (A )
Noise potential (E )
dB (A )
n°
1
Electric power
W
A
kg
Содержание FR-FC-FCO-FCR Series
Страница 1: ...Technical Information FR FC FCO FCR 100 800 Fan coil units series FR FC FCO FCR Models100 800...
Страница 9: ...pag 8 1 8 DETAILED VIEW Vertical FR version with cover Fig 3 modd 100 200...
Страница 10: ...pag 9 1 8 DETAILED VIEW Horizontal FC version with cover Fig 4 modd 100 200...
Страница 11: ...pag 10 1 8 DETAILED VIEW Vertical FCO version with casing Fig 5 modd 100 200...
Страница 12: ...pag 11 1 8 DETAILED VIEW Horizontal FCR version with casing Fig 6 modd 100 200...
Страница 32: ...pag 31...
Страница 33: ...Fan coil units series FR FC FCO FCR Technical details Cod 26209501 IT Rev 1 07 04 03...
Страница 34: ......