pag. 28

those parts.

- do not remove the filter without first

disconnecting the electricity supply and
allowing the internal parts to cool.

- in places where it is advisable to block

access to the control panel (public places,
schools etc.), the flaps in version F (vertical
with cover) can be blocked using the screws
and screw covers provided.

7. STARTING UP

7.1 CHECKS

Before starting up the fan heater, make sure the
installer has fully completed all the necessary
installation procedures.

7.2 SWITCHING ON

7.2.1 (references to control panel functions refer
to fig. 14)

a) check that the electricity supply is properly

connected and proceed as follows:
- Version 1 controls

Turn switch (A) to the "ON" position.
If there is one (on the electronic or
microprocessor thermostats) put the
summer/winter switch (B) in the positions
suitable for the cycle in course (pointing up
= summer, down = winter).

- Version 2 controls

Turn switch (B) to the position suitable for
the cycle in course (

 = summer, 

  =

winter).

b) If there is one (on the electronic or

microprocessor thermostats), turn the air tem-
perature thermostat (C) to the temperature
required. The indicator light (E) will show the
function according to the characteristics of
the different control panels.

c) Select the fan speed using (D). If there is a trip

thermostat (optional extra), the fan will start
up only if the internal water temperature in the
exchanger is higher than a pre-determined
level. In this case, wait until the system is
ready.

e) Consult the specific instructions for the actual

control panel in use to see any additional
characteristics and likewise for any optional
accessories which have been installed.

7.3 SWITCHING OFF

7.3.1 7.3.1 When turning off the fan heater, it is
not necessary to touch the temperature control
if there is one, but to proceed as follows:

- Version 1 controls

Turn switch (A) to "OFF"

- Version 2 controls

Turn switch (B) to "OFF"

7.3.2 To turn off the heater for a prolonged period:

a) Stop the heat generator or cooling system in

the plant according to the specific instructions.

b) According to the control panel version in use,

turn switch (A) or  (B) to the "OFF" position.

c) Disconnect the electric supply from the heater

switch.

d) When the system is not used during periods

when there are low outside temperatures,
ensure there is no risk of pipes freezing up by
consulting the installer.

8.   MAINTENANCE

8.1

NORMAL MAINTENANCE
PROCEDURES FOR THE USER

WARNING! Any procedure which is not
explicitly mentioned in this chapter should
be carried out by specialised personnel.

8.1.1 Cleaning external parts

The external parts of the heater should be cleaned
at least every two months, always after
disconnecting the electricity supply. Use a damp
cloth and remove any dust from the air outlet with
a brush. WARNING! Do not use water sprays
to clean the appliance.

Check that the fan is working well and that air is
coming out of the air outlet grille correctly.

8.1.2 Cleaning the filter

The air filter should be cleaned before every
operational season, or, if the fan heater is in a
dusty environment, at least once a month.

WARNING! Always disconnect the heater
from the electricity supply and allow the fan
motor to cool before proceeding to remove
the filter.

The following instructions relate to F - FR versions
with covers.  For encased versions with their
appropriate panelling, refer to the system used
by the planner and/or installer.

Loosen and extract the filter by turning the fixing
screws on the plastic filter holders and turning
them outwards.

Clean the filter, preferably with compressed air,
by blowing in the opposite direction from the
intake, or use a vacuum cleaner.  If necessary,

Содержание FR-FC-FCO-FCR 100

Страница 1: ...Technical Information FR FC FCO FCR 100 800 Fan coil units series FR FC FCO FCR Models100 800...

Страница 2: ...refully considered 3 Accorroni S r l is not responsible for any damage caused by the improper use of the appliance by any use different from the one designated or by any incomplete or approximate conf...

Страница 3: ...2 4 Data control 22 2 5 Instruction use 22 3 INSTALLATION 23 3 1 Positioning 23 3 2 Installation procedures 23 4 STARTING UP 25 4 1 Checks 25 4 2 Starting up 25 5 REPLACING COMPONENTS 26 5 1 Fan grou...

Страница 4: ...and in the following versions FR Vertical with casing For wall installation under windows or in anyotherfreespaceorpositionwhichoffers technical or functional advantages FC Horizontal with casing For...

Страница 5: ...indicator light The control panel is set up for connection of a thermostat suppliedseparately whichmeans that in the heating mode the fan is activated only when the temperature of the water in the he...

Страница 6: ...ry condensation collection tray for use with F FC vertical versions Pair of foot supports for F version with cover Frontal grille support for F FR versions with cover 90 air intake system for FC FCR v...

Страница 7: ...2 G exit 1 2 G entry B 220 48 172 C 150 360 93 D D 1 7 SIZE AND MASS Mod 100 200 300 400 600 800 A 760 870 980 1 090 1 310 1 310 B 440 550 660 770 990 990 C 460 570 680 790 1 010 1 010 D 644 754 864...

Страница 8: ...0 600 800 A 480 590 700 810 1 030 1 030 B 440 550 660 770 990 990 VERTICAL FC VERSION WITH CASING HORIZONTAL FCR VERSION WITH CASING 220 142 B A 525 144 45 477 274 1 2 G exit 1 2 G entry 525 A 1 2 G e...

Страница 9: ...pag 8 1 8 DETAILED VIEW Vertical FR version with cover Fig 3 modd 100 200...

Страница 10: ...pag 9 1 8 DETAILED VIEW Horizontal FC version with cover Fig 4 modd 100 200...

Страница 11: ...pag 10 1 8 DETAILED VIEW Vertical FCO version with casing Fig 5 modd 100 200...

Страница 12: ...pag 11 1 8 DETAILED VIEW Horizontal FCR version with casing Fig 6 modd 100 200...

Страница 13: ...5 03 3 row heat exchange system 04 complete fan system 05 autotransformer 08 fan motor 09 fan casing fan Components Horizontal FC version with cover fig 4 01 cover with grille 02 variation G with fron...

Страница 14: ...790 868 Max charge loss cooling water E 1 22 2 70 7 65 10 55 26 45 31 00 max 210 340 450 560 760 1 000 med 180 280 400 485 630 890 min 150 240 340 434 540 780 Number of fans max 30 6 39 5 40 7 42 3 44...

Страница 15: ...0 900 Portata acqua l h Resa termica kW 20 30 40 50 60 70 Le rese temiche del grafico corrispondono alla massima velocit Per conoscere le rese alle altre velocit moltiplicare i valori per i seguenti c...

Страница 16: ...0 50 60 70 Le rese temiche del grafico corrispondono alla massima velocit Per conoscere le rese alle altre velocit moltiplicare i valori per i seguenti coefficienti V med 0 91 V min 0 83 T T acqua ent...

Страница 17: ...0 70 Le rese temiche del grafico corrispondono alla massima velocit Per conoscere le rese alle altre velocit moltiplicare i valori per i seguenti coefficienti V med 0 93 V min 0 86 T T acqua entrante...

Страница 18: ...iply by coefficient K FR FC FCO FCR 100 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 1 1 1 2 1 3 1 4 1 5 1 6 1 7 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 Portata kg h P kPa FR FC FCO FCR 200 0 6...

Страница 19: ...mperatures multiply by coefficient K FR FC FCO FCR 400 2 3 4 5 6 7 8 9 10 11 12 13 14 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 Portata kg h P kPa FR FC FCO FCR 300 1...

Страница 20: ...loss at different temperatures multiply by coefficient K FR FC FCO FCR 600 4 6 8 10 12 14 16 18 20 22 24 26 28 30 300 350 400 450 500 550 600 650 700 750 800 850 Portata kg h P kPa FR FC FCO FCR 800 1...

Страница 21: ...nk ro red v green vi purple WARNING Install a sectioning device with contact opening of at least 3 mm on the appliance and protect the electrical wiring with 2A 250 V fuses Variation for connecting 80...

Страница 22: ...URSCODES ar orange az blue b white g v yellow green gi yellow gr grey m brown n black r pink ro red v green vi purple ELETRONICTHERMOSTAT1 Fan Summer Winter ELETRONICTHERMOSTAT2 Water thermostat Outsi...

Страница 23: ...engineer who can guarantee correctcomplianceandexecution of all necessary operations 2 3 TRANSPORT AND HANDLING The fan heater comes in a standard cardboard pack with internal expanded polystyrene or...

Страница 24: ...ion units F FC must be placed at a height of about 10 cm from the floor so that air is collected correctly by the fan heater There must be the same distance betweenthewallandthebackoftheappliance for...

Страница 25: ...at screwdriver or a size 8 hexagonal spanner on the one in the highest position in the circuit Close the bleed valves and check carefully that there have been no losses at the various junctions Connec...

Страница 26: ...e various types to choose from Carry out the mounting operations for the specific control panel according to the model chosen and the type of installation on the side of the appliance or remote on a w...

Страница 27: ...ing the filter cover and any panels where the heater is installed in a casing For vertical versions F FC take the rubber condensation disposal joint off from under the tray Disconnect the electrical w...

Страница 28: ...6 2 RECOMMENDATIONS IMPROPER USE WARNING To ensure correct and safe use of the fan heater do not use the heater for any purpose other than that for which it was designed do not lean on jump over or s...

Страница 29: ...it is not necessary to touch the temperature control if there is one but to proceed as follows Version 1 controls Turn switch A to OFF Version 2 controls Turn switch B to OFF 7 3 2Toturnofftheheaterfo...

Страница 30: ...he minimum and to keep the fan heater in perfect workingorder thusensuringmaximumefficiency at the lowest costs it is advisable to have a general check carried out by a specialist at the start of ever...

Страница 31: ...FC FCO FCR Models 100 200 300 400 600 800 With reference to the above appliances Accorroni S r l D E C L A R E S thattheseproducts conformtothe98 37EECdirectiveregardingmachinery andalsoconformtothef...

Страница 32: ...pag 31...

Страница 33: ...Fan coil units series FR FC FCO FCR Technical details Cod 26209501 IT Rev 1 07 04 03...

Страница 34: ......

Отзывы: